1112/24B and 1112/24BA Ionization

Smoke Detectors

INSTALLATION AND MAINTENANCE INSTRUCTIONS

A Division of Pittway

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

Before Installing

Please thoroughly read System Sensor Manual I56-407,

Guide for Proper Use of System Smoke Detectors,

 which

provides detailed information on detector spacing,
placement, zoning, wiring, and special applications.
Copies of this manual are available at no charge from
System Sensor. (For installation in Canada, refer to
CAN/ULC-S524-M91, 

Standard for the Installation of

Fire Alarm Systems

, and CEC Part 1, Sec. 32.)

NOTICE: 

This manual should be left with the owner/user

of this equipment.

IMPORTANT: 

This detector must be tested and maintained

following NFPA 72 requirements. The detector should be
cleaned at least once a year.

Specifications

Diameter:

5.5 inches (140 mm)

Height (including adapter bracket): 1.7 inches (43 mm)
Weight:

5.3 oz. (150 g)

Operating Temperature Range:

32

°

 to 120

°

F (0

°

 to 50

°

C)

Operating Humidity Range:

10% to 93% Relative Humidity, Noncondensing

Latching Alarm:

Reset by momentary power interruption

Relay Contact Ratings–
Resistive or inductive (60% power factor) load
Form A:

0.5A @ 30VAC/DC

Electrical Ratings

System Voltage nominal:

12 or 24 VDC

Minimum:

8.5 VDC

Maximum:

35 VDC

Maximum Ripple Voltage:

30% of nominal voltage (peak to peak)

Reset Voltage:

0.8 VDC minimum

Standby Current:

50 

µ

A maximum

Alarm Current:

17 mA typical, 23 mA maximum @ 12V
19 mA typical, 25 mA maximum @ 24V

Reset Time:

0.3 seconds maximum

Start-up Time:

30 seconds maximum (after 60 second reset)

General Description

The 1112/24B and 1112/24BA are 4-wire ionization
smoke detectors that use a state-of-the-art sensing
chamber. These detectors are designed to provide open
area protection.

Installation of these detectors are simplified by the use
of an adapter bracket and a plug-in screw terminal block
that can be prewired to the system, allowing the detec-
tors to be easily installed or removed for cleaning. The
detector sensitivity can be tested in place using the
MOD400R Test Module.

An LED on the detector provides local visual indication of
the detector status. If power is applied to the detector, and
it is functioning normally in standby, the status LED blinks
every five seconds. The LED also latches on in alarm.

The 1112/24B also features visual indication that mainte-
nance is required; if the sensing chamber drifts out of its
sensitivity limits, the LED ceases to blink.