suprema CoreStation Installation Manual Download Page 17

15

Installation

Relay

Fail Safe Lock

In order to use the Fail Safe Lock, connect the NC relay as shown in the figure below. There is normally a current flowing 

through the relay for the Fail Safe Lock. When the relay is activated, blocking the current flow, the door will open. If the 

power supply to the product is cut off due to a power failure or an external factor, the door will open.

• 

Connect a diode to both ends of the power input as shown in the figure below when installing a deadbolt or a 

door strike. Make sure to connect the Cathode (direction to the stripe) to the + part of the power while paying 

attention to the direction of the diode.

Dead bolt

/ Door strike

DC power

Fail Secure Lock

In order to use the Fail Secure Lock, connect NO relay as shown in the figure below. There is normally no current flowing 

through the relay for the Fail Secure Lock. When the current flow is activated by the relay, the door will open. If the 

power supply to the product is cut off due to a power failure or an external factor, the door will lock.

• 

Connect a diode to both ends of the power input as shown in the figure below when installing a deadbolt or a 

door strike. Make sure to connect the Cathode (direction to the stripe) to the + part of the power while paying 

attention to the direction of diode.

Dead bolt /

Door strike

DC power

Summary of Contents for CoreStation

Page 1: ...CoreStation INSTALLATION GUIDE Version 1 05 English EN 101 00 CS 40 V1 05A...

Page 2: ...TCP IP 14 RS 485 Connection 15 Relay 16 Fail Safe Lock 16 Fail Secure Lock 16 Wiegand IN 17 Door sensor and Exit button 17 AUX IN 18 Product Specifications 19 Dimensions 20 FCC compliance information...

Page 3: ...ons or failure to follow installation instructions can void the manufacturer s warranty Do not install the product in a place with direct sunlight moisture dust soot or a gas leak This may result in e...

Page 4: ...duct by force or do not press them with a sharp tool The product may malfunction Do not store your product in very hot or very cold places It is recommended to use the product at temperatures from 0 C...

Page 5: ...Star 2 8 5 Administrator Guide EN 101 00 BS2 V1 8 5A BioStar 2 8 5 Installation Guide EN 201 00 BS2 V1 01A BioStar 2 Quick Guide Warranty_SP_001 V12 Suprema Warranty Policy Components CoreStation Core...

Page 6: ...0 on the wall Install it to a safe and convenient location for you to use Fixing screws for the enclosure CoreStation and the power supply cable are included in the ENCR 10 package Use each screw corr...

Page 7: ...6 Introduction Name and function of each part 5 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37...

Page 8: ...pervised input 4 5 connection 14 TTL output 0 1 connection 33 TTL output 4 5 connection 15 Wiegand 0 connection 34 Wiegand 2 connection 16 12V output 35 12V output 17 RS 485 0 connection 36 RS 485 2 c...

Page 9: ...ay operation SUPERVISED INPUT 0 7 TTL input Green lighting Normal Close Off Normal Open Supervised Input Green lighting Normal Close short circuit Normal Open Switch On Off Switch Off AUX IN 0 1 Orang...

Page 10: ...reen Yellow The slave device is disconnected Green Blue The slave device is normal Green Off HW error RS 485 2 Sky blue Red No slave device Sky blue Yellow The slave device is disconnected Sky blue Bl...

Page 11: ...can be connected to CS 40 and when DM 20 is connected using a daisy chain Wiegand devices can be expanded up to 132 5 Sensor Wiegand Reader Door Outside Door Inside Door Lock Door Sensor Alarm RS 485...

Page 12: ...1 Introduction Overall Connection Diagram The enclosure contains an LED control board power distribution board power supply battery and tamper 5 5 Do not connect to A receptacle controlled by A switch...

Page 13: ...ion 1 Fix a spacer on the position to mount CS 40 using a fixing screw 2 Fix the product on top of the fixed spacer firmly using a fixing screw Battery Insert the battery velcro strap into the enclosu...

Page 14: ...e the correct power specifications 12V 3A It is recommended to connect and use an Uninterruptible Power Supply UPS to prevent power failure Power Enclosure For UL 294 installation the power source mus...

Page 15: ...connecting to a hub You can connect the product to a hub using a general type CAT 5e cable Hub PC LAN connection connecting to a PC directly CS 40 has automatic MDI MDI X function so it can be connec...

Page 16: ...ends of the RS 485 daisy chain connection If connected to the middle line the signal level will weaken and the communication performance will deteriorate Make sure to connect it to both ends of the da...

Page 17: ...tripe to the part of the power while paying attention to the direction of the diode Dead bolt Door strike DC power Fail Secure Lock In order to use the Fail Secure Lock connect NO relay as shown in th...

Page 18: ...iegand IN Door sensor and Exit button SUPERVISED INPUT terminals No 0 No 7 can be set to be used for normal TTL input or supervised input Other manufacturer s device D1 D0 GND IN IN Door sensor Door E...

Page 19: ...he CS 40 Setup Manager CS 40 Setup Manager is supported with CS 40 firmware version 1 3 1 or later If you are using a firmware version lower than 1 3 1 upgrade the CS 40 firmware on the BioStar 2 For...

Page 20: ...int 100 000 Face 4 000 Max Text Log 5 000 000 Interface Ethernet Support 10 100 Mbps Auto MDI MDI X RS 485 5 ch Wiegand 4 ch Supervised Input 8 ch TTL input selectable TTL Output 8 ch AUX Input 2 ch A...

Page 21: ...19 Product Specifications Dimensions Unit mm The tolerance is 0 3 mm 150 136 101 99 214...

Page 22: ...se limits are designed to provide reasonable protection against harmful interference in a commercial installation This equipment generates uses and can radiate radio frequency energy and if not instal...

Page 23: ...function and design of the product Designers must bear in mind that functions or descriptions indicated as to be implemented or undefined may change at any time Suprema will implement or define such f...

Page 24: ...e and or modify it For the developers and authors protection the GPL clearly explains that there is no warranty for this free software For both users and authors sake the GPL requires that modified ve...

Page 25: ...t code interpreter used to run it The Corresponding Source for a work in object code form means all the source code needed to generate install and for an executable work run the object code and to mod...

Page 26: ...ts parts regardless of how they are packaged This License gives no permission to license the work in any other way but it does not invalidate such permission if you have separately received it d If th...

Page 27: ...the User Product is transferred to the recipient in perpetuity or for a fixed term regardless of how the transaction is characterized the Corresponding Source conveyed under this section must be accom...

Page 28: ...of the violation by some reasonable means this is the first time you have received notice of violation of this License for any work from that copyright holder and you cure the violation prior to 30 d...

Page 29: ...t license to some of the parties receiving the covered work authorizing them to use propagate modify or convey a specific copy of the covered work then the patent license you grant is automatically ex...

Page 30: ...PLICABLE LAW EXCEPT WHEN OTHERWISE STATED IN WRITING THE COPYRIGHT HOLDERS AND OR OTHER PARTIES PROVIDE THE PROGRAM AS IS WITHOUT WARRANTY OF ANY KIND EITHER EXPRESSED OR IMPLIED INCLUDING BUT NOT LIM...

Page 31: ...Exception to Section 3 of the GNU GPL You may convey a covered work under sections 3 and 4 of this License without being bound by section 3 of the GNU GPL 2 Conveying Modified Versions If you modify...

Page 32: ...raries You may place library facilities that are a work based on the Library side by side in a single library together with other library facilities that are not Applications and are not covered by th...

Page 33: ...called OpenSSL nor may OpenSSL appear in their names without prior written permission of the OpenSSL Project 6 Redistributions of any form whatsoever must retain the following acknowledgment This pro...

Page 34: ...the following disclaimer in the documentation and or other materials provided with the distribution 3 All advertising materials mentioning features or use of this software must display the following...

Page 35: ...ames and numbers herein are registered trade marks of Suprema Inc All non Suprema brands and product names are trademarks or registered trademarks of their respective companies Product appearance buil...

Reviews: