Connecting of the control panel
Examples of cable types for panel and module
connection and their acceptable lengths:
-
the cable YTLYp 4x0.12 mm
2
(about
resistance 155
Ω/km
) the maximum length
of 50m,
-
the cable LiYY 4x0.25 mm
2
(about resistance
155
Ω/km
) the maximum length of 100 m.
The panel can appear in two hardware versions.
Version 1:
Signal outputs in the connector, on the back wall
of the panel casing.
Version 2:
In additional, necessarily must insert the EMC
filter, type ZCAT1518-0730 on the cable, as
shown in the figure below. The EMC filter should
be included with the controller.
The filter should be inserted on the cable,
necessarily in the form of a cable loop between
the control panel and the controller module at
distance about 120 mm from the control panel
connector.
Installation EMC filter: 1 - control panel, 2
–
TAC5/TAC6 controller module, 3 - EMC filter (type
ZCAT1518-073).
The control panel should be installed with the
mains supply disconnected from the
controller
.
The cable poles must be connected properly,
as wrong connection may lead to control
panel and module damage
.
When choosing the cable between the panel
and the module, the rule is that the
resistance of one conductor in the cable
should not be greater than 8
Ω
and the total
length of the conductor must not exceed 100
m. The longer the wire, the larger the wire
cross section
.
Summary of Contents for TACtouch
Page 1: ...OPERATION ASSEMBLY MANUAL TACtouch CONTROL PANEL TO THE TAC5 TAC6 CONTROLLER 050371 20220503 ...
Page 10: ...10 TAC5 Slave wiring star with other devices in daisy chain Maximum cable length 100m ...
Page 11: ...11 TAC5 Slave wiring Maximum cable length 100m Shield ...
Page 12: ...12 Red Grey Blue Black TAC6 wiring ...
Page 15: ...15 ...