UPS-1000-Li-2 User Manual
© 2019 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / surgex.com
9
VII.
Specifications
SYSTEM SPECIFICATIONS
Topology
Line-Interactive, Simulated Sine Wave
Maximum Power Capacity (Battery & Surge
Outlets)
1000VA / 600W
8.3A
Maximum Power Capacity (Surge Only Outlets)
1800W
15A
INPUT
Number of Phases
Single (1
∅
2W +G)
Nominal Voltage
120VAC
Acceptable Input voltage
0 - 150VAC
Voltage Range
90 - 140VAC
Frequency Limits
60 Hz, +/-6Hz
Low Voltage Transfer Point
90V resets to Utility Power at 94V or higher
High Voltage Transfer Point
140V resets to Utility Power at 136V or lower
Input Protection
Resettable Circuit Breaker
OUTPUT NON-BATTERY OPERATION
Voltage Range
104 - 140VAC
Voltage Regulation
120VAC: -13.3% - +16.7%
Frequency Range
60Hz: 54 - 66Hz
Efficiency (Line Mode)
>96% (Full Load)
OUTPUT BATTERY OPERATION
Waveform Type
Simulated Sine Wave (Step Wave)
Nominal Voltage
120VAC
Voltage Regulation
N/-5% (until Low Battery Warning)
Frequency
60Hz, +/-0.5Hz (unless synchronized to utility)
Transfer Time
6 ms Typical
Overload Capacity
AC Mode: 110% for 1-minute then shutdown, 150% Shutdown Immediately
DC Mode: 110% for 20-seconds then shutdown, 150% Shutdown Immediately
Protection
Over-Current, Short-Circuit Protected and Latching Shutdown
REGULATORY COMPLIANCE
Safety and Approvals
Conforms to UL Stds 1778 & 1449
Certified to CSA Std C22.2 No. 8 & C22.2 No. 107.3
FCC Class B