Installation, operation and maintenance instructions

for design engineers, installation engineers and service personnel

SDHE_c_EN–m

Swegon 

CASA

®

  

Electric duct mounted air heaters

Important information

Only qualified personnel 

Only qualified personnel should carry out installation, 
configuration and commissioning.

Observe the following during installation 

The air heater is installed in the outdoor or supply air 
duct. If the heater is installed in the outdoor air duct 
before the ventilation unit, the heater and the duct 
must be insulated with nonflamable insulation and a 
duct mounted filter must be used for the air heater. 

The air heater must be accessible without obstruction. The 
air heater must not be installed in the immediate vicinity 
of the ventilation unit or duct bends, as this will prevent an 
even air flow across the heater resulting in impaired output.

Commissioning 

The duct connection spigots of the air heater must be 
capped during transport, storage and installation.
Make sure that the air heater and the ducts are clean 
and that there are no loose objects in them before 
you commission the ventilation system.

Do not commission the air heater until all work that 
produces large quantities of sanding dust or other 
impurities has been completed.

Electrical safety 

The air heater must be installed according to the local 
electrical safety provisions.

!

Products

For 125 mm ducts; SDHE125-1T 

(LVI nro. 7906723)

•  Electric duct heater, 1,2 kW: 300H125-12-1
•  SET connection unit

For 160 mm ducts; SDHE160-1T 

(LVI nro. 7906724)

•  Electric duct heater, 1,2 kW: 300H160-12-1
•  SET connection unit

For 200 mm ducts; SDHE200-1T 

(LVI nro. 7906725)

•  Electric duct heater, 1,2 kW: 300H200-12-1
•  SET connection unit

For 250 mm ducts; SDHE250-1T

•  Electric duct heater, 1,2 kW: 300H250-12-1
•  SET connection unit

For 250 mm ducts; SDHE250-2T

•  Electric duct heater, 2,0 kW: 300H250-20-1
•  SET connection unit

For 315 mm ducts; SDHE315-1T

•  Electric duct heater, 1,2 kW: 300H315-12-1
•  SET connection unit

For 315 mm ducts; SDHE315-2T

•  Electric duct heater, 2,0 kW: 300H315-20-1
•  SET connection unit

NOTE! The manual’s original language is English.

General Description

Duct mounted electric air heater for pre- or post heating 
the air. 

As pre heater  

Guarantees continuous ventilation under very cold 
conditions and to permit balancing functions (fireplace 
function/cooker hood function) in ventilation units that 
are not equipped with an internal air heater.

As post heater 

Helps to achieve the desired supply air temperature 
under very cold conditions whereby the heat exchanger 
may not be capable to heat air sufficiently.

Planning

Take the pressure loss caused by the air heater into 

consideration when sizing the airflows and selection of 

the ventilation unit.
The airflow through the heater must be greater than 1.5 m/s.
Make sure there is free access to the air heater for service. 

The air heater must not be installed with the service hatch 
cover directed downwards.

Summary of Contents for CASA SDHE125-1T

Page 1: ...ovisions Products For 125 mm ducts SDHE125 1T LVI nro 7906723 Electric duct heater 1 2 kW 300H125 12 1 SET connection unit For 160 mm ducts SDHE160 1T LVI nro 7906724 Electric duct heater 1 2 kW 300H160 12 1 SET connection unit For 200 mm ducts SDHE200 1T LVI nro 7906725 Electric duct heater 1 2 kW 300H200 12 1 SET connection unit For 250 mm ducts SDHE250 1T Electric duct heater 1 2 kW 300H250 12 ...

Page 2: ...enclosure NOTE Make sure that the strain relief is arranged for the connections according to the electrical safety directives 2 Electric and control cables Smart Extension Temperature module Sensor T6 T7 T8 T9 Smart unit SET2 SET1 DI max 50 VDC NC NC NC 1 2 3 4 5 6 7 8 9 10 11 12 max 250 V 6 A Relay 1 4 3 2 1 max 250 V 6 A Relay 2 NC 4 3 2 1 AO3 AO2 AO1 NC NC NC SET 1 0 230V 2 1 3 4 5 7 8 9 10 1 A...

Page 3: ... cal safety directives in a separate enclosure NOTE Make sure that the strain relief is arranged for the connections according to the electrical safety directives 2 Electric and control cables Smart Extension Temperature module Sensor T6 T7 T8 T9 Smart unit SET2 SET1 DI max 50 VDC NC NC NC 1 2 3 4 5 6 7 8 9 10 11 12 max 250 V 6 A Relay 1 4 3 2 1 max 250 V 6 A Relay 2 NC 4 3 2 1 AO3 AO2 AO1 NC NC N...

Page 4: ... mm 452 mm Direction of airflow B H D K L Dimensions for FLK duct filter Pressure loss in FLK duct filter with G4 filter 12 16 20 150 100 50 0 0 50 100 150 200 250 300 350 400 450 500 550 l s 600 25 31 Dimensions and technical data 270 370 Technical data Model mm Capacity kW Minimum airflow l s m3 h SDHE125 1T 125 1 2 19 70 SDHE160 1T 160 1 2 31 110 SDHE200 1T 200 1 2 47 170 SDHE250 1T 250 1 2 75 ...

Reviews: