background image

Installation

Manual

version 1.4

WARNING

: This manual contains information on limitations regarding

product use and function and information on the limitations as to
liability of the manufacturer. The entire manual should be carefully read.

Sur-Gard MLR2000

Virtual Network Receiver

firealarmresources.com

Summary of Contents for MLR2000

Page 1: ...contains information on limitations regarding product use and function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read Sur Gard MLR20...

Page 2: ...s represented by are the REN without a decimal point e g 03 is a REN of 0 3 For earlier products the REN is separately shown on the label Incidence of Harm If this equipment Sur Gard MLR2000 causes ha...

Page 3: ...DTMF Formats 23 7 3 Acron Format 23 7 4 Ademco Contact ID 23 7 5 Ademco Express 25 7 6 Ademco Super Fast High Speed Format 25 7 7 FBI Super Fast Format 25 7 8 ITI Format 25 7 9 ITI Sensor Library 25...

Page 4: ...NOTE firealarmresources com...

Page 5: ...ommunica tions with the CPM2000 In the event of a malfunction the operator will be advised with a visual indication and the Line Cards will continue to function Each line card will continue to receive...

Page 6: ...er and three serial ports The serial ports are intended primarily for debug applications but may be used for fall back automation outputs optional The primary automa tion connection is via 10BT Ethern...

Page 7: ...e connected to the BNC connector ENET A IN of the backplane Take a 50 ohm coaxial cable and connect one end to the BNC connector ETHERNET B of the CPM2000 The other end of the coaxial cable should be...

Page 8: ...4 Figure 2 72 Line Cards Configuration Expansion cabinet firealarmresources com...

Page 9: ...RT 4 MAN REC COL PAR PAR PORT A PWR JAM ACT Fan Tray 120V 60Hz 10A NOTE Battery wiring should be run in conduit and batteries should be housed in a separate UL Listed enclosure Recommended batter ies...

Page 10: ...urs bac kup batter ies used in conjunction with power gener ator Model INTERSTATE SG8D WARNING To reduce the risk of electric shock this product is provided with a grounding type power supply cord Con...

Page 11: ...7 2 1 4 Signaling Supervisory Connections Figure 5 60 Line Cards Configuration firealarmresources com...

Page 12: ...8 Figure 6 72 Line Cards Configuration Expansion Cabinet firealarmresources com...

Page 13: ...the ACK button on the CPM2000 module to silence the buzzer 2 2 3 Debug Output The debug output is another means of accessing the line card s programmed options and diagnostics features A debug cable i...

Page 14: ...dle module has the con nections shown here Connect each line module output POTS to the telephone line analog with 6 pin modular cables NOTE Use minimum AWG 26 wires for telephone cables NOTE Connectio...

Page 15: ...reset to factory default programming DSP processing to reduce data receiving errors and to help for weak and noisy signals Gain boost available to amplify weak signals Serial link for troubleshooting...

Page 16: ...alls When the CPM2000 Error condition is corrected the alarm messages in the event buffer will be transmitted to the CPM2000 with the corresponding time date the alarm have been received 5 2 DRL2000 C...

Page 17: ...amic Options The static options are the same for all profiles but the dynamic options can be programmed specifically per hunt groups panel type etc By receiving the DNIS or Caller ID the appropriate p...

Page 18: ...CPM2000 BLOCKED CALL 6 3 Static Options 00 2F Option 00 Reserved Option 01 Line Card Number Default 01 The line card Number provides a virtual identification code for each DRL2000 module Hexadecimal...

Page 19: ...ollowing 00 01 04 Do not send to the printer Send to the printer each alarm will print an extra line showing the Caller ID Send to the printer each alarm will print an extra line showing the ANI numbe...

Page 20: ...nd to the handshake given by the line card it will proceed with it s handshake sequence from this profile as opposed to the default profile 00 01 02 A H S Disable A H S enable 10 digits A H S enable i...

Page 21: ...meanings for different companies Because of this the individual event codes in Options 30 through 5F can not accurately represent the alarm condition To over come this Option 70 may be programmed as i...

Page 22: ...replace an account code digit or insert a value into an account code Option A2 is used to replace a digit or insert a digit To replace a digit use 0x where x is the digit to be replaced To shift a di...

Page 23: ...lowest code The sec ond digit indicates the highest zone that will activate audio Option 7D may be used with 10 to 40 Baud for mats DTMF 4 1 4 2 and 4 3 formats Option 7E Audio RS 232 Default 00 This...

Page 24: ...0 When Option 94 is set to 01 the leading digit of a four digit account code will be stripped if it is an F Example Standard 4 2 format Output 1RRLllssssssAAAAsXssYZ Example 1 Option 94 set to 00 Pane...

Page 25: ...es the protocol sent to the computer Note that this option will also affect the BFSK format only if programmed as 00 or 01 00 01 02 03 6500 protocol 1RRLLLssssssAAAAXXYYYY DC4 SG protocol 6RRLLLssssss...

Page 26: ...ed and replaced with a space For example if 02349 is sent then the receiver will output 234 for the panel account Option A7 Silent Knight FSK2 RS 232 Default 00 The DRL2000 provides two possible outpu...

Page 27: ...several examples of Acron transmis sions Handshake Kiss off 2300 Hz 1234 Account Code Example AAAAZZZZZZZZorAAAZZZZZZZZ 9RRLLLssssAAAACCCCCCCC DC4 With option disabled 4 8 Computer 101123ssssss1234sC...

Page 28: ...inger Bypass 320 Sounder relay 402 Group O C Test Misc 600 321 Bell 1 403 Automatic O C 601 Manual trigger test 322 Bell 2 404 Late to O C 602 Periodic test report 323 Alarm relay 405 Deferred O C 603...

Page 29: ...232 output when enable Example FBI RS232 Option On Computer JO112323452032 14 Printer 20 Jul 1998 13 12 29 Jul 20 1998 13 14 51 01 2 SG 01 123 2345 003 PANIC FBI RS232 Option Off Computer 101123 2345...

Page 30: ...e Definitions for information on interpreting the alarm codes Acknowledgments for the SIA format are tonal by default The transmitter may however request data acknowledg ment by transmission of the op...

Page 31: ...ystem Restore AC D60z Trouble phone line 0z DE0z Restore phone line 0z E60z Expand trouble device ID z EE0z Expand restore device ID z E6zz Expand trouble station ID zz zz 17 31 EEzz Expand restore st...

Page 32: ...RESTORE Trble Fx T SYSTEM TROUBLE Alarm 0xx Axx T 0 PER TEST REPORT Alarm 1xx A 1 FIRE ALARM Alarm 2xx A 2 PANIC ALARM Alarm 3xx A 3 BURGLARY Close 4xx C 4 CLOSING Open 5xx O 5 OPENING Alarm 6xx T 6...

Page 33: ...no delay in transfer of information between the Line Card and the CPM2000 The CPM2000 is capable of polling more than 200 Line Cards in less than 2 seconds LCD contrast easily adjusted Hot switching t...

Page 34: ...ued on the Sur Gard console to jump back to the first entry The CPM and automation must connect to all resources announced all the time In the CPM s case this means that a socket is presented for each...

Page 35: ...s are present the CPM2000 will send to the TCP IP until it fails proceed to the serial until it fails pro ceed back to the TCP IP until it fails and so on 10 2 2Second configuration FALL BACK 1 If bot...

Page 36: ...ves data from a Line Card it for wards the data to the automation and awaits an acknowl edgment signal from the computer The CPM2000 also monitors the connection to the computer by sending a superviso...

Page 37: ...ure YZ0002 Serial Port 1 not responding COM 1 Absent YC0001 Serial Port 1 responded ACK COM 1 Restored YK0001 Serial Port 2 not responding COM 2 Absent YC0002 Serial Port 2 started polling COM 2 Resto...

Page 38: ...file Also presented is the selection of ports that may be supervised for the pur poses of restorals or fall down VZ0000 Parallel port Printer Error VZ0001 TCP IP Printer Error YC0001 COM 1 Absent YC0...

Page 39: ...U2000 Power supply Module AC LED It indicates the presence of AC BATTERY OK LED It indicates the battery status ON when battery is charged Trouble LED It indicates a trouble in the power supply fireal...

Page 40: ...be programmed on the receiver to enable different configurations 12 2 Acknowledgment of the Signal The Sur Gard receiver requires an acknowledgment signal ACK Hex 06 from the computer software within...

Page 41: ...CPM will continue to attempt to send a signal to the computer until it gets a response The CPM2000 will use the heartbeat signal to poll auto mation for a response It will make 4 attempts then wait t...

Page 42: ...y NO 2300Hz Radionics 2300Hz 1800Hz 40bps 3 1 parity YES 4 2 parity 2300Hz RadionicsBFSK 1400Hz FSK 42 3 2 NO 1400Hz RadionicsBFSK 2300Hz FSK 42 3 2 NO 2300Hz Sescoa S Speed 2300Hz 1800Hz 40bps 4 3 Ch...

Page 43: ...001 0111 0010 0111 0011 0111 0100 0111 0101 0111 0110 0111 0111 0111 1000 0111 1001 0111 1010 0111 1011 0111 1100 0111 1101 0111 1110 0111 1111 128 129 130 131 132 133 134 135 136 137 138 139 140 141...

Page 44: ...h library on printer Option 70 HEX Character 20 Space 30 0 31 1 32 2 33 3 34 4 35 5 36 6 37 7 38 8 39 9 41 A 42 B 43 C 44 D 45 E 46 F 47 G 48 H 49 I 4A J 4B K 4C L 4D M 4E N 4F O 50 P 51 Q 52 R 53 S 5...

Page 45: ...LATCHKEY DOOR LEFT OPEN RESERVED RESERVED Hex Printer Words 46 47 48 49 4A 4B 4C 4D 4E 4F 50 51 52 53 54 55 56 57 58 59 5A 5B 5C 5D 5E 5F 60 61 62 63 64 65 66 67 68 69 6A 6B 6C 6D 6E 6F 70 71 72 73 74...

Page 46: ...NT CLOSE SOUNDER RELAY DISABLED BELL 1 DISABLE Hex Printer Words CC CD CE CF D0 D1 D2 D3 D4 D5 D6 D7 D8 D9 DA DB DC DD DE DF E0 E1 E2 E3 E4 E5 E6 E7 E8 E9 EA EB EC ED EE EF F0 F1 F2 F3 F4 F5 F6 F7 F8...

Page 47: ...BPS Passed 20 BPS Sescoa Passed 40 BPS Passed BFSK Passed AT T System 8300 10 BPS Passed 20 BPS Passed Ademco High Speed Passed SIA Passed Panel Formats Passed Failed C K System 236 10 BPS Passed 20 B...

Page 48: ...ssed SIA Passed DSC PC5010 V2 X 20 BPS Passed Ademco Contact ID Passed SIA Passed DSC WSS 5010 V2 1 SIA Passed DSC PC5015 V2 20 10 BPS Passed 20 BPS Passed Ademco Contact ID Passed SIA Passed DSC PC50...

Page 49: ...assed Failed Modem IIA Passed Radionics D7112 BFSK Passed Modem IIA Passed Radionics D7212 BFSK Passed Modem IIE Passed Radionics D7412 Not Verified Radionics D8112G2 10 BPS Passed 20 BPS Passed 40 BP...

Page 50: ...ed Westec 5000 Westec Format 6 Not Supported ADT A910 Multi point II Passed ADT Focus D50 ADT SIA Passed ADT Focus 45 Old Focus FSK Passed ADT Focus 45B Multi point II Passed ADT Focus 48 Old Focus FS...

Page 51: ...Most problems that would prevent an alarm system from operating as intended can be found by regular testing and maintenance The complete system should be tested weekly and immediately after a break in...

Page 52: ...rols Ltd Toronto Canada www dsc com Sales 1 888 888 7838 Tech Support Canada USA 1 800 503 5869 Direct all comments concerning this publication to pubs dscltd com Printed in Canada 2 9 0 3 4 6 3 7 R0...

Reviews: