Page 2
7)
Flush system and check for leaks
■ Turn valve to the warm position and
run for a few minutes.
■ If system is dirty, remove valve spindle
in center of valve to ensure proper
flushing. (See service instructions.)
■ Check for leaks around valve
assembly and all pipe fittings.
5)
Remove protective shield
If attached in
Step 3
, then remove shield
snap fitted over the end of valve spindle
once valve is securely installed and wall
finish work has been completed.
6)
Adjust valve packing nut
Reference figure 3
■ Turn hot & cold supplies on.
Valve will not operate unless both hot
and cold water supply pressures are on.
■ Place handle over
control spindle stem
.
■ Adjust
packing nut
for positive
frictional resistance as handle is
rotated from shutoff position across
adjustment range.
9-1/4"
(236 mm)
3-1/8"
(79 mm)
finished wall
Floor
hot / cold
supply
showerhead
supply
5/8" (16 mm)
1/2" (13 mm)
7-1/2" diameter
(191 mm)
tub spout
supply plug
1/2" (13 mm)
2" ± 1/2"
(51 mm ±13 mm)
pipe centerline
to finished wall
*
Note (2)
1/2"-14 NPT
mounting plate,
*
Notes (1)(2)
*
Notes:
(1) Valve spindle can be further extended through
thicker walls by removing
mounting plate
.
(2) Dimension applies when
mounting plate
is not used.
(3) Dimensions subject to change without notice.
Temptrol
control valve
S-4001-BODY
approx
27"
(686 mm)
approx
48"
(1219 mm)
Dimensions
Carrington Shower System, S-4401
Figure 3
Valve adjustments
wall
Temp Limit
stop screw
packing nut
control
spindle
stem
8)
Set Temp Limit stop screw
Reference figure 3
The limit stop screw limits valve handle
from being turned to maximum
position resulting in excessive hot
water discharge temperatures.
Warning:
Failure to adjust
limit stop screw
properly may
result in serious scalding.
■ Place handle on control spindle and open
valve to maximum desired temperature.
■Turn limit stop screw clockwise until
it seats.
Note:
Do not install positive shut-off
devices on control valve outlet or devices that
do not allow the valve to flow at least 1.5 gpm.