GB.BCHA455.050101

Specifications are subject to alteration without notice.

3.5 To clean the humidifier cassettes

Unlatch the locking pins at the top (1)

and bottom (2).

Remove the retaining piece of

the cassettes (3).

Back off the hose couplings (4).

The cassettes can now be

withdrawn (5).

Hose them clean with water.

OBS!  Do not confuse the hose

 

connections when refitting. 

2

1

3

4

5

3. Maintenance

3.1 General

Cleaning at regular intervals is necessary to ensure that the 
humidifier will operate as intended without malfunctioning. 
The interval between cleaning is largely conditional on the 
evaporation rate, dust content in the air, water quality and 
whether once-through or circulated water is used.
The humidifier should be inspected every third month and 
should be cleaned every six months.

3.2 Service under special conditions

Drain  and  clean  the  water  tray  whenever  the  system  is 
shut  down  for  an  extended  period,  such  as  during  long 
weekends.
If the humidifier is to be out of service for some time, the 
humidifier fills should be removed and stored where they 
will not sustain damage.
If there is a high concentration of calcium and bicarbonate in 
the water or if the dust concentration in the air is high, inspect 
the humidifier more often. If circulated water is used, the 
bleed-off flow can be increased (see page 2). The frequency 
of inspection and the bleed-off rate are conditional on the 
installation and should be based on experience.

3.3 When servicing, check the following:

1  The  humidifying  surface  should  be  equally  damp  on 

both sides. If they are not, clean the water system and 

the spray pipes above the humidifier cassettes.

2  Water should be bled-off through the drain valve – if not, 

clean the valve and refit it back in its original position. If 

softened water is used, very little bleed-off will occur and 

the valve may easily become clogged. 

3  The humidifier cassettes and water tray should be clean 

– if not, clean them.

4  The water trap should be filled with water.
5  There should not be any salt deposits on the front or 

back side of the humidifier – if there are, increase the 

water bleed-off by 25%.

3.4 Measures prior to major maintenance

Switch off the water pump (circulated water) or turn off the 

water supply (once-through water) and let the fans run for 

about 30 min. to allow the humidifier to dry. The humidifier 

cassettes are relatively fragile when they are wet and should 

be handled with care. 

Summary of Contents for BASIC BCHA

Page 1: ...d woven glass fibre of cross block design The contact fill is incombustible and thus is not affected by high air temperatures or high water temperatures The woven glass fibre is also highly water absorbent that allows complete wetting of the surfaces The air flow through the humidifier must be horizontal The water distribution system for circulated water consists of water spray tubes pump drain valve fl...

Page 2: ...table level 2 3 Electrical connections Before wiring the humidifer remove the humidifier casettes and run the power supply cables through the casing to the humidifier pump and the solenoid valve The cables must not be run above or through the inspection door A safety isolating switch for the appropriate rated output and cur rent tabulated on page 6 Section 4 1 Electrical data must precede the electr...

Page 3: ... fitted with a cleanable type BCXZ 1 71 water trap 6 and must be run without any reduction in diameter to a floor gulley 2 7 Humidification by once through water 2 7 1 Connecting the humidifier to the mains water system Fit a constant flow valve 3 to the inlet of the distribution tube size 15 conn Then connect the supply pipe 1 to the constant flow valve Fit a solenoid type or motor driven shut off valv...

Page 4: ...ere is a high concentration of calcium and bicarbonate in thewaterorifthedustconcentrationintheairishigh inspect the humidifier more often If circulated water is used the bleed off flow can be increased see page 2 The frequency of inspection and the bleed off rate are conditional on the installation and should be based on experience 3 3 When servicing check the following 1 The humidifying surface sh...

Page 5: ...assettes have been withdrawnfromthehumidifier Openthehoseclamp 2 and lift the cover plate with spray pipe 3 Pull the spray pipe 4 out of the cover plate Remove the end plugs 5 from the spray pipe Use an awl or a similar tool to clean the holes in the spray pipe and flush the pipe clean with water 3 6 To clean the water tray Remove the overfilling protection 1 and clean the bottom of the water tray ...

Page 6: ...lation class B 4 1 Electrical data 4 Technical data Weight std Weight EI 30 W o water With water W o water With water 65 85 Weight std Weight EI 30 W o water With water W o water With water 60 66 68 74 70 80 80 90 94 142 110 158 117 180 137 200 130 211 152 233 163 269 189 295 195 325 225 355 242 417 277 452 004 1039 546 453 006 1259 656 453 009 1459 756 653 014 1759 906 653 020 1946 1026 653 027 2...

Reviews: