of the frequency converter is higher than 3.5 mA AC or 10 mA DC, a fixed protective 
earthing connection must be used. In addition:   

1)

 

The  cross-sectional  area of  the  protective  earthing  wire  should be copper  wires 
of at least 10mm

2

 or aluminum wires of at least 16mm

2

2)

 

Automatically  cut  off  the  power  when  the  protective  earthing  conductor  is 
interrupted. 

3)

 

Replace the original protective earthing conductor with a spare one that has the 
same cross-sectional area. 

 

Grounding Directions: 

1)

 

The  length  of  grounding  wires  should  comply  with  the  electrical  equipment 
regulations; the shorter the better. 

2)

 

The  grounding  wire  of  the  driver  should  be  grounded  separately  with 
high-current loads such as electric welders or high frequency motors.   

3)

 

Please refer to the picture below when the controller is grounded with multiple 
electrical control devices. Do not make it a loop. 

(a) O                                    (b) O                                      (c) X 

(a) 良

(b) 良

(c) 不良

 

 