12713020-002-2 Revision D – April 2004
SSU-2000 User’s Guide 441
SSU-2000 Shelf Specifications
Operating Conditions Specifications
The unit operates at specified parameters in the operating conditions summarized in
Table F-2. Normal Operating Conditions
Parameter
Minimum
Maximum
Units
Notes
Supply Voltage
–38
–65
Volts DC
Temperature
0
50
°
C
1
Temperature Rate of Change
–
8.3
°
C/Hr
Relative Humidity
5
85
%
2
Altitude
-200 ft.
13,000 ft.
feet
3
Inlet air temperature, limited convection 15 ft./min.
Non-condensing over specified temperature range.
The maximum operation ambient temperature shall be reduced by 2 C for every 984 ft.
altitude above 4,921 ft.
The unit is not damaged when exposed to the levels specified in
, but
performance is degraded. The unit returns to specified performance upon returning
to specified operating conditions.
Table F-3. Exceptional Operating Conditions
Parameter
Minimum
Maximum
Units
Notes
Supply Voltage: (48 vDC)
–38
–75
Volts, DC
1
Temperature
–5
50
°C
2
Relative Humidity
5
90
%
3
1. The unit is not damaged if the polarity on the power leads is reversed.
2. At 30
°
C max/hour rate of change.
3. Non-condensing.
Summary of Contents for SDU-2000
Page 12: ...12 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 18: ...18 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 390: ...SNMP Protocol 390 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...
Page 420: ...I O Connector Grounding 420 SSU 2000 User s Guide 12713020 002 2 Revision D April 2004 ...