GENERAL:
Upon receipt of the product, thoroughly inspect for any freight damage which should be brought to the attention of the delivery carrier.
INSTALLATION:
Product Information
E24629
Mounting Instruction (Ceiling
and Wall Mount)
1. Connect input as shown in wiring diagram
below and fasten canopy to the J-Box bracket.
2. Snap housing to canopy
3. Connect the battery (when applicable ) toithe
PC board.
4. Secure faceplate to housing and remove the
proper arrow as required.
Wiring Diagrams
Maintenance:
BATTERY: The battery supplied with the Battery Backup model requires no maintenance. However, it
should be tested periodically replaced when it no longer operates the connected fixtures for the duration of a
30-second or 90-minute test. The battery supplied in this equipment has a life expectancy of 5 years when
used in a normal ambient temperature of 72º .
Operation (Battery Backup):
1. Apply AC power to the unit. The LED indicator
should turn RED.
2. After the battery has been left to charge for 24
hours, test the unit by pushing the switch. The LED
indicator turns OFF and the LED board stays ON.
3. When the switch is released, the LEDs turn OFF and
the LED indicator turns back to RED.
Testing:
National Electric Code (NEC) and NFPA life safety code regulations require that routine tests need to be
performed as listed below : Once every month, the unit needs to be tested for duration of 30 seconds. Push in
and hold the test switch to perform this test. Once every 12 months, a full 90 minute (per UL requirements) test
needs to be performed on the unit. Disconnect the power to the unit and leave it in the emergency mode. The
LEDs should stay ON for at least 90 minutes.