Superior WRT35STWSI Custom Series Installation And Operation Instructions Manual Download Page 8

www.Superiorfireplaces.US.com

126610-01A

8

Figure 13 - Pipe Connection

Hemmed 

End

12 

3

/

8

Galvanized 

Outer Pipe

8'' Stainless 

Inner Pipe 

Lanced Side 

Up

VENTING INSTALLATION 

Continued

LINEAL GAIN

PART NO.

DESCRIPTION

GAIN

WRT35STWSI See-Through

54"

12-8DM

Flue Pipe

10 

5

/

8

"

18-8DM

Flue Pipe

16 

5

/

8

"

24-8DM

Flue Pipe

23 

5

/

8

"

36-8DM

Flue Pipe

34 

5

/

8

"

48-8DM

Flue Pipe

46 

5

/

8

"

RTL-8DM

RTTL-8DM

Round Top 

Termination

6"

ETL-8M

ETO-8DM

ETLO-8DM

Econo-Top

Termination

1" to 12"

FIRESTOP SPACERS FS-8DM

Firestop spacers are required at each point where the chimney pen-

etrates a floor or ceiling joist space. Their purpose is to establish 

and maintain the required clearance between the chimney and the 

combustible materials.
When penetrating a floor or ceiling at an angle, use firestop spacer 

number FS-8DM (see Replacement parts, page15 and Accessories, 

page 16).
When the pipe passes through a framed opening into a living space 

above, the firestop must be placed onto the ceiling from below as 

shown in Figure 14, page 8. When the pipe passes through a framed 

opening into an attic space above, the firestop must be placed on the 

CHIMNEY PIPE

The IHP chimney system is a snap-lock, double-wall pipe. It consists 

of a stainless steel inner flue pipe(s), a galvanized outer pipe and a 

wire spacer. Each section of pipe comes in lengths of 12", 18", 36" 

and 48". The actual lineal gain for each is measured after each section 

is fully connected. Lineal gain is the actual measurable length of a 

part after two or more parts are connected.

PIPE INSTALLATION

The pipe sections must be assembled independently as the chimney is 

installed. When connecting chimney directly to the firebox, the inner 

flue pipe section must be installed first with the lanced side up. The 

outer pipe section can then be installed over the flue pipe section 

with the hemmed end up. Press down on each pipe section until the 

lances securely engage the hem on the firebox starter. The wire will 

assure the proper spacing between the inner and outer pipe sections.
Continue to assemble chimney sections as outlined above, making 

sure that both the inner and outer pipe sections are locked together 

(see Figure 13). When installing double wall snap-lock chimney 

together, it is important to assure the joint between the chimney sec-

tions is locked. Check by pulling chimney upward after locking. The 

chimney will not come apart if properly locked. It is not necessary 

to add screws to keep the chimney together.

attic floor as shown in Figure 15, page 8.

 WARNING: The opening in collar around chimney 

at top of fireplace must not be obstructed. Never use 

Figure 14 - Firestop Spacer with Living Space Above Ceiling

Figure 15 - Firestop Spacer with Attic Space Above Ceiling

Existing 

Ceiling 

Frame

Firestop 

Spacer

Screws or 

Staples 

(Min. of 8)

Firestop 

Spacer

Screws or Staples 

(Min. of 8)

Existing 

Ceiling 

Frame

Summary of Contents for WRT35STWSI Custom Series

Page 1: ...e is approved for use as a wood burning fireplace or for use with a vented gas log approved to ANS Z21 60 Z21 84 standards or for use with a vent free gas log heater approved to ANS Z21 11 2 standard...

Page 2: ...ire hazard The IHP warranty will be voided by and IHP disclaims any respon sibility for the following actions a Modification of the fireplace or any of the components manu factured by IHP unless other...

Page 3: ...urn veryquickly DONOTusetreatedwood charcoal coal trash driftwoodorwoodsthathavebeendippedintar pitch pine tar creosote etc Wood products made with synthetic binders such as plywood produce ab normall...

Page 4: ...re itshallberemoved to reduce the risk of a chimney fire SAFETY Continued Figure 1 Dimensions WARNING Always leave glass doors fully opened or fully closed when operating fireplace WARNING Children an...

Page 5: ...box Clearances Figure 2 Common Location of Fireplace Existing Wall Projected Wall 12 30 4 cm to Perpendicular Wall MINIMUM CLEARANCE TO COMBUSTIBLES Back and sides of fireplace 1 minimum Adjacent wall...

Page 6: ...cm Min Clearance From Outer Pipes to Combustibles 1 2 5 cm Min To Combustibles 21 5 16 54 cm 42 5 8 108 cm 24 61 cm 12 31 cm Figure 7 Framing Firebox with Z Type Ember Protectors As Required by Desig...

Page 7: ...ies on page 16 Avoid installing outside air eyebrow in areas where inlet opening may be blocked by snow bushes or other obstacles It should also be located beyond the reach of children CAUTION Combust...

Page 8: ...18 36 and 48 The actual lineal gain for each is measured after each section is fully connected Lineal gain is the actual measurable length of a part after two or more parts are connected PIPE INSTALL...

Page 9: ...wall pipe see offset chart and Figure 18 Maximum length of pipe between supports is 6 feet of angled run A Figure 18 Raise and Offset B A Screws Figure 16 Elbow Offset 30 FT 9 14m 30 FT 9 14m Return...

Page 10: ...er elbow and one return elbow Uncommon circumstances such as neighboring hills tall trees or strong wind areas can cause down drafts in chimney system In such cases going beyond the minimum recommende...

Page 11: ...as needed to cover exposed area and flashing base Secure in position by nailing through shingles see Figure 23 DO NOT NAIL THROUGH FLASHING CONE Nail Only Outer Perimeter of Flashing Storm Collar Und...

Page 12: ...e material may be used for facing glass tile brick etc as long as proper clearances are adhered to and firebox openings are not obstructed in any way see Figure 27 Use only heat resistant noncombustib...

Page 13: ...tween gas line and refractory knockout hole with refractory cement or commercial furnace cement Install the gas appliance or cap off gas line if desired CAUTION All gas piping and connections must be...

Page 14: ...llow flames to contact the glass Figure 31 Bi Fold Glass Doors Doors Fully Closed Firebox Front Firebox Front Doors Fully Opened Figure 30 Cabinet Glass Doors Cabinet Glass Doors WARNING FIREPLACESEQU...

Page 15: ...d burns or clothing igni tion Young children should be carefully supervised when they are in the same room as fireplace OPERATION AND MAINTENANCE GUIDELINES Continued REPLACEMENT PARTS Note Use only o...

Page 16: ...Not Shown PUSH ON NUT 11418 Not Shown SCREEN ROD 20806 Not Shown CHIMNEY SUPPORT 12S 8DM FIRESTOP SPACER FS 8DM DOUBLE WALL 30 ELBOW OFFSET 30E 8DM Return Elbow Starter Elbow 8 CHIMNEY PIPE ASSEMBLY 1...

Page 17: ...WITH SLIP SECTION ETL 8DM ETLO 8DM BI FOLD GLASS DOOR DG368ST Brushed Brass DC368ST Platinum DBP368ST Black ACCESSORIES Continued OUTSIDE AIR KIT FOR FLOOR INSTALLATION AK4 ROUND TOP TERMINATION RTL 8...

Page 18: ...____________________________________ ______________________________________________________ ______________________________________________________ _____________________________________________________...

Page 19: ...____________________________________ ______________________________________________________ ______________________________________________________ _____________________________________________________...

Page 20: ...design materials specifications pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2013 IHP LLC P N 126610 01 Rev A 12 20...

Reviews: