Swegon ADAPT Extract d Installation, Commissioning Maintenance Download Page 2

Swegon reserves the right to alter specifications. 

20130610 

www.swegon.com

WISE

2

Figure 3. Lighting fixtures or similar objects must not be installed 
beneath the diffuser as this disrupts the presence detection and  
room temperature measurement.

Maintenance

The exterior surface of the ADAPT air diffusers can be 
cleaned whenever necessary using lukewarm water with 
dishwashing detergent added. 
The duct system is accessible through the air diffuser and 
the commissioning box. 

Commissioning

All the ADAPT Air diffusers are delivered preset into com-
missioning mode, which means that the air diffuser is set to 
max. airflow by force control. 
When the ADAPT air diffuser is in commissioning mode, 
the light-emitting diode shines orange. The different LED 
indications:

• 

Steady green LED: Normal operation, the air diffuser is 
operating normally.

• 

Flashing green LED: The air diffuser has just been 
powered on and calibration is in progress.

• 

Steady red LED: Function failure, see separate docu-
mentation in the TUNE Adapt manual.

• 

Steady orange LED: The commissioning mode, max. 
airflow

• 

Flashing orange LED: Other commissioning modes and 
all the forced control situations of the feedback control 
system. 

More information about the commissioning process itself 
can be read in the Project Manual for the Wise system and 
in the TUNE Adapt manual. 