7
R5-H
Smart
All rights to changes reserved.
2020-11-11
2.2 Changing flow direction
The ventilation unit has been supplied in the left-hand
version and it can be changed to right-hand version on
site.
A. Left-hand version
B. Right-hand version
1. Supply air
2. Extract air
3. Outdoor air
4. Exhaust air
1. Airflow settings
Flow direction can be changed from left-hand version to
right-hand version with user panel by making the Mirror
supply/exhaust selection in the
Settings/(1234)/Airflow
adjustments
menu.
2. Sensor package
If the ventilation unit is equipped with sensor package,
it must be relocated to extract chamber and control
cable connection in electrical box must be changed. See
Accessories chapter.
3. Reheater
If the ventilation unit is equipped with reheater, it must
be relocated when the flow directions is changed.
• Disconnect the quick-fit connector.
• Open three screws on the heater.
• Pull out the heater.
• Flip the heater over and push it in to new position.
• Remove the protective connector from the quick
connector and place it to the connector where you
disconnected the heater from.
• Connect the quick-fit connector and tighten the
three screws.
A. Placement in left-hand version
B. Placement in right-hand version