Swegon reserves the right to alter specifications. 

20150225 

www.swegon.com

WISE

Maintenance

The exterior surface of the ADAPT air diffusers can be 
cleaned whenever necessary using lukewarm water with 
dishwashing detergent added.
The duct system is accessible through the air diffuser and 
the commissioning box. 

Commissioning

All the ADAPT air diffusers are delivered preset into com-
missioning mode, which means that the air diffuser is set to 
max. airflow by force control. 
When the ADAPT air diffuser is in commissioning mode, 
the light-emitting diode shines orange. The different LED 
indications:

• 

Steady green LED: Normal operation, the air diffuser is 
operating normally.

• 

Flashing green LED: The air diffuser has just been 
powered on and calibration is in progress.

• 

Steady red LED: Function failure, see separate docu-
mentation in the TUNE Adapt manual.

• 

Steady orange LED: The commissioning mode, max. 
airflow

• 

Flashing orange LED: Other commissioning modes and 
all the forced control situations of the feedback control 
system. 

More information about the commissioning process itself 
can be read in the Project Manual for the Wise system and 
in the TUNE Adapt manual. 

Figure 4. Lighting fixtures or similar objects must not be installed 
beneath the diffuser as this disrupts the presence detection and  
room temperature measurement.

Summary of Contents for ADAPT Colibri d

Page 1: ...s The diffuser should be turned so it s hinges C figure 2 face the same direction as the inlet of the commissioning box Readjust the hanger rods of the commissioning box if needed so that the air diffuser is firmly positioned against the false ceiling or the frame work of the modular suspended ceiling 3 Remove the frontplate section of the air diffuser by applying the Quick Access principle see fi...

Page 2: ... orange The different LED indications Steady green LED Normal operation the air diffuser is operating normally Flashing green LED The air diffuser has just been powered on and calibration is in progress Steady red LED Function failure see separate docu mentation in the TUNE Adapt manual Steady orange LED The commissioning mode max airflow Flashing orange LED Other commissioning modes and all the f...

Page 3: ...f longer distances are required All cables and contacts are different so that they will not be confused or incorrectly connected Electrical data ADAPT is supplied with power via the connection box See the wiring diagram in figure 7 or relevant diagram from the Swegon Templates application containing details for the specific installation It is important that cables with appro priate cross sectional...

Page 4: ...m version without display Q0 1 VA Room version with display Q1 and duct version Q2 3 VA 7c DETECT RH humidity sensor 1 VA 8 ACTUATOR radiator control max 3 valves at 6 VA 9 ADAPT Relay relay for lighting 10 Connection to main control system Modbus RTU 11 SPLIT Link RJ45 12 SPLIT Modbus RJ12 max stab length 10 m Only one of the accessories in paragraph 7 can be connected at any one time in a room i...

Reviews: