3. Commissioning

Select the functions for the temperature sensors used 
and fine adjust the measurements if necessary from 
the 

Main menu / Settings / (1234) / Heating/cooling / 

Sensor/Control 

menu.

Outdoor air sensor

 

Select the SET sensor input to which outdoor air sensor 

is connected: 

”SET T6 -T9” = SET-connection unit’s Sensor inputs. 

(“Internal” = The unit’s internal outdoor air temperature 

sensor.)

Relay control functions

 

Select the heat medium pump function for the SET-

connection unit’s relays. SET Relay 1 / SET Relay 2 = Heat 

medium pump.

The commissioning of the battery is performed from the 

Heating/cooling 

menu

.

Heating function

 

Put the heating function into service from the menu 

item 

External liquid coil -> selected.

Heating always occurs primarily through control of 

the duct battery, yet if the battery’s heating capacity is 

insufficient to maintain the required temperature or if 

the freeze protection is activated, a possible internal 

electrically powered air heater in the unit is also cont-

rolled. Thus, do not turn off the internal air heater for 

after-heating when using external after heating.

Limit value (heating)

 

Select the required start temperature for external pre-

heating. When the outdoor temperature (transferred 

outside temperature) measured before the air heater/

cooler drops below the limit value, the relays in the SET 

unit selected for the heat medium pump are activated. 

The operating signal is received from the relay output, 

for example, the heat medium pump and/or solenoid 

valve. A minimum operating time has been established 

for the heating medium pump’s control (10 minutes).

Limit value (cooling)

 

Select the required start temperature for external pre-

cooling. When the outdoor temperature (transferred 

outside temperature) measured before the air heater/

cooler rises above the limit value, the relays in the SET 

unit selected for the heat medium pump are activated. 

The operating signal is received from the relay output, 

for example, the heat medium pump and/or solenoid 

valve. A minimum operating time has been established 
for the heating medium pump’s control (10 minutes).

4. Use

When the unit is commissioned it operates automatical-
ly according to the outdoor temperature. Incoming air 
being heated in the winter and cooled in the summer. A 
minimum operating time (10 minutes) has been set for 
control of the heating medium pump. 

5. Service

NOTE!

 Disconnect the power to duct battery and venti-

lation unit before servicing.. 

Service should always be carried out on the duct battery 
when servicing the ventilation unit. Check that dirt has 
not collected in the air cooler, clean if necessary.

The filter is cleaned by vacuuming and replaced if 
necessary. Order new filters (W2504FSS) from the web  
casastore.fi.

The inlet side of the air cooler is cleaned first with a 
brush, and then you can clean the entire air cooler. If 
the compressed air is used, blow off dirt in the direction 
from the output side towards the input side. Be careful 
so that the thin edges of the fins are not damaged.

Any dirt that has accumulated on the bottom of the 
condensate tray can be wiped off using a cloth and mild 
detergent. The function of the water trap and drainage 
pipes for condensate water should be checked at least 
twice a year by pouring water in the bottom of the 
condensate tray.

Summary of Contents for CASA SDHW250F

Page 1: ... cooling unit In the winter the unit heats the air taken in and ensures that the ventilation unit operates with the greatest effi ciency even in extreme cold In the summer the medium in the ground circuit is used to cool the building Planning Take into account the duct battery s capacity for the established airflows when sizing the depth of the ground source heating well see Technical data Take th...

Page 2: ...lanning to the effect of the duct battery Ensure that the ground source heating well cannot freeze on account of the duct battery being added to the system Supplement with the necessary protection Commissioning The duct connection spigots of the unit must be capped during transport storage and installation Make sure that the unit and the ducts are clean and that there are no loose objects in them ...

Page 3: ...harge The discharge hose is connected to the condensate out let G3 8 The condensate is led off to a floor drain or the like using a hose with an inner diameter of at least 12 mm The condensate hose 502130 is available as an accessory The hose must not be led off directly to the drain There must not be two water traps or a horizontal section on the condensate hose The damming height of the water tr...

Page 4: ...rature sensor 4 SET connection unit 5 Heat pump 6 Solenoid valve 7 Circulation water pump 8 Vent valve 9 Power source 24 VDC 10 Operating switch for the circula tion water pump ON OFF Not included in the delivery NOTE If the SET module is used for 230 VAC control the module must be installed according to the electri cal safety directives in a separate enclosure NOTE Make sure that the strain relie...

Page 5: ...m operating time has been established for the heating medium pump s control 10 minutes Limit value cooling Select the required start temperature for external pre cooling When the outdoor temperature transferred outside temperature measured before the air heater cooler rises above the limit value the relays in the SET unit selected for the heat medium pump are activated The operating signal is rece...

Page 6: ...6 SDHWM 210119 Swegon reserves the right to make changes www swegon com Dimensions Leave at least 50 cm service space in front of the door 479 425 381 350 250 477 22 22 22 22 ...

Page 7: ...velocity m s 0 3 0 3 0 4 0 4 0 5 Fluid s pressure loss kPa 5 9 7 9 8 7 10 0 10 6 Pipe connection DN 25 25 25 25 25 The unit s function for use as a preheater has been sized with 28 ethanol Air heater cooler s performance data Cooling Capacity kW 0 8 1 2 1 4 Air flow l s 40 100 150 INCOMING AIR Temperature C 25 25 25 Relative humidity 55 55 55 OUTGOING AIR Temperature C 13 17 18 Relative humidity 9...

Page 8: ......

Reviews: