Valve Control Module
User’s Manual 11
4. Connect each wire to the appropriate input on the terminal strip. Connect a brown, a black, and a blue wire
for each valve to be controlled by the VCM.
a. Loosen the set screw for each wire.
b. Insert the wire in the appropriate location. See Fig. 10.
c. Tighten the set screw.
Note: Put a strain relief in place to prevent the wires from being accidentally pulled out.
5. Repeat steps 2 through 4 for each proximity sensor to be attached to the VCM.
6. Place the enclosure and gasket against the VCM body, lining up both with the mounting holes.
7. Tighten each cable gland nut on the enclosure to 1.00 in. · lb (0.11 N · m) to maintain IP rating.
8. Insert the six enclosure mounting screws with PTFE washers. Tighten the screws hand-tight in the pattern
shown.
Fig. 10 Connect Wire to Terminal Strip
Brown
Black
Blue
Note: Terminal inputs 10 and 20
are no connects.
1
2
5
3
4
6
Fig. 11 Tighten Enclosure Screws
Set
screw