background image

Actionair 

SPAN Installation Guide

6

Swegon reserves the right to alter specifications.              20220811 - L00009 (1.2)                                                        

Periodic Maintenance

Manufacturer Recommended Service 

Intervals

•  After commissioning and handover (see DW145 check 

sheet), in order to remain compliant with 15650:2010, 
we recommend that you follow a regular service and 
inspection programme to ensure correct operation 
of dampers in the event the damper is required to 
actuate.

•  In addition to regular physical inspections (in accor-

dance with 15650:2010) we recommend using a 
dedicated damper control panel with a digital reporting 

mechanism (such as an Actionpac LNS system) to fre

-

quently monitor and report on regular remote damper 
testing. 

•  Ensure maintenance is performed in line with the latest 

best practice and relevant local or specialist guidance.

•  Our recommended service intervals for life safety pro-

ducts are as follows:

Interval

Action

Competence

6 Months

Check Actuator Wiring (if appli-

cable) for Damage

Specialist 

Persons

6 Months

Check Limit Switch Wiring (if 

applicable) for Damage

Specialist 

Persons

6 Months

Check Damper Cleanliness, Clean 

and Lubricate if necessary.

Specialist 

Persons

6 Months

Check Condition of Blades and 

Seals, report and rectify if neces-

sary.

Specialist 

Persons

6 Months

Check for blade obstructions

Specialist 

Persons

6 Months

Check Damper Release Me-

chanism (through activation or 

release of the ETR or Thermal 

Fuse Device)

Specialist 

Persons

6 Months

Check damper is left in normal 

operational position after inspec-

tion.

Specialist 

Persons

Monthly

Complete actuation of damper 

from control panel (if installed)

and check all faults. Consult spe-

cialist persons to investigate any 

reported faults.

Facility Ma-

nager

•  *Specialist Persons: A recognised and experienced 

person with prior experience in the inspection and 

assessment of the functional safety of smoke and fire 

damper products. If in doubt, please consult with our 
technical support team for advice. To talk about our 
OEM maintenance inspections, contact our nationwide 
service team.

BS EN 15650:2010 - Ventilation for Buildings 

- Fire Dampers

• 

Section 8.3 states regular testing/ inspection should 

be undertaken to meet regulatory requirements, or at 
intervals not exceeding six months.

•  A comprehensive example of the maintenance pro-

cedure is given in Annex D of the standard. Some 

automatic systems may allow more frequent testing 
(48hr or less) and this may be required by a national 
standard.

Approved Document B, Volume 2

•  Clause 10.12 states adequate means of access must be 

provided to allow inspection, testing and maintenance 

of both fire damper and its actuating mechanism.

BS 9999:2017 - Code of Practice for the Fire 

Safety in the Design, Management and Use 

of Buildings - Annex I

Smoke Control Systems

•  For means of escape states actuation of the system 

should be simulated once a week. It should be ensured 
that any fans and powered exhaust ventilators ope-
rate correctly, smoke dampers close (or open in some 
systems), natural exhaust ventilators open, automatic 
smoke curtains move into position, etc.

Three Monthly

•  In addition to the checks recommended in V.2, V.3 and 

V.4, the actuation of all smoke control systems should 
be simulated once every three months. All zones should 
be separately tested and it should be ensured that any 
fans and powered exhaust ventilators operate correctly, 
smoke dampers close (or open in some systems) etc.

Yearly

•  In addition to the following checks should be made for 

annual inspections and tests of the following to be car-
ried out by competent persons, for any defects to be 

logged and the necessary action taken, and for certifi

-

cates of testing to be obtained.

 

Fire detection and fire alarm systems;

 

– Self-contained luminaires with sealed batteries, if more 

than 3 years old;

 

– Sprinkler, drencher and watermist systems;

 

– Smoke ventilators and smoke control systems;

 

– Fire dampers

BS 9999:2017 - Code of Practice for the Fire 

Safety in the Design, Management and Use 

of Buildings - Annex W

Maintenance of air conditioning and ventilation 

equipment including air filters, motors, fire dampers 

and their controls, smoke detectors and alarms is 

of paramount importance both in preventing fire 

and in ensuring that measures taken to mitigate its 
consequences are effective when needed. Arrangements 

should be made for all fire dampers to be tested by a 

competent person on completion of the installation 
and at least annually, and to be prepaired or replaced 

immediately if found to be faulty. Spring-operated fire 
dampers should be tested annually and fire dampers 

situated in dust-laden and similar atmospheres should 
be tested much more frequently, at periods suited to the 
degree of pollution.

Summary of Contents for Actionair SmokeShield PTC

Page 1: ...nt supplier Actuators All wiring should be carried out in accor dance with the wiring details provided by the IEE and BS regulations and by a competent person Care must be taken when installing and inspecting dampers as they are likely to close without warning due to loss of electrical power or a temperature rise in the ductwork This is their prime function Do not insert any items fingers or limbs...

Page 2: ... with fire separating elements to maintain fire compart ments The SmokeShield is an actuated failsafe close damper with low smoke leakage often referred to in the industry as a Fire Smoke damper Under the Fire Damper Product standard BS EN 15650 our Fire Damper products are tested to BS EN 1366 2 and classified under BS EN 13501 3 For smoke control the product you use should be tested to BS EN 121...

Page 3: ...nto the interface shroud Do NOT fill above damper casing 6 When compound has fully set remove damper inter face transit plate and check the internal is free from any debris remove any debris 7 Follow the actuator installation procedure detailed in this document Comments Rev Drawn By M Bushell Approved By Kimberley M 1 Reference No Gore S Checked By AAF12368 Description If your proposed installatio...

Page 4: ...d the damper casing making sure all the gaps are fully sealed as per industry standard 8 When the first layer has set pour in the next level to 100mm thickness IMPORTANT Compound must not be too watery or runny as it risks penetrating into the interface shroud do NOT fill above damper casing against penetration of compound into interface shroud 9 When compound has fully set remove the shutterbatt ...

Page 5: ...n Both screws should be tightened fully to ensure that both sections of the ETR are closed together It is a safety feature if both sections are not closed the unit will not operate For ductless installations the ETR should be fitted onto the damper spigot not casing above the damper interface shroud and in accordance with the fitting instructions If the ETR is not fitted in the exact manner descri...

Page 6: ...s A comprehensive example of the maintenance pro cedure is given in Annex D of the standard Some automatic systems may allow more frequent testing 48hr or less and this may be required by a national standard Approved Document B Volume 2 Clause 10 12 states adequate means of access must be provided to allow inspection testing and maintenance of both fire damper and its actuating mechanism BS 9999 2...

Page 7: ...LY OPEN AC DC 230V 50 60 Hz 14 VA 12 4 W 30 C 50 C CONTINUOUS TF 72 C AC 250V 6 3 A N CONTINUITY WITH COMMON ELECTRICAL THERMAL RELEASE ETR MUST BE FITTED TO DUCTING FOR DAMPER OPERATION SPRING BIASED TEST SWITCH WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPEN CONTINUITY WITH COMMON WHEN DAMPER CLOSED CONTINUITY WITH COMMON WHEN DAMPER OPEN Supply Off Damper spring closes Mode 5 3P PTC ...

Page 8: ...H WIDTHS AND HEIGHTS OF 200 1000MM FOR DUCT WIDTHS AND HEIGHTS OF 151 199MM FOR DUCT WIDTHS 200MM 1000MM WITH HEIGHTS OF 100 199MM Base Dampers Circular Dampers Series 601 For Circular and Flat Oval Dampers spigots are 3mm under duct size Diameters and flat oval diameters in 1mm increments Circular Dampers Series 601 FOR DAMPERS 100 150MM D FOR CIRCULAR AMPERS SERIES 601 DIAMETERS 151 199MM 2 FOR ...

Page 9: ...red Check wiring in accordance with procedures The ETR cables have been damaged or tampered with Replace with new mode Control Mode operates but limited or no movement of damper blades is observed The mode is not correctly synchronised with the inter face Remove motor from interface Check motor in fully released state Set position of interface and refit motor with label upmost include motor locati...

Page 10: ...pening will invalidate the installation method Damper installer to advise the lead contractor if problems are foreseen 8 Using the access opening provided check that blades open and close Check position of damper blades 9 Has the damper been checked for internal cleanliness free from damage and that vertical casings in particular are free from debris With the damper in the closed position inspect ...

Page 11: ...11 20220811 L00009 1 2 Swegon reserves the right to alter specifications Actionair SPAN Installation Guide Notes ...

Reviews:

Related manuals for Actionair SmokeShield PTC