Sur-Gard SG-DV4420 Manual Download Page 5

5

If the transmitter is not communicating (no signal on Rx
led of transmitter) to the central station at this point, call
the telephone Company and ask them to make sure
that the “Leg” is on. The telephone company will ask
you for the circuit number and the leg number which
can be found along with the service telephone number
on a card fixed on the F1/F2 subset.

REQUIREMENTS FOR ULC
INSTALLATION APPROVAL

All components used in the system (contacts, detectors,
etc...) must be ULC listed.

Wire the transformer to the A.C. line according to the
electrical code on a separate circuit breaker.

The F1/F2 subset should be placed in a metal box,
(for example the SUR-GARD SG-UMBX1) close to
the control panel.

The battery must have a minimum ampere hour
capacity of 6.5AH. In case of long time power failure,
the control panel must function normally for 24hrs.

NOTE:

Refer to ULC Standard  booklet “FIRE ALARM
CERTIFICATE SERVICE OF UNDEWRITER’S
LABORATORIES OF CANADA”. You can
contact ULC at Toronto for more information
or to obtain the booklet.

CONTROL POINT INFORMATION

Control point #1: programmable output PGM OUT

The control point #1 can be activated remotely from the
receiver. This is done by sending a command containing
the subscriber unit ID, which identifies to which unit the
command message is addressed and the point ID  which
identifies the control point.

Point ID bytes are split into 2 digits. The first digit specifies
the type of command and the second digit indicates
which control point is to execute the command (on the
DV4420, the control point is always #1). The point ID
byte start with a letter from A to D, giving the desired
output function, as follows:

A. Turn On the specified point.
B. Turn Off the specified point (stop).
C. Turn On for 2 seconds (Pulse) the specified point.
D. Flash the specified point, 2 seconds On, 2 Seconds

Off, until a command is received to stop (B).

When a new command is received, for the programmable
output (control point #1), it replaces the command
previously in effect, if any.

Control point #1 can be activated internally (locally) by
the unit, for an “on time” of 2 seconds, when the SG-
DV4420 receives the “Kiss OFF” character from the
receiver. The “Kiss Off” character is sent by the receiver
as a confirmation signal that the last change of status
message from the SG-DV4420 was correctly received.
This output command takes priority over any command
that output point was already executing.

A. For 50 feet to 100 feet

Use #18 awg shielded 4 conductor cable such
as Provo (Cat. Num. 1782-21) or Belden (Cat.
Num. 9814).

#22 or #24 awg shielded 4 conductor cable.

B. For 100 feet to 500 feet

Use Low Capacitance #24 awg shielded 4 conductor
cable such as ALCATEL (Cat. Num. 371-02-24), Provo
(Cat. Num. 6652-21), or Belden (Cat. Num. 9927) for
the RS-232 communication (Rx, Tx, and SG).

You must also use a 24Vdc power supply (such as
Sur-Gard's SG-2415 24Vdc power supply) close to
the F1/F2 Subset to power it. Make sure to run a
wire (#18 or two #24 awg wires in parallel) between
the negative 24Vdc terminal of the Fire Transmitter
and the power supply, so that they are connected
together.

POWER-UP PROCEDURE

Before applying power to the SG-DV4420 or the F1/F2
subset, connect the 24V output to the “Batt” input of the
F1/F2 subset.

Connect the tansformer, wait approx. 5 seconds. Check
that A1 and A2 loop status led lights are off and the
green “A.C. POWER” led is on. If a led(s) does not turn
off, find the cause (such as loop open or shorted) and
correct it. If the “A.C. POWER LED” is off, find the cause
(such as breaker turned off) and correct it.

NOTE:

To supply AC power to the SG-DV4420, the
transformer should not be connected to an
outlet that is controlled by a switch.

Check for the WATCH-DOG led pulses. This led indicator
flashes once every 10 seconds to show unit is functioning
normally. Activate a zone to be sure that the panel is
responding to signals. If the panel does not respond
and there are no indicators on, check that the wiring is
correct. If the panel is responding normally, connect the
battery. The red battery lead attaches to the positive
battery post and the black battery lead attaches to the
negative battery post.

SYSTEM TESTING

First test the system thoroughly using an SG-DVT1 tester.
Contact the monitoring station to request a transmission
test before connecting the 6 pin modular cable to the
modem. Trip an alarm on any loop. Wait for the
communication to complete and check with the monitoring
station to confirm the transmission. You can use the Rx/
Tx Led indicator to see if the transmitter receives or
transmits. Perform additional transmissions required by
the monitoring station.

The system should be tested on batteries only and AC
only, to be sure that both supplies are present and
adequate. Make sure that the AC Power to the unit is
connected to a separate, well marked, circuit breaker
which will not be turned off by accident.

Summary of Contents for SG-DV4420

Page 1: ...receiver at the central station It includes the 12V power supply battery charger and the 24V power supply for the F1 F2 modem The standby power is obtained from a 12V battery The EEPROM programming is...

Page 2: ...for each installation such as the ID code the all call response etc SERIAL OUTPUT The serial output to the F1F2 subset modem is on a 6 position modular jack A 6 foot modular cable is supplied with the...

Page 3: ...y loop S1 is an End of Line Resistor loop The supervisory loop S1 must have a 2 7K end of line resistor This is not a Class B fire circuit since either a short or an open circuit condition causes the...

Page 4: ...ESTING The SG DV4420 contains factory default programming Any additional programming required is done through the SG DVT1 tester For many applications all that will be required is to enter the ID numb...

Page 5: ...tput command takes priority over any command that output point was already executing A For 50 feet to 100 feet Use 18 awg shielded 4 conductor cable such as Provo Cat Num 1782 21 or Belden Cat Num 981...

Page 6: ...6 SG DV4420 WIRING DIAGRAM N O T USED 14VAC 20VA 14V 14V 14V 14V 14VA C A C A C A C A C...

Page 7: ...7 F1 F2 SUBSET CONNECTION DIAGRAM...

Page 8: ...8 SG DVT1 CONNECTION DIAGRAM...

Page 9: ...ting Factory Writing Factory Writing Factory Writing Factory and Writing COMPLETE Writing COMPLETE Writing COMPLETE Writing COMPLETE Writing COMPLETE Defaults Wait Defaults Wait Defaults Wait Defaults...

Page 10: ...at that address will show SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS SELECT ADDRESS ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 0 ADDR 00 DATA 01 1 1 1 1 The flashing cu...

Page 11: ...l data shown are generally in Decimal Values Except for alarm restore codes which may be in Hex value The locations are in Hex value LOCATION 00 IDENTIFICATION CODE You may change the account identifi...

Page 12: ...programmable output can be activated as indicated below DEFAULT 04 LEFT DIGIT 0X NO INDICATION 1X ALARM ON A1 INDICATION 2X ALARM ON A2 INDICATION 3X ALARM ON A1 OR A2 INDICATION 4X LINE FAULT INDICA...

Page 13: ...sion Select for FIRE TROUBLE A2 02 I____ ____ 07 Transmission Select for SUPERVISORY S1 02 I____ ____ 08 Transmission Select for SUPERVISORY S2 02 I____ ____ 09 Transmission Select for SUPERVISORY S3...

Page 14: ...lm Zn 02 0E 01 18 37 Other Trb Zn D8 Fire A2 0F 03 19 50 Alm Zn 03 0F 01 19 0C Fire Alm Zn 10 Trouble A2 10 04 1A 50 Alm Zn 04 10 02 1A 37 Other Trb Zn D9 Sup 1 11 05 1B 50 Alm Zn 05 11 01 1B 35 Lpres...

Page 15: ...It should be between 24 and 26VDC If more than one panel is connected to the same modem negatives of the panel 24 volts modem power supplies must be connected together 3 Verify the connections betwee...

Page 16: ...polling 7 If there is some but unsatisfactory communication have the telephone company measure the distortion on the leg Each bit transmitted should be near 6 6mS long Distortion can cause bits eg sp...

Page 17: ...17 APPENDIX A SG DS1 WIRING DIAGRAMS...

Page 18: ...18 APPENDIX B SG DV4420 PROGRAMMING FLOW CHART V6 0 V6 0 V6 0...

Page 19: ...is and shall be in lieu of any and all other warranties whether expressed or implied and of all other obligations or liabilities on the part of Sur Gard Security Systems Ltd This warranty contains th...

Page 20: ...1999 SG Security Communications 401 Magnetic Drive Units 24 28 Downsview OntarioCanadaM3J3H9 Tel 416 665 4494 Fax 416 665 4222 TollFree1 800 418 7618 www sur gard com 29000633R001 Printed in Canada...

Page 21: ...INSTRUCTION MANUAL SG DV4420 Software Version 1 1...

Page 22: ...4 MOUNTING THE PANEL 4 HOOK UP PROCEDURE 4 POWER UP PROCEDURE 5 SYSTEMTESTING 5 REQUIREMENTS FOR ULC INSTALLATION APPROVAL 5 CONTROL POINT INFORMATION 5 SG DV4420 WIRING DIAGRAM 6 F1 F2 SUBSET CONNEC...

Page 23: ...24...

Reviews: