background image

SDHW. 180118

03/06/2015 Swegon reserves the right to make changes.

5

www.swegonhomesolutions.com

Control of cooling can be observed from a diagnostics 
screen. 

Main menu/Diagnostics/Heating and cooling.

Depending on the selected control mode, the set point 
value is shown for room air control’s supply air or the set 
point value for supply air control, the measured supply 
air temperature and the heating and or cooling capacity.

Temperature boost

 

if the after heating works as the home’s primary heating 
source and room air control is selected, you can use 
heating boost. The function increases the ventilation 
capacity variably to improve the efficiency of heating.

The function is put into service from the “Smart-
functions” menu 

Main menu/Settings/Smart functions/

Temperature boost

 The efficiency of the temperature 

boost can be regulated by changing the heating boost.

Temperature boost works automatically, but it can be 
temporarily taken out of service by changing the ven-
tilation mode. Boost will then be out of service for the 
following six hours. During temperature boost you can 
select Away and Boost speeds as normal. However, you 
can decide whether the function should be permitted in 
Away mode from the temperature boost menu.

Freeze protection

 

The air heater is equipped with anti-frost sensor that pro-
tects the air heater from freezing. The freeze risk alarm is 
activated if the outdoor temperature is below 0 °C and 
the return water temperature drops below the alarm 
limit. If the return water’s temperature drops yet further, 
the unit is switched off to prevent freezing. The unit 
starts again, when the temperature of the return water or 
the outdoor temperature has risen to a safe level.

The unit must be cleaned at regular intervals to obtain full 
power from the air heater. The length of the service inter-
val is entirely dependent on the cleanliness of the air, and 
of how well the filters and unit are maintained in general.  
The air heater can be easily cleaned once the heater’s 
cover has been removed. The inlet side of the air heater 
is cleaned first with a brush, and then you can clean the 
entire air heater with compressed air, water or steam. 
Blow or wipe off dirt in the direction from the output 
side towards the input side.  Exercise care so that the 
thin edges of the fins are not damaged.

6. Service

Stop the ventilation before servicing.

“UP2” = Internal temperature sensor in CASA control panel 2.

Relay control functions

 

If you wish to use relay control functions, e.g. for a 
circulation water pump or a duct damper, the SET unit’s 
relays can be programmed for the required function 
from the 

Sensor/Control

 menu. 

5. Use and function

The after heating is regulated automatically when the 
outdoor temperature has fallen below the set limit value.

You can select supply air or room air control as the after 
heating control method. 

Main menu/Settings/(1234)/

Heating and cooling/Control methid

Supply air control

 

During the heating season you should attempt to keep 
the supply air stable.  

NOTE!

 Due to the high efficiency of the heat exchanger, 

the supply air temperature may be higher than the set 
point value even though the outdoor air is cool.

Room air control

 

For room air control, the temperature of the supply air is 
based on the measurement of the room air temperature. 
It is possible, from the 

Control mode

 menu, to select the 

highest and lowest set point for cooling and heating to 
the supply air. The heating values should be kept close to 
the comfort temperature for the heating season.

The control’s set point

 

The set point can be changed directly from the 

Main menu

From the 

Heating and cooling

 menu you can also select 

separate set point values for Away and Travelling modes.

Diagnostics

 

Control type

Control type

Supply control max value
Cooling min setpoint

17°C

Supply control min value

Room air

Cooling max setpoint

25°C

14°C

17°C

Heating and Cooling

Eftervärme effekt

Supply air temperature
Summer mode

16,5°C

Supply air setpoint

0%

Preheater status

0%

100%

17°C

Summary of Contents for CASA CWW 125

Page 1: ...Installation operation and maintenance instructions for design engineers installation engineers and service personnel SDHW_e_EN m Swegon CASA Air heater for heating the supply air ...

Page 2: ...ered during transport storage and installation Make sure that the air heater and the ducts are clean and that there are no loose objects in them before you commission the ventilation system Ensure that the heating pipe system is mounted and insulated and that the venting sleeves and shut off valves are mounted Do not commission the air heater until all work that produces large quantities of sandin...

Page 3: ...e loss caused by the air heater into consideration when sizing the airflows and selection of the ventilation unit A shut off damper must be installed in the outdoor duct The shut off damper s relay control is taken from a SET connection unit 3 2 Water connection The following must be taken into consideration when the air heater is connected to the pipe system 1 Compression couplings are to be used...

Page 4: ...e commissioning of the air heater is performed with a Smart control panel Main menu Settings 1234 Heating and cooling 4 Commissioning Important Only a qualified electrician may make the electrical connections 3 3 Electric and control cables Install the SET connection unit in an appropriate posi tion in the vicinity of the sensor and actuator Connect the CAT45 cables 2 pcs supplied with the SET uni...

Page 5: ...he filters and unit are maintained in general The air heater can be easily cleaned once the heater s cover has been removed The inlet side of the air heater is cleaned first with a brush and then you can clean the entire air heater with compressed air water or steam Blow or wipe off dirt in the direction from the output side towards the input side Exercise care so that the thin edges of the fins a...

Page 6: ...ensor 8 Room air temperature sensor 9 Control panel 10 Circulation water pump 11 Extract air 12 Flow regulator 13 CAT45 cable 2 pcs 14 Modular cable PMK20 15 Duct actuator 16 Air heater s anti frost sensor Not included in the delivery Smart Extension Temperature module Sensor T6 T7 T8 T9 Smart unit SET2 SET1 DI max 50 VDC NC NC NC 1 2 3 4 5 6 7 8 9 10 11 12 max 250 V 6 A Relay 1 4 3 2 1 max 250 V ...

Page 7: ...uct CASA air heater ØD mm B mm H mm Øo d mm F G mm K mm L mm Pipe system s int volume I Weight kg CWW 125 125 313 255 10 175 40 276 356 0 20 5 5 CWW 160 160 313 255 10 175 40 276 356 0 42 5 4 Airflow l s m3 h Pres sure loss for air Pa Air in ºC Air out ºC Capac ity kW Water flow l s Pres sure loss for air kPa Air out ºC Capac ity kW Water flow l s Pres sure loss for air kPa Air out ºC Capac ity kW...

Page 8: ...www swegonhomesolutions com D B H 8 H Leave at least 40 cm service space in front of the door CWW 125 H 255 B 313 D 125 CWW 160 H 255 B 313 D 160 CWW 125 K 276 L 356 CWW 160 K 276 L 356 8 Dimensions ...

Reviews: