background image

www.SuperiorFireplaces.US.com

126868-01A

7

the rooms.

1.  Determine the volume of the space (length 

x width x height).

 

Length x Width x Height =__________cu. ft. 

(volume of space)

 

Example:

 Space size 20 ft. (length) x 16 ft. 

(width) x 8 ft. (ceiling height) = 2,560 cu. ft. 

(volume of space)

 

If  additional  ventilation  to  adjoining  room 

is supplied with grills or openings, add the 

volume of these rooms to the total volume 

of the space. 

2.  Multiply the space volume by 20 to determine 

the maximum Btu/Hr the space can support.

 

 ________ (volume of space) x 20 = (Maxi-

mum Btu/Hr the space can support)

 

Example:

 2,560 cu. ft. (volume of space) x 

20 = 51,200 (maximum Btu/Hr the space can 

support)

3.  Add the Btu/Hr of all fuel burning appliances 

in the space.

 

Vent-free fireplace 

 _________ Btu/Hr

 

Gas water heater* 

 _________ Btu/Hr

 

Gas furnace 

 _________ Btu/Hr

 

Vented gas heater 

 _________ Btu/Hr

 

Gas fireplace logs 

 _________ Btu/Hr

 

Other gas appliances*  +________ Btu/Hr

 Total 

= ________ Btu/Hr

 

* Do not include direct-vent gas appliances. 

Direct-vent draws combustion air from the 

outdoors and vents to the outdoors.

 

Example:

 

 

Gas water heater 

 _____________ Btu/Hr

 

Vent-free fir

 ___________ Btu/Hr

 Total 

= ____________ Btu/Hr

4.  Compare the maximum Btu/Hr the space 

can support with the actual amount of Btu/

Hr used.

 

 _______ Btu/Hr (maximum the space can 

support)

 

 _______ Btu/Hr (actual amount of Btu/Hr 

used)

 

Example:

  51,200  Btu/Hr  (maximum  the 

space can support) 

 

 

73,000 Btu/Hr (actual amount of 

Btu/Hr used)

The space in the example is a confined space 

because the actual Btu/Hr used is more than the 

maximum  Btu/Hr  the  space  can  support. You 

must provide additional fresh air. Your options 

are as follows:

A.  Rework worksheet, adding the space of an 

adjoining room. If the extra space provides an 

unconfined space, remove door to adjoining 

room or add ventilation grills between rooms. 

See 

Ventilation Air From Inside Building.

AIR FOR COMBUSTION AND VENTILATION

Continued

40,000

33,000

73,000

Figure 3 - Ventilation Air from Inside 

Building

Or 

Remove 

Door into 
Adjoining 

Room, 
Option 

Ventilation Grills  

Into Adjoining Room, 

Option 2 

Ventilation

Grills Into

Adjoining 

Room,

Option 1

12" 

12" 

B.  Vent room directly to the outdoors. See 

Ventilation Air From Outdoors

 page 8

.

C.  Install a lower Btu/Hr fireplace, if lower Btu/

Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maxi-

mum Btu/Hr the space can support,

 

the space is 

an unconfined space. You will need no additional 

fresh air ventilation.

 WARNING: If the area in which 

the heater may be operated does 

not meet the required volume for 

indoor combustion air, combus-

tion and ventilation air shall be 

provided by one of the methods 

described in the 

National Fuel 

Gas Code, ANSI Z223.1/NFPA 

54, 

the

 International Fuel Gas 

Code,

 or applicable local codes.

VENTILATION AIR

Ventilation Air From Inside Building 

This fresh air would come from an adjoining 

unconfined  space.  When  ventilating  to  an 

adjoining unconfined space, you must provide 

two permanent openings: one within 12" of the 

ceiling and one within 12" of the floor on the 

wall connecting the two spaces (see options 

1 and 2, Figure 3). You can also remove door 

into adjoining room (see option 3, Figure 3). 

Summary of Contents for VRT4032ZMN

Page 1: ...hese instructions is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in t...

Page 2: ...onvertible for use with other gases Aftermarket Completion of sale not for purpose of resale from the manufacturer WARNING Thisproductcon tainsand orgenerateschemicals known to the state of California...

Page 3: ...type of gas indicated on rating plate This appli ance is not convertible for use with other gases 2 Do not place propane LP supply tank s inside any structure Locate propane LP supply tank s outdoors...

Page 4: ...any part of the control system and any gas control which has been under water Figure 1 Log Base Assembly Top Outer Casing Figure 2 Fireplace Log Set Base Assembly Front Burner Top panel Assembly Firep...

Page 5: ...iscard these screws Push the bottom corners of the screen in and release The screen will pop out at the bottom Grasp the bottom of the screen lift the screen up and pull out to remove 3 Remove protect...

Page 6: ...OR FIREPLACE LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined or unconfined space Space Includes the room in which you will insta...

Page 7: ...n the example is a confined space because the actual Btu Hr used is more than the maximum Btu Hr the space can support You must provide additional fresh air Your options are as follows A Rework worksh...

Page 8: ...entilated Attic Outlet Air Inlet Air Inlet Air Ventilated Crawl Space To Crawl Space To Attic Follow the National Fuel Gas Code ANSI Z223 1 NFPA 54 Air for Combustion and Ventilation for required size...

Page 9: ...LP gas but not both Gas type is indicated on rating plate Field conversion is not permitted ELECTRICAL HOOKUP This fireplace includes a blower which must be connected to either a wall receptacle or t...

Page 10: ...upply page 14 9 Route blower electrical cord through ac cess holes in either side of fireplace CONVENTIONAL FIREPLACE INSTALLATION Conventional installation of this fireplace involves installing firep...

Page 11: ...page 15 INSTALLATION Continued Figure 12 Inserting Fireplace Into Cabinet Mantel BUILT IN FIREPLACE INSTALLATION Built in installation of this fireplace involves installing fireplace into a framed in...

Page 12: ...front facing WARNING Do not allow any combustiblematerialstooverlap the firebox front facing IMPORTANT Noncombustible materials such as brick tile etc may overlap the front facing but should never cov...

Page 13: ...ally tinned copper tubing may be used in certain areas Check your local codes Use pipe of 1 2 diameter or greater to allow proper gas volume to fireplace If pipe is too small undue loss of volume will...

Page 14: ...n Propane LP Supply Tank with Vent Pointing Down External Regulator Propane LP Supply Tank Vent Pointing Down CONNECTING FIREPLACE TO GAS SUPPLY Installation Items Needed 5 16 hex socket wrench or nut...

Page 15: ...A flexible gas line is provided to allow accessibility fromthefireplace seeFigure20 The flexible gas supply line con nection to the equipment shutoff valve should be accessible CHECKING GAS CONNECTIO...

Page 16: ...nts for Propane LP Gas Propane LP Supply Tank Figure 22 Checking Gas Joints for Natural Gas Gas Control Valve Equipment Shutoff Valve Equipment Shutoff Valve Gas Meter Gas Control Valve Open Closed Eq...

Page 17: ...k side of this log needs to rest against the front of the base assembly Make sure the flame from the ember pan does not touch the ember bed log 5 The left middle log has a groove on the bottom to sit...

Page 18: ...rner sections of chassis assembly as shown in Figure 31 9 Place the left top log onto the rear log and the left middle log Make sure to place the projection on the bottom of the left top log into the...

Page 19: ...shown in Fig ure 35 on page 20 by placing the ember chunk with the number 1 on the left 2 in the center and 3 on the right These numbers are embossed on the back of each piece for identification purpo...

Page 20: ...Ember Chunk 1 Ember Chunk 2 Ember Chunk 3 Flat Front Burner Figure 38 Installing Fireplace Screen Magnets Screen Bracket 4 Installfireplacescreenbyplacingthescreen brackets on top of the fireplace scr...

Page 21: ...spect the appliance and to replace any part of the control system and any gas control which has been under water LIGHTING INSTRUCTIONS WARNING Youmustoperate this fireplace with the fireplace screen i...

Page 22: ...d contact a qualified service person or gas supplier for repairs Note If pilot goes out repeat steps 4 through 8 beginning on page 21 9 Slightly push in and turn control knob coun terclockwise to the...

Page 23: ...yellow tipping Dirt or other fine particles are burned by fireplace causing brief patches of orange flame Figure 43 shows the correct burner flame The front ember burner should have a small blue flam...

Page 24: ...ropertydamage BURNER INJECTOR HOLDER AND PILOT AIR INLET HOLE The primary air inlet holes allow the proper amount of air to mix with the gas This provides a clean burning flame Keep these holes clear...

Page 25: ...es when in stalled 5 Depleted gas supply pro pane LP only 6 ODS pilot is clogged 7 Gas regulator setting is not correct REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or...

Page 26: ...andMaintenance page24 or replace burner orifice s 1 Clean burner see Cleaning and Maintenance page 24 or replace burner orifice s 2 Replace damaged burner 3 Replace gas regulator 1 Check burner for di...

Page 27: ...products 1 Replace 9 volt batteries in receiver and remote control 1 Read EMBER PLACE MENT and correct per in structions 2 Replace orifice Call techni cal service 3 Check burner s for dirt and debris...

Page 28: ...d Maintenance page 24 1 Locate and correct all leaks see Checking Gas Con nections page 15 2 Replace control valve or gas control 1 Take apart gas tubing and remove foreign matter 2 Locate and correct...

Page 29: ...ight 122 lbs For input adjustment REPLACEMENT PARTS Note Use only original replacement parts This will protect your warranty coverage for parts replaced under warranty Contact authorized dealers of th...

Page 30: ...126868 01A 30 PARTS LOG BASE ASSEMBLY MODELS VRT4032ZMN VRT4032ZMP VRT4036ZMN AND VRT4036ZMP See page 32 for part numbers 1 2 3 5 29 30 4 7 40 13 21 27 11 10 14 16 15 24 12 36 18 37 38 17 39 35 31 20...

Page 31: ...781 06 Valve Gas LP 0 820 642 1 15 103784 01 Knob Short Extension Pilot 1 16 103784 02 Knob Short Extension HI LO 1 17 107634 01SA Plate NG Conversion 1 18 111435 04 Ignitor Electronic 1 19 112465 01...

Page 32: ...1 101004 10 Orifice 0453 1 15MM Middle 1 37 111819 10 Orifice Elbow P53 95 110 Pan 1 099056 45 Orifice 0 028 0 711MM Pan 1 111819 11 Orifice Elbow P53 95 300 Pan 1 38 124933 01 Orifice Holder 90 Degr...

Page 33: ...423 01 Panel Closure Smooth 2 106651 01 Panel Closure Smooth 2 2 108423 02 Panel Face Top 32 Stamped 2 106684 01 Panel Closure Top Louvered 36 2 3 110037 01 Electrical Duct Assembly 1 4 20280 Spacer T...

Page 34: ...851 06 125852 06 Log Left Middle 1 7 125851 07 125852 07 Log Right Middle 1 8 125851 08 125852 08 Log Rear Middle 1 9 125851 09 125852 09 Log Rear 1 10 125851 10 125851 10 Log Left Top 1 11 125851 11...

Page 35: ...ase these fireplace accessories from your local dealer If they can not supply these accessories call INNOVATIVE HEARTH PRODUCTS at 1 800 655 2008 for informa tion You can also write to the address lis...

Page 36: ...al or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c dam...

Page 37: ...EP THIS WARRANTY Model located on product or identification tag ______________________________ Serial No located on product or identification tag ___________________________ Date Purchased ___________...

Page 38: ...126868 01 Rev A 02 14 1508 Elm Hill Pike Suite 108 Nashville TN 37210 1 800 655 2008 www IHP US com P126868 01...

Reviews: