Synergy RA5204-L520-30A-L143 Installation Manual Download Page 5

How to Shorten the Power Cord

Rack Power Distribution Unit

5

Cut the cord

1. Cut the outer cord sleeve to the desired length. Be careful not to cut 

through the four wire bundles. The cord must remain at least 
4.9 feet (58.8 inches) long from unit to end. Remove the cut sleeve 
from the wire bundles. 

2. Cut each wire bundle, making sure each is approximately 1.5 

inches from the end of the cord sleeve. 

3. Strip approximately 0.5 inches of insulation from each wire 

bundle.

Reassemble the plug

1. Twist together any loose wires.
2. Fully insert each wire into its coordinating terminal on the plug 

face before you tighten the terminal screw.

3. Tighten the terminal screws to a minimum torque of 18 inch-

pounds.

4. Slide the plastic plug case back around the face of the plug. Align 

the tab on the case with the corresponding opening on the plug 
face. Secure the case by tightening two of the screws in the side of 
the case to a minimum torque of 10 inch-pounds.

5. Reattach the strain relief to the plug, using the remaining two 

screws. Tighten the screws to a torque of 16 to 20 inch-pounds.

Note

Insert only the bare copper wires into the terminals. 
Do not tin the wires that hold the strands together.

Wire color

Terminal

Red

Terminal marked “Y”

Black

Terminal marked “X”

Green

Ground pin, has a green screw

 White

No markings, has a silver prong

Summary of Contents for RA5204-L520-30A-L143

Page 1: ...power cord Four 20 amp circuit breakers AP7580 Four NEMA L5 20 outlets AP7581 Four NEMA L6 20 outlets 28 foot NEMA L14 30 power cord Two 20 amp circuit breakers Twelve NEMA 5 20 outlets RA5204 L520 3...

Page 2: ...2 Rack Power Distribution Unit 28 foot NEMA L14 30 power cord AP7583 Four NEMA L5 30 outlets AP7584 Four NEMA L6 30 outlets RA5204 L530 30A L143 RA5204 L630 30A L143...

Page 3: ...that the power cord plug and socket are in good condition Disconnect the PDU from the power outlet before you install or connect equipment to reduce the risk of electric shock when you cannot verify g...

Page 4: ...m the sides of the plug until the cord easily slides in and out 3 Slide the plug case down the cord to your desired length 4 Loosen but do not remove all four terminal screws until you can remove all...

Page 5: ...ing terminal on the plug face before you tighten the terminal screw 3 Tighten the terminal screws to a minimum torque of 18 inch pounds 4 Slide the plastic plug case back around the face of the plug A...

Page 6: ...ets Ground J on the plug and Ground J on the outlet Neutral Q on the plug and Neutral Q on the outlet X on the plug and X on the outlet Y on the plug and Y on the outlet Verify that there is no contin...

Page 7: ...lug prongs and the slots on the outlets X on the plug and X on the outlet Y on the plug and Y on the outlet Ground J on the plug and Ground J on the outlet Verify that there is no continuity among any...

Page 8: ...and the slots on the outlets Ground J on the plug and Ground J on the outlet Neutral Q on the plug and Neutral Q on the outlet X on the plug and X on the outlet Y on the plug and Y on the outlet Veri...

Page 9: ...the mounting brackets to the PDU using four flat head screws per bracket provided To mount the PDU with the outlets facing out of the rack To mount the PDU with the outlets facing the top of the rack...

Page 10: ...s of the brackets with the installed caged nuts Insert and tighten the screws Connect to an APC UPS 1 Route the power cord through one of the slots on the roof of the enclosure 2 If necessary route th...

Page 11: ...20 outlets RA5204 L530 30A L143 Four NEMA L5 30 outlets RA5204 L630 30A L143 Four NEMA L6 30 outlets Maximum total current draw 24 A Physical Size H W D 3 50 17 20 3 50 in 8 89 43 69 8 89 cm Weight 1...

Reviews: