6-7 Power Supply
The system has a 400 watt redundant power supply consisting of two power mod-
ules. In the event that one power module fails, the redundant module will keep
the system powered on. The failed power module should be replaced as soon as
possible.
This power supply is auto-switching capable, enabling it to automatically sense and
operate at a 100v to 240v input voltage. New units can be ordered directly from
Supermicro (see contact information in the Preface).
Replacing the Power Supply
Replacing the Power Supply
With redundant power, the system should keep running if a single power module
fails.
1. Remove the AC power cord from the back of the failed power supply module.
2. Push the release tab on the rear of the power supply.
3. Pull the power supply out of the power supply bay using the handle.
4. Push the new power supply module into the power bay until it clicks.
5. Plug the AC power cord back into the module.
Figure 6-8. Power Supply Modules
Summary of Contents for 5018D2-AR12L
Page 1: ...SUPER STORAGE SYSTEM 5018D2 AR12L 5018D4 AR12L 5018D8 AR12L USER S MANUAL 1 0b...
Page 5: ...Notes Preface v...
Page 14: ...1 6 SUPERSTORAGESYSTEM 5018D2 AR12L D4 AR12L D8 AR12L User s Manual Notes...
Page 22: ...2 8 SUPERSTORAGESYSTEM 5018D2 AR12L D4 AR12L D8 AR12L User s Manual Notes...
Page 26: ...3 4 SUPERSTORAGESYSTEM 5018D2 AR12L D4 AR12L D8 AR12L User s Manual Notes...
Page 46: ...4 20 SUPERSTORAGESYSTEM 5018D2 AR12L D4 AR12L D8 AR12L User s Manual Notes...
Page 105: ...Chapter 7 BIOS 7 27 TPM Enabled Status TPM Active Status TPM Owner Status TXT Support...
Page 118: ...7 40 SUPERSTORAGESYSTEM 5018D2 AR12L D4 AR12L D8 AR12L User s Manual Notes...
Page 120: ...A 2 SUPERSTORAGESYSTEM 5018D2 AR12L D4 AR12L D8 AR12L User s Manual Notes...