Use the following procedure to adjust the bypass:
1.
Close the valve to
Position A
2.
Turn on the circulation pump
3.
Slowly open the valve towards Position B until the display error code of “E6” disappears.
Once the message clears, the default display is the current water temperature. Starting
sequence will now begin.
ATTENTION
Bypass Installation
Operation without a bypass or with improper bypass adjustment may result in suboptimal
heat pump operation and possible damage to the heat pump. Failure to observe this
instruction will void the warranty.