Installation Instructions for the 
TBLF/TCLF Air Heater, for water
GOLD

1. General

The TBLF/TCLF air heater uses hot water as the heating 
medium for preheating the supply air. Install the TBLF in 
the outdoor air duct.

Finned-tube heat exchanger fabricated of copper tubes 
and profi led aluminium fi ns. Fin pitch: 5.5 mm. The head-
ers and the pipework to the water connections are made 
of copper. The male threaded pipe connections are made 
of brass.

The control functions for preheat are integrated into the 
control equipment of the air handling unit. Temperature 
sensor for duct and IQlogic

+

 with a 0.25 metre long cable, 

frost guard sensor (insertion type), and T-piece (for air 
heaters without outlet for an insertion sensor) are included 
in the air heater supply.

Extra accessories 

Circulation pump used for ensuring the frost guard func-
tion for the air heater. Supplied with T coupling, non-
return valve and commissioning valve. The automatic 
pump control system is integrated into the control equip-
ment of the air handling unit. See the individual instruc-
tions for the TBPA accessory. 

The TBVL valve set with 2(3)-way valve, actuator, con-
nection cable with quick-fi t connector, frost guard sensor 
(insertion type), and T-piece (for air heaters without outlet 
for an insertion sensor). See the individual instructions for 
the TBVL. If the air heater is to be installed outdoors or in 
a cold space, take into consideration the enclosure class of 
the actuator and the permissible ambient temperature.  If 
necessary, see to it that required protection is arranged. 

If you use a valve of your own, you have the option of 
instead selecting a set of electrical connection compo-
nents. This set contains a connection cable with quick-fi t 
connector, resistor and insertion or strap-on sensor.

2. Maintenance

Check at least twice a year whether cleaning is necessary.

Cleaning shall only be done by blowing with compressed 
air against the ordinary direction of airfl ow, vacuum clean-
ing with a soft nozzle or wet cleaning with water and/
or solvent. Before you begin wet cleaning, you should 
cover adjacent functional sections to protect them. After 
wet cleaning, you should blow the surfaces dry with com-
pressed air to remove every trace of cleaning solvent.

TBLF

TCLF

If cleaning solvent is used, this solvent must not contain 
ingredients that will corrode aluminium or copper. Swe-
gon’s cleaning agent is recommended. This cleaning agent 
is sold by Swegon or Swegon Service.

While cleaning, check whether the liquid circuit needs to 
be vented. 

Summary of Contents for TCLF

Page 1: ...alve actuator con nection cable with quick fit connector frost guard sensor insertion type and T piece for air heaters without outlet for an insertion sensor See the individual instructions for the TBVL If the air heater is to be installed outdoors or in a cold space take into consideration the enclosure class of the actuator and the permissible ambient temperature If necessary see to it that requ...

Page 2: ...e air heater as near to the air heater as possible A T piece is supplied with the air heater for installing an insertion sensor See fig 2 and 3 Make sure that the frost guard sensor is protected to prevent inad vertent damage This can be done for example by fitting a pipe extension piece to the air heater s outgoing header Rectangular connections Install the frost guard sensor on the air heater in...

Page 3: ...atisfactory anti freeze monitor function in the air heater A secondary pump and non return valve must therefore be installed as illustrated in Fig 2 A pump kit consisting of a pump non return valve and commissioning valve is avail able as an accessory The temperature sensor can to advantage be mounted at an appropriate place in the air handling unit between the filter and the heat exchanger in ord...

Page 4: ... 202 can be loaded with a total of max 48 VA GOLD RX PX CX SD version E F 4 5 6 7 8 9 A BCDE F 0 1 2 3 P1 COM POWER IQlogic 1 2 3 4 5 6 7 8 9 10 11 12 S S C 13 NO 14 C 15 NO 16 17 18 19 20 G 21 G0 22 Com 1 Heat Cool Com 2 Temp sensor for pre heated air Contactor Pump Digital temperature sensors require correct polarity when you connect them Jack for wall mounting 019611 T1 GR R1 RD 32 G0 IQlogic c...

Reviews: