3. Commissioning
3.1 General
Commissioning sequence:
1. Check that there are no foreign objects inside the unit,
duct system or functional sections.
2. Check that rotary heat exchanger rotor (SILVER C RX
only) rotates easily. On sizes 50-120, the rotary heat
exchanger must be angled slightly towards the filter,
see drawing below.
If the inclination needs adjusting, see special
instructions for adjusting the inclination of the rotary
heat exchanger (04-80) or the installation instructions
for the SILVER C (120).
L
L
≈
0,5xL
≈
0,5xL
SILVER C RX, sizes 50-120: The illustration shows the factory-
preset rotor inclination in a unit with Fan Arrangement 1. The
inclination must always be towards the filter, which means that
the inclination for Fan Arrangement 2 is in the other direction.
7. Check and adjust, if required, the pressure balance in
the air handling unit as described in Section 3.3.