12713140-003-2 Revision E.01 – January 2007
SSU-2000e Technical Reference 169
Chapter 3 ICS Command Reference
ALARM
ALARM
Use this command to provide the current alarm status and access to the alarm
settings.
Level 0
Not applicable
Level 1
ALARM [{ALL|xAy[-z]}]
Use this command to view the current alarm status for the module that
you specify. Only active alarms display, unless an option is passed.
If you do not specify a parameter, each active alarm status stored in the
Communications Module is displayed. If you specify ALL, the current
status of all alarms for all modules through the SPI command displays.
Output from the command includes the alarm number (internal number
used for alarm identification), a text description of the alarm, the current
status, the current alarm level (elevated alarms are indicated with an
asterisk *), and the delay time for the alarm.
Example:
SSU_2000->alarm 1A2
2003-05-24T18:23:38Z ID: SSU2000 Name: SSU_2000
Input #
Alarm Status
Level(*=Elev) Delay
------- ---- ------------- --------------- ------------- ---------
1A02 (00) Communication Ok
Minor
5 sec
1A02 (01) Mastership
Ok
Minor
30 sec
1A02 (02) Power-A
Ok
Minor
Immed
Level 2
Same as Level 1 operation, with the following additions:
ALARM TEST {MINOR|MAJOR|CRITICAL}
Options are:
TEST
Use this option to test and activate alarm relay/LED for one
second. This has no effect on alarm status.
MINOR
Sets the MINOR alarm relay/LED
MAJOR
Sets the MAJOR alarm relay/LED
CRITICAL
Sets the CRITICAL alarm relay/LED
Level 3
Same as Level 2 operation, with the following additions:
ALARM xAy[-z] # DELAY time
ALARM xAy[-z] # {IGNORE|REPORT|MINOR|MAJOR|CRITICAL}
ALARM ACO