8. Commissioning form
Function
Factory setting
Setting value
Fan speeds
Away, supply air fan
40 %
Away, extract air fan
40 %
Home, supply air fan
55 %
Home, extract air fan
55 %
Boost, supply air fan
70 %
Boost, extract air fan
70 %
Maximum automatic boost, supply air fan
100 %
Maximum automatic boost, extract air fan
100 %
Smart settings
Cooling, supply air fan
75 %
RH, boost limit
5 %
RH, full boost
30 %
A
+
, Home limit
900 ppm
A
+
, Away limit
600 ppm
AQ, boost limit
800 ppm
AQ maximum boost
1,400 ppm
Fireplace function, difference in fan speed
20 %
Cooker hood function, compensation (home)
20 %
Cooker hood function, compensation (boost change)
0 %
Central vacuum cleaner function, compensation
20 %
Airflows | NOTE! All the fan modes should be preset.
Project planning values
Setting value
Supply air, total
l/s m
3
/h
l/s m
3
/h
Away
Home
Boosting
Extract air, total
l/s m
3
/h
l/s m
3
/h
Away
Home
Boosting
Ventilation unit data |
Write down the data on the ventilation unit identification plate for reference when the
need arises to contact a
service company.
Preset by:
Date:
Important
The supply airflow must be 2–10 % lower than the extract airflow.
Remember to explain the use of the item of optional equipment and how to service it to the user/caretaker!
!
Summary of Contents for CASA W4 Smart
Page 32: ...32 W4 311016 Swegon reserves the right to alter specifications www swegonhomesolutions com ...
Page 33: ...W4 311016 Swegon reserves the right to alter specifications 33 www swegonhomesolutions com ...
Page 34: ...34 W4 311016 Swegon reserves the right to alter specifications www swegonhomesolutions com ...
Page 35: ...W4 311016 Swegon reserves the right to alter specifications 35 www swegonhomesolutions com ...