background image

PELICAN 

Ceiling

12

Swegon reserves the right to alter specifications.                   20181005

Figure 5. Dimensions, PELICAN Ceiling.

Figure 6. Dimensions, PELICAN Ceiling with ALS. CL = Centerline.

Figure 7. Dimensions, PELICAN Ceiling with ALS, low build.

Figure 8. Dimensions, SAR K frame.

Q

Frame – SAR K

Size

Dimensions (mm)

Weight (kg)

L

N

400

395

75

1.0

500

495

75

1,24

600

595

75

1.6

When installing size 315-600 and 400-600 diffusers, position the 
ALS box so that its branch extends 20 mm below the ceiling surface. 

N

Dimensions and weights

PELICAN Ceiling

Size

Dimensions (mm)

Weight 

(kg)

A

Ød

I

M

P

125-400

395

124

375

70

35

2,1

125-600

595

124

575

70

35

4,3

160-400

395

159

375

70

35

2,1

160-600

595

159

575

70

35

4,3

200-600

595

199

575

70

35

4,3

250-600

595

244

575

70

35

4,3

315-600

595

314

575

50

34

4,3

400-600

595

399

575

50

34

4,3

Hole cutting dimensions, I x I 
CL = Centreline of branch

PELICAN Ceiling with ALS, 1 step

Size

Dimensions (mm)

Weight 

(kg)

A

B

C

ØD

Ød

E1

E2

F1

F2

G1

G2

H

K

Q

125-400

395

282

217

99

125

255

212

113

70

175

132

270

80

40

3,5

125-600

595

282

217

99

125

255

212

113

70

175

132

270

80

40

5,7

160-400

395

342

252

124

160

279

236

113

70

188

145

315

80

40

4,2

160-600

595

342

252

124

160

279

236

113

70

188

145

315

80

40

5,7

200-600

595

404

288

159

200

314

271

113

70

205

162

375

100

40

7,0

250-600

595

504

332

199

250

354

311

113

70

225

182

465

115

40

8,7

315-600

595

622

388

249

315

395

352

93

50

230

187

575

140

40

11,8

400-600

595

767

488

314

400

455

93

262

712

175

40

15,0

PELICAN Ceiling with ALS, 2 steps

Size

Dimensions (mm)

Weight 

(kg)

A

B

C

ØD

Ød

E1

E2

F1

F2

G1

G2

H

K

Q

160-400

395

342

252

99

160

255

212

113

70

175

132

315

80

40

4,1

160-600

595

342

252

99

160

255

212

113

70

175

132

315

80

40

5,7

200-600

595

404

288

124

200

279

236

113

70

188

145

355

80

40

5,0

250-600

595

504

332

159

250

314

271

113

70

205

162

450

100

40

7,8

315-600

595

622

388

199

315

334

291

93

50

205

162

550

115

40

9,5

Summary of Contents for PELICAN Ceiling

Page 1: ...0 125 160 38 137 54 194 70 252 200 600 160 200 58 209 80 288 110 196 250 600 200 250 83 299 107 385 150 540 315 600 250 315 125 450 150 540 180 648 400 600 315 400 180 648 215 774 255 918 Data specified for supply air applies to 50 Pa total pressure Lp10A Sound pressure incl A filter with 4 dB room attenuation and 10 m2 room absorption area EXTRACT AIR AIR FLOW SOUND PRESSURE ROOM Lp10A PELICAN CE...

Page 2: ...eiling Supply supply air 5 PELICAN Ceiling Supply Diffuser only 5 Air flow Pressure drop Sound level Throw 6 PELICAN Ceiling Supply ALS supply air 6 PELICAN Ceiling Supply supply air 6 PELICAN Ceiling Extract extract air 9 PELICAN Ceiling Extract extract air 9 PELICAN Ceiling Extract ALS 9 9 Air flow Pressure drop Sound level 10 PELICAN Ceiling Extract ALS extract air 11 Dimensions and weights 12 ...

Page 3: ...llation in a ceiling void where the installation height of components must be mini mized The air flow director can be accessed after you remove the air diffuser face from its spring retainers It consists of a number of adjustable air deflectors and by turning these you can easily set the distribution pattern desired See Figure 1 Installation To unfasten the diffuser face press in the spring retain...

Page 4: ...ter specifications 20181005 Figure 2 Installing PELICAN 1 Supply air 2 Extract air 1 2 Figure 1 Quick Access Figure 3 Installation of air diffusers and commissioning box with low installation height Figure 4 To dismantle the damper 0xD 5 0xD 5 2xD 10 ...

Page 5: ...000 2000 4000 8000 125 400 600 1 11 11 5 5 5 11 13 160 400 600 8 12 10 5 1 5 10 11 200 600 5 10 7 3 0 4 8 10 250 600 3 10 5 3 0 5 9 9 315 600 5 9 6 6 2 6 11 13 400 600 8 9 4 5 2 8 15 16 Sound attenuation DL Table DL Size 63 125 250 500 1000 2000 4000 8000 125 400 600 20 14 9 5 3 2 1 0 160 400 600 20 13 8 4 3 1 1 0 200 600 18 11 6 3 2 1 0 0 250 600 16 10 5 2 1 1 0 0 315 600 14 8 4 1 1 0 0 0 400 600...

Page 6: ...ALS 100 160 two steps PELICAN Ceiling Supply ALS supply air pt Pa 200 300 400 500 1000 40 50 100 200 300 400 3 4 5 10 20 30 40 50 100 20 25 30 35 40 dB A 125 160 200 250 315 400 m3 h l s pt Pa pt Pa 40 50 100 200 pt Pa pt Pa 10 20 30 40 50 100 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 100 0 1 2 3 4 5 m 0 2 l m3 h l s PELICAN Ceiling Supply 125 400 600 ALS 100 125 one step The version ...

Page 7: ...10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 100 0 2 3 4 5 10 m 0 2 l m3 h l s PELICAN Ceiling Supply 200 600 ALS 160 200 one step pt Pa pt Pa 100 200 300 400 pt Pa pt Pa 20 30 40 50 100 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 100 0 1 2 3 4 5 m 0 2 l m3 h l s PELICAN Ceiling Supply 200 600 ALS 125 200 two steps pt Pa pt Pa 100 200 300 400 500 pt Pa pt Pa 20 30 40 50 100 20...

Page 8: ... 100 200 300 400 10 20 30 40 50 100 200 300 400 500 20 25 30 35 40 dB A 100 0 3 4 5 10 20 m 0 2 l m3 h l s PELICAN Ceiling Supply 315 ALS 200 315 two steps pt Pa pt Pa 200 300 400 500 1000 pt Pa pt Pa 50 100 200 300 400 10 20 30 40 50 100 200 300 400 20 25 30 35 40 dB A 100 0 3 4 5 10 20 m 0 2 l m3 h l s PELICAN Ceiling Supply 315 ALS 250 315 one step PELICAN Ceiling Supply 400 ALS 315 400 one ste...

Page 9: ...0 8000 125 400 1 7 6 3 3 11 13 17 160 400 5 8 5 2 1 11 20 21 200 600 4 8 6 3 3 13 21 21 250 600 2 10 6 2 2 13 21 22 315 600 4 9 5 2 1 10 18 20 400 600 7 6 6 4 2 4 15 18 PELICAN Ceiling Extract ALS Sound power level LW dB Table KOK Size 63 125 250 500 1000 2000 4000 8000 125 400 1 11 11 5 5 5 11 13 160 400 3 13 10 3 4 4 8 8 200 600 3 12 7 2 1 3 9 11 250 600 5 12 5 1 1 4 10 10 315 600 7 13 5 0 1 5 1...

Page 10: ...her Sizing Diagram PELICAN CE Air flow Pressure drop Sound level The diagrams provide data for an air diffuser placed in a ceiling The diagrams should not be used for commissioning Min airflow required for obtaining sufficient com missioning pressure The dB A values are applicable to rooms with normal acoustic absorption 4 dB room attenuation The dB C value is normally 6 9 dB higher than the dB A ...

Page 11: ...30 40 50 100 200 5 10 20 30 40 50 100 200 20 25 30 35 40 dB A 100 0 m3 h l s PELICAN Ceiling Extract 200 600 ALS 160 200 PELICAN Ceiling Extract ALS extract air pt Pa pt Pa 200 300 400 500 pt Pa pt Pa 30 40 50 100 200 300 5 10 20 30 40 50 100 200 20 25 30 35 40 dB A 100 0 m3 h l s PELICAN Ceiling Extract 250 600 ALS 200 250 pt Pa pt Pa 200 300 400 500 1000 pt Pa pt Pa 40 50 100 200 300 400 10 20 3...

Page 12: ...eline of branch PELICAN Ceiling with ALS 1 step Size Dimensions mm Weight kg A B C ØD Ød E1 E2 F1 F2 G1 G2 H K Q 125 400 395 282 217 99 125 255 212 113 70 175 132 270 80 40 3 5 125 600 595 282 217 99 125 255 212 113 70 175 132 270 80 40 5 7 160 400 395 342 252 124 160 279 236 113 70 188 145 315 80 40 4 2 160 600 595 342 252 124 160 279 236 113 70 188 145 315 80 40 5 7 200 600 595 404 288 159 200 3...

Page 13: ...height L Specify only if diffusers in the low version is selected all sizes except 400 600 Frame SARb K b K aaa Version K Quadratic For size 125 400 400 125 600 600 160 400 400 160 600 600 200 600 600 250 600 600 315 600 600 400 600 600 Specification text SD XX ER XX Swegon s type PELICAN Ceiling square perforated ceiling air diffuser with air deflector complete with ALS commis sioning box and the...

Reviews: