Operation and maintenance instructions
Boost
The boost mode can be used to force the supply and extract
airflow to a higher setpoint, when specific conditions are met.
The boost mode can be activated with a contact connected to
the digital input IN2 or by an analogue 0...10V control signal
connected to input K3. The boost setpoint is preset in (l/s,
m³/h).
Setting
Settings
range
Factory
setting
Supply / Extract airflow
0...max
Boost activation on
Contact
RH
Contact
RH on / off
0...100%
60% / 40%
Vmin/max RH on K3
0...10V
2,0V / 9,5V
RH ~Vmin/max
0...100%
2% / 95%
Post ventilation
The post ventilation function is used to keep the fans running
during a specified laps of time. This function is activated auto-
matically when an electrical heating coil is activated.
Setting
Settings
range
Factory
setting
Activation
No
Yes
No
Time
0...9999sec 90sec