33
Operation and maintenance instructions – v2.8.8 & 2.7.3
Boost
The boost mode can be used to force the supply and extract
airflow to a higher setpoint, when specific conditions are met.
The boost mode can be activated with a contact connected to
the digital input IN9 or by an analogue 0...10V control signal
connected to input K3. The boost setpoint is preset in (l/s,
m³/h).
Setting
Settings
range
Factory
setting
Supply / Extract airflow
0...max
Boost activation on
Contact
RH
Contact
RH on / off
0...100%
60% / 40%
Vmin/max RH on K3
0...10V
2,0V / 9,5V
RH ~Vmin/max
0...100%
2% / 95%
Post ventilation
The post ventilation function is used to keep the fans running
during a specified laps of time. This function is activated auto-
matically when an electrical heating coil is activated.
Setting
Settings
range
Factory
setting
Activation
No
Yes
No
Time
0...9999sec 90sec
DEACTIVATE SOFTSTOP
TEMPERATURE
BOOST
POST VENTILATION
EXTERNAL COILS
ADVANCED SETUP
TEMPERATURE
BOOST
POST VENTILATION
INTERNAL COILS
EXTERNAL COILS
ADVANCED SETUP