![Swegon DRIF Installation, Commisioning, Maintenance Download Page 2](http://html1.mh-extra.com/html/swegon/drif/drif_installation-commisioning-maintenance_1413544002.webp)
DRI
2
Swegon reserves the right to alter specifications. 20170516
Disc settings – Varizon
®
Dimensions, weight and K-factor
Size
DRI
Dimensions
(mm)
Weight
(kg)
K-factor
**)
Supply air
A
B
C ØD
*)
E
F x G
H
200
590 1190 300 200 115
-
0
23
32,0
250
590 1990 350 250 140
-
0
41
53,0
315
1190 1990 415 315 173
-
0
78
85,0
400
1190 1990 500 400 215
-
0
81
130,0
200-600 1190 1990 300
-
- 200 x 600 55
73
120,0
250-800 1190 1990 350
-
- 250 x 800 75
75
176,0
*)
DRI with circular duct connection has a spigot for connecting a duct joint.
**)
Number of measuring tubes: 1.
Figure 7. Maintenance for
two-piece front with A=1190
mm and circular connection,
dismantle the cover strip and
then the screws that secure the
front plate, lift and pull out.
Figure 8. Maintenance
for two-piece front with
A=1190 mm and rectangu-
lar connection, dismantle
the cover strip and then the
screws that secure the front
plate, lift and pull out.
2 mm
2 mm
30 m
m
≥
315
≤
250
Commissioning
Maintenance for
≤
250
Maintenance for
≥
315
Figure 4. Commissioning.
Figure 5. Disc settings.
Figure 6. Maintenance for one-piece front with A=590 mm and
circular connection 200 and 250, lift and pull out.
Figure 9. Maintenance.
K
-f
ac
tor
K
-f
ac
tor