Chapter 3 ICS Command Reference
ELEVTIME
182
SSU-2000e Technical Reference
12713140-003-2 Revision E.01 – January 2007
ELEVTIME
Use this command to read
and set the current time-outs for alarm elevation.
Level 0
Not applicable
Level 1
ELEVTIME [xAy]
If you do not specify a parameter, then all elevation times for each
module within the unit are displayed.
Level 2
Same as Level 1 operation.
Level 3
Same as Level 2 operation, with the following additions:
ELEVTIME [xAy] time
Supervisor-level users can use this command to read and set the current
time-out length for alarm elevation. The unit is required to elevate
MINOR and MAJOR alarms to the next level after a user-settable time
period. Time is in seconds and can be from 60 seconds (1 minute) to
500,000 seconds.
Level 4
Same as Level 3 operation
Remarks The default value for the elevation time is 86,400 seconds (24 hours).
Related
RestrictionsNone
Example
The following is an example of the ELEVTIME command message format:
SSU_2000->ELEVTIME
SSU_2000->elevtime
2003-06-18T20:44:50Z ID: SSU2000 Name: SSU_2000
1A01 elevation time is 86400 seconds
1A02 elevation time is 86400 seconds
1A03 elevation time is 86400 seconds
1A04 elevation time is 86400 seconds
1A05 elevation time is 86400 seconds
1A08 elevation time is 86400 seconds
1A09 elevation time is 86400 seconds