3.1. Installation of the sensor in the duct 

system

Install the pressure sensor close to the measurement 
point. When measuring the (positive) pressure on the 
supply air duct, connect the measuring tube to the tap-
ping on the pressure sensor (+). When measuring the 
(negative) pressure on the extract air duct, connect the 
measuring tube to the tapping on the pressure sensor (-).

3.2. Electric and control cables

Connect the 3-wire cable from the pressure sensor to 
the ventilation unit’s I/O connection according to the 
wiring diagram.

NOTE! Make sure that the strain relief is arranged 
for the connections according to the electrical 
safety directives.

3. Installation

The constant duct pressure function on the Smart venti-
lation unit attempts to regulate the fan speeds to main-
tain the duct pressure at the set value. Individual setting 
values for the duct pressure should be determined for 
each operating mode (away, home, boost). The operat-
ing mode can be switched as normal when the constant 
duct pressure function is used.

1. General Description

2. Planning

Select the position of the measurement tapping point 
in the duct with care, so that as far as possible it repre-
sents the pressure in the entire duct system. For exam-
ple, a suitable location is close to the ventilation unit, 
yet so the airflow is still uniform in the measurement 
point. The measurement is based on the pressure differ-
ence, and therefore the other measurement sensor must 
be positioned so it represents the air that surrounds the 
duct, and where the air is stable. 

Important

Only a qualified electrician may make the 
electrical connections.

!

!

4. Commissioning

The commissioning of regulation for constant air pres-
sure is performed with a Smart control panel. 

Main 

menu/Settings/(1234)/IO controls

IO controls

IO 1

IO 2
IO 3 (ext.)
IO 4 (ext.)

Pa Extract  - AI

Away - DI

Emg.Stop_NO - DI

Pa Supply - AI

IO 5 (ext.)

DDC control - AI

Select connections that correspond to the IO-points 

Pa 

Supply - AI / Pa Extract - AI

. Example: “Pa Supply - AI” 

as a function for IO 1 and “Pa Extract - AI” as a function 
for IO 2.

The pressure setting values and airflows must be adjust-
ed for all operating modes (Home, Away, Boost), so that 
the ventilation unit functions in all conditions.

NOTE! The constant duct pressure function is not 
activated until you have set the values for all oper-
ating modes.

The control type for the ventilation unit is selected and 
the airflow is set from the menu 

Main menu/settings/

(1234)/Airflow adjustments

.

Airflow adjustments

Commissioning mode

Home (exhaust)
Away (supply)
Away (exhaust)
Boost (supply)

Boost (exhaust)
Travelling (supply)
Max Smart boost (supply)

50 Pa

35 Pa
38 Pa
90 Pa
92 Pa
35 Pa
82 Pa

Control type

 Pa

Home (supply)

48 Pa

Select “Pa” as the control type of both ducts that are to 
be regulated for a constant duct pressure. If the control 
type is set to “Pa Supply” or “Pa Extract”, the selected 
duct is solely regulated for constant duct pressure and 

5. Settings