q = k ·
√
p [l/s]
i
p = [Pa]
i
( )
k
q
2
[pi Pa]
q [l/s]
k
= k-factor
1
2
4
3
ADAPT Parasol EX
Nozzle setting
per side
Side
k-factor
690
L
1&3
0,253
690
L
2&4
0,253
690
M
1&3
0,44
690
M
2&4
0,44
690
H
1&3
0,693
690
H
2&4
0,693
1290
L
1&3
0,253
1290
L
2&4
0,665
1290
M
1&3
0,44
1290
M
2&4
1,16
1290
H
1&3
0,693
1290
H
2&4
1,825
Nozzle configuration
H M L
H =
M=
L=
1 x 8
T-25
P
i
(2,4)
P
i
(1,3)
Commissioning
1
k (1+3) + p
i
(1,3) => q (1+3)
The K-factor of the short sides together with the
commissioning pressure reading of these equals
the flow of the short sides, 1&3.
2
k (2+4) + p
i
(2,4) => q (2+4)
The K-factor of the long sides together with the
commissioning pressure reading of these equals
the flow of the long sides, 2 & 4.
3
q tot =q (1+3) + q (2+4)
The product's total flow is the sum of the above.
NB! p
i
(1,3) = p
i
(2,4)
NOTE: The commissioning pressure is diffe-
rent for the long sides (2 & 4) and the short
sides (1 & 3).
/