background image

 

 
 
Suppose  a  client  wants  to  drive  four  1.2kW  motors  with  1kW*4  Servo  Drive 
Embedded Controller, it means the gross power should supply at most 4.8kW. Then 
we reverse the formula and set the power factor at 0.7. If only Servo Drive Embedded 
Controllers  are  used,  the  capacity  should  be  at  least  4.8/0.7=6.85kVA.  In  addition, 
10%  of  the  backup  capacity  should  be  considered.  Thus,  7.5kVA  would  be  more 
suitable. Moreover, if an inverter is used, and the power is supplied by an isolation 
transformer, the capacity of the inverter should be considered. 

 

Do not connect a cable with other cables to extend the length. It might cause signal 
error or malfunction. 

 

Please crimp or weld the wire connections while doing the wirings. 

 

If the servo line in use is not a standard Syntec cable, please verify all the terminals 
connected  properly  before  power-on.  Wrong  wirings  will  lead  to  controller  output 
command errors and malfunctioning.

 

 

The +5V output capacity of the encoder is 500mA and is only for a single encoder. 

Do not connect it with other loads or it might cause error due to the lack of  driving 
force.

 

 

Do  not  use  counterfeit  terminal  strips.  Those terminal  strips  cannot  provide  overall 

protection  for  the  system.  The  quality  is  also  not  guaranteed  and  tend  to  cause 
electrical control problems of the machine tools.

 

 

The wiring of the driver and the motor cannot be pulled too tightly.   

 

Do not stake on top.   

 

The six power lines, R, S, T and U, V, W, should not be close to other signal lines, 

and should be at least 30 cm apart. 

 

After cutting off the power, the capacitor of the driver still contains large amount of 

charge.  Do  not  touch  the  6  power  lines,  R,  S,  T  and  U,  V,  W,  until  the  power 
indicator goes out. 

 

If  the  encoder  line  should  be  longer,  please  use  twisted-pair  and  signal  cable  with 

isolated  ground.  Do  not  extend  it  over  20  meters.  In  case  of  extensions  over  20 
meters, please double the wire diameter of signal cables to reduce signal attenuation. 

 

To  ensure  the  quality  of  communication,  the  USB extension cord in  use  should  not 
exceed 5 meters, and do not use for charging purposes to avoid controller failure. 

 

The drive is fragile. Please handle it with care.   

 

Do not allow conductive foreign matter such as screws or metal chips, or combustible 

foreign matter such as oil enter the driver. 

 

Applicable motors: Please refer to the selection manual. 

 

Please comply with the wire gauge standards. The recommended wire diameter varies 
with the motor wattage. Please refer to the table below: 

 

Type 

Wattage 

Wire Diameter 

Axial 

100W~850W 

20AWG 

850W~7.5kW 

16AWG 

Spindle 

Less than 7.5kW (Include) 

12AWG 

More than11kW (Include) 

10AWG 

 

Please connect the ground wire to class-

3 (under 100Ω). Poor grounding might cause 

signal error, electric shock, or fire. 

 

The grounding of the motor must be connected to one of the grounding terminals of 

the frequency converter. 

 

In  accordance  with  EN  61800-5-1  (Section  4.3.5.5.2),  since  the  normal  contact 

current of the frequency converter is higher than 3.5 mA AC or 10 mA DC, a fixed 

protective earthing connection must be used:   

1)  The cross-sectional area of the protective earthing wire should be coper wires of 

at least 10mm

2

 or aluminum wires of at least 16 mm

2

2)  Automatically  cut  off  the  power  when  the  protective  earthing  conductor  is 

interrupted. 

3)  Replace the original protective earthing conductor with a spare one that has the 

same cross-sectional area. 

 

Grounding Directions:   

1)  The  length  of  grounding  wires  should  comply  with  the  electrical  equipment 

regulations; the shorter the better. 

2)  The  grounding  wire  of  the  driver  should  be  grounded  separately  with 

high-current loads such as electric welders or high frequency motors.   

3)  Please refer to the pictures below when the controller is grounded with multiple 

electrical control devices. Do not make it a loop

 

 

(a) O                                  (b) O                                      (c) X 

(a) 良

(b) 良

(c) 不良

 

 

Reviews: