5. Electrical connections

For access, unscrew the bolts that secure the blue 
cover on the motor control system casing. Connect the 
hand-held micro terminal to the motor control system's 
integrated wiring terminals, in Port "A". Use a bus 
cable, (type 6-core, unshielded, 30 AWG/0.066 mm

2

 

telecommunication cable or a similar flat cable) with 
RJ12/6 connectors in both ends, see the figures below. 

BR1014A

11

a

© 2015 OJ Electronic  

A/

S

-V+

-Add. Pin2

-Bus B

-Bus A
-Gnd

-Add. Pin2

-Add. Pin2

-Bus B

-Bus A
-Gnd

-Add. Pin2

-V+

-Gnd

-Bus B

-Bus A
-Gnd

-V+

A

C

B

-

Same order of colours

OC

(green)

Alarms
(red)

6. Indications, LEDs

The hand-held micro terminal has two integrated LEDs 
(See figure) with the following function:

Steady 

glow

Flashing

Red LED

-

Alarm active

Green LED

OC

Oversteering with hand-held 

micro terminal.

7. Alarm

For particulars of current alarms, see table in Section 4.

Alarms are reset automatically if the fault ceases to exist 
and the EC control system starts up again. 

If the maximum number of restarts has been exceeded 
the resetting of alarms can take place by selecting "Reset 
Alarm" in the alarm menu. As an alternative, short-circuit 
Terminals 26 (GND) and 27 (Din2) on the motor control 
system's integrated wiring terminal or interrupt the supply 
voltage for the EC control system.

8. Trouble shooting

Symptoms

Cause

Action

No values in the hand-held 

micro terminal 

– Display window off

The EC control system is switched off

Start the EC control system

Modbus cable is defective

Replace the Modbus cable

The RJ12 connector is not correctly connected

Check the contact connections in both the hand-held micro 

terminal and the motor control system.

Connect the RJ12 cable to Port "A" in the motor control 

system.