Swegon TACTouch TAC5 Manual Download Page 8

In additional, necessarily must use the EMC filter, type 
ZCAT1518-0730 on the cable, as shown in the figure 
below. The EMC filter should be included with the con-
troller. The filter should be inserted on the cable, necessa-
rily in the form of a cable loop between the control panel 
and the controller module at distance about 120 mm from 
the control panel connector.

Installation EMC filter: 1 - control panel, 2 - controller 
module, 3 - EMC filter (type ZCAT1518-073).
In addition, EL2adapter_v2 adapter can be used to 
extension the control panel connection to the controller 
module. The adapter provides a wire connection with an 
RJ-type plug with a 4-wire cable and is available from the 
control panel manufacturer.

Cleaning and maintenance procedures

The outer surface and maintenance of the control panel 
screen.

The device should be cleaned with a soft, dry 
cloth.

It is not allowed to clean the device with a flam-
mable agent or substance (i.e. benzene or any 
kind of solvents) or a wet cloth. Such treatment 
can lead to malfunction of the device.

It is not allowed to scratch the screen with nails 
or other sharp objects. It can lead to scratches or 
damage of the device.

It is not allowed to clean the device by spraying 
water on it. If the water gets inside of the device 
it can cause a fire or lead to electrocution or 
damage the device.

8

Swegon reserves the right to alter specifications.

Summary of Contents for TACTouch TAC5

Page 1: ...TACTouch Operation Assembly Manual TAC5 TAC6 Controller 20210315 ...

Page 2: ...tive 3 General information 4 Operation of the panel 4 Software update 5 Technical data 5 Exploitation conditions 6 Assembly requirements 6 The control panel installation 6 Connecting the control panel to the controller 7 Cleaning and maintenance procedures 8 Connecting TACTouch control panel to the TAC5 controller 9 2 ...

Page 3: ...s the requirements of the Directive 2012 19 EU of 4 July 2012 on waste electrical and electronic equipment WEEE accor ding to which it is marked by the symbol of crossed out wheeled bin like below meaning that product is subjec ted to separate collection Responsibilities after finishing a period of using product dispose of the packaging and product at the end of their period of use in an appropria...

Page 4: ... parameters exit a chosen menu position or cancel a parameter setting quick return back to the main screen menu information concerning the selected menu position enter to the main menu Main screen Main screen If the heat exchanger is working main screen shows schematics with most important values like temperatures speed of fans date actual time etc To start the controller press anywhere on the scr...

Page 5: ...software should be copied directly to the memory card not to a subfolder Connect the supply to the con troller and open software update from main menu and replace the program in the TACTouch control panel Technical data Supply power 5 24 VDC from the TAC5 controller socket Consumed current at 12 VDC supply voltage 0 15 A Protection class IP20 Work temp Storage temp 0 50 C 0 65 C Temperature measur...

Page 6: ...n The control panel installation should be done according to the following guidelines Assembly Disconnect the mounting frame 1 from the back of control panel housing 2 The frame is attached to the control panel housing with latches Use a flat screwdriver to detach the frame Using sharp tool cut out holes in four places of the cover 3 for the screw terminals Drill holes in the wall and use screws m...

Page 7: ...ables connecting the control panel with the controller as this may damage the control panel and the controller When choosing the cable between the control panel and the controller the rule is that the resis tance of one conductor in the cable should not be greater than 8Ω and the total length of the conduc tor must not exceed 100 m The longer the wire the larger the wire cross section Example of c...

Page 8: ...es a wire connection with an RJ type plug with a 4 wire cable and is available from the control panel manufacturer Cleaning and maintenance procedures The outer surface and maintenance of the control panel screen The device should be cleaned with a soft dry cloth It is not allowed to clean the device with a flam mable agent or substance i e benzene or any kind of solvents or a wet cloth Such treat...

Page 9: ...Connecting TACTouch control panel to the TAC6 TAC5 controller 9 20210215 Swegon reserves the right to alter specifications TACTouch ...

Page 10: ...TACTouch 10 Swegon reserves the right to alter specifications 20210215 TACtouch centralized TAC5 TAC6 Advanced setup configure SAT MODBUS with correct address ...

Page 11: ...The manufacturer reserves a right for making changes in construction and software without previous notice 11 20210215 Swegon reserves the right to alter specifications TACTouch ...

Reviews: