DEVYL ARTIC
24
3.10 Setting the appliance
The boiler has already been factory set by the manufacturer.
However, should it need to be readjusted, for example after
non-scheduled maintenance, replacing the gas valve or gas
conversion, proceed as described below.
b
Adjustments to maximum power must be performed in
the indicated sequence and only by qualified technicians.
- Remove the casing as shown in section 6.
- Loosen the pressure tapping point screw (fig. 11 -
1
) located
downstream of the gas valve by approximately two turns and
connect a pressure gauge there.
- Disconnect the compensation inlet (fig. 11 -
5
) from the gas
valve.
- Remove the protective cap (fig. 11 -
2
).
- Turn a water tap on fully, bring the temperature selector to
the maximum and connect the boiler to a power supply.
2
5
3
4
1
Setting to the maximum value:
- Screw the nut (fig. 11 -
3
) fully until obtaining the gas pres-
sure shown in the table.
Maximum gas pressure at nozzles
11
G20
10,40
mbar
106,05
mm. C.A.
G30
28,00
mbar
285,52
mm. C.A.
G31
36,00
mbar
367,10
mm. C.A.
13
G20
11,80
mbar
120,33
mm. C.A.
G30
27,80
mbar
283,48
mm. C.A.
G31
35,80
mbar
365,06
mm. C.A.
17
G20
11,30
mbar
115,23
mm. C.A.
G30
28,00
mbar
285,52
mm. C.A.
G31
36,00
mbar
367,10
mm. C.A.
Setting to the minimum value:
- disconnect one of the two electrical cables from the coil
- screw or unscrew the hex head socket screw (fig. 11 -
4
) to
adjust the minimum until obtaining the gas pressure value
shown in the table
- refit the protective cap (fig. 11 -
2
).
Minimum gas pressure at nozzles
11
G20
1,20
mbar
12,24
mm. C.A.
G30
3,00
mbar
30,59
mm. C.A.
G31
3,90
mbar
39,77
mm. C.A.
13
G20
1,50
mbar
15,30
mm. C.A.
G30
3,30
mbar
33,65
mm. C.A.
G31
4,30
mbar
43,85
mm. C.A.
17
G20
1,60
mbar
16,32
mm. C.A.
G30
3,60
mbar
36,71
mm. C.A.
G31
4,80
mbar
48,95
mm. C.A.
- Reconnect the compensation inlet to the gas valve (fig. 11
-
5
).
- Disconnect the pressure gauge and retighten the pressure
tapping point screw (fig. 11 -
1
).
b
Please remember that for operation with LPG, a gas pres-
sure regulator at the appliance power supply is required,
set to 28-30 mbar if operating with butane and 37 mbar for
propane.