4-21
Interfaces of the Device
4.2.5.1
Pin Assignment
Figure 4-19
9 pin D-SUB female connector strip
Connector in the terminal: 9 pin D-SUB female connector
4.2.5.2
Cable
The maximum length of one segment is 50 m which cannot be exceeded. This 50 m
applies from the first node to the last node in the segment.
4.2.5.3
Termination
The bus line is terminated at the connector.
For point-to-point connections, always activate the termination. For multi-point con-
nections, only activate the termination at the cable end. For spur lines, always deac-
tivate the termination.
Table 4-22
Pin assignment MPI
Pin
Designation
Function
1
nc
Not Connected
2
nc
Not Connected
3
RxD/TxD-P
Received Data / Transmitted Data Plus
4
CNTR-P
Repeater Control Signal Plus
5
DGND
Data Transmission Potential
6
VP
Supply Voltage of Terminators Plus
7
nc
Not Connected
8
RxD/TxD-N
Received Data / Transmitted Data Minus
9
CNTR-N
Repeater Control Signal Minus
The D-SUB connector strips must be shielded sufficiently.
See chapter “Shielding D-SUB Connectors“ on page 4-27.
Any cable that conforms with the following parameters can be used:
Table 4-23
Cable characteristics MPI
Parameters
Value
Loop Resistance
110 Ohm/km
Capacitance
30 nF/km
Surge Impedance
150 Ohm
For further information on the installation, please refer to the Siemens manual "SI-
MATIC S7-400 and M7-400 Programmable Controllers Hardware and Installation,
6ES7498-8AA03-8BA0".