Swadling Brassware Installation Manual Download Page 7

1. Assemble the Temperature handle to the Thermostatic cartridge. 
2. Using the handle rotate anti-clockwise until the Handle temperature stop meets the Cartridge temperature stop and will 
not turn anymore anti-clockwise. This is the maximum hot water temperature  - 

The maximum temperature should not 

exceed 41°c.

 

3. To adjust the maximum temperature - Remove handle, re-position the Handle temperature stop by rotating the handle, 
re-fit handle and turn to stop position, re-test.
If using for a Bath filler see 

IMPORTANT

 page for advised maximum temperatures.

Commissioning notes for Thermostatic Mixing Valves, please check the following

(a) The designation of the Thermostatic Mixing Valve matches the application. (b) The supply pressures are within the valve 
operating range.(c) The supply temperatures are within the valve operating range. (d) Isolating valves are fitted.

If all these conditions are met set the temperature as per installation instructions.
It is a requirement that all TMV2 approved valves shall be verified against the original set temperature results once a 
year. When commissioning/testing is due the following performance checks should be done.

Measure the mixed water temperature at the outlet. Carry out the cold water supply isolation test by isolating the cold 
water supply to the TMV, wait for five seconds if water is still flowing check that the temperature is below 46°C. If there 
is no significant change to the set outlet temperature (+/- 2°C or less change from the original settings) and the fail-safe 
shut off is functioning, then the valve is working correctly and no further service work is required.

Notes; 

If there is a residual flow during the commissioning or the annual verification (cold water supply isolation test)  

then this is acceptable providing the temperature of the water seeping from the valve is no more than 2°C above the 
designated maximum mixed water outlet temperature setting of the valve. Temperature should be taken at normal flow 
rate after allowing for the system to stabilise. The sensing part of the readings thermometer probe must be fully 
submerged in the water that is to be tested. Any TMV that has been adjusted or serviced must be re-commissioned and 
re-tested in accordance with the installation instructions. The installation of the thermostatic mixing valve must 
comply with the requirements of the Water Supply (Water Fittings) Regulations 1999.   

 

SETTING THE 

TEMPERATURE

HANDLE 
TEMPERATURE
STOP

CARTRIDGE
TEMPERATURE
STOP

HO

T STOP

COMMISSIONING 

& MAINTENANCE

Reviews: