background image

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

8

Step 5. Fireplace should be secured to side
framing members using the full length nailing
tabs at the top and bottom of the fireplace front
face.  Use 8d nails or equivalent (

Figure 18 ).

Figure 18

Note: The nailing tabs and the area directly
behind the nailing tabs are exempt from the
clearances described on page 5.  Maintain at
least 1/2" clearance from the firebox wrapper to
the framing at the closest point of contact,
directly adjacent to the flange.

For Canadian Installations
Proceed with Steps 6–9

Step 6. Remove one of the knockouts from the
fireplace transition and attach the 4" (102 mm)
collar from the air kit to the transition with four
(4) No. 8 x 

¹⁄₂

" screws provided (

Figure 19 ).

Figure 20

Step 3. Position appropriate firestop spacer at
ceiling and nail temporarily with two (2) 8d
nails. Use flat firestop spacer, Model F10FS-2,
if chimney penetrates ceiling vertically. If chim-
ney penetrates ceiling at 30

°

 angle (offset

chimney), use 30

°

 firestop spacer, Model

F10FS30-2 (refer to page 14 and

 Figures 42

and 43 ). Use one nail on opposite sides to hold
firestop spacer in position. Nail permanently,
using at least two (2) more 8d nails, after
chimney sections have been assembled
through the firestop spacer and after any nec-
essary adjustments have been made. Firestop
spacer must be secured by at least four (4) 8d
nails when completely installed.

Note: If there is a room above ceiling level,
firestop spacer must be installed on the bottom
side of the ceiling. If an attic is above ceiling
level, firestop spacer must be installed on top
side of ceiling joist (Figures 21 and 22 ).

Firestop Spacer

Room Above

Firestop Spacer

Attic Above

Nailing Tab

8d Nail

Framing Stud

Figure 22

Note: If the fireplace is installed against an
inside wall, the Class 0 air duct may be extended
into a ventilated attic space at least 18"
(457 mm) above the attic floor. Secure the duct
hood to a vertical post with the inlet positioned
downward. Ensure nothing blocks the hood
opening. This air duct must never terminate
higher than the chimney.

Step 9. Cut or frame hole through the outside
wall for the installation of the duct inlet hood. A

¹⁄₂

" (114 mm) diameter hole is sufficient. Feed

the loose end of the flexible duct through the
hole cut for the inlet hood and attach to collar on
inlet hood using two (2) No. 6 x 

³⁄₈

" screws

provided. Insert hood into opening. Secure
hood in place with the No. 8 x 1 

¹⁄₂

" screws

provided or with nails driven through holes in
hood flange. Seal with noncombustible water-
proof silicon type caulking. If additional duct is
needed, use Class 0 metallic duct.

INSTALLING THE CHIMNEY SYSTEM

Step 1. Before continuing, check the operation
of the damper, as described on page 4, (

refer to

Figure 3 ).

Step 2. Using standard construction framing
techniques, construct opening for chimney route
up through the ceiling(s) and roof or through an
outside chase.

Framing must maintain adequate minimum air
space clearance at all times.

CAUTION: ALLOW MINIMUM 2" CHIMNEY
AIR SPACE TO COMBUSTIBLE FRAMING MEM-
BERS THROUGHOUT VERTICAL OR OFFSET
CHIMNEY INSTALLATION.

A minimum 2" air space must be reserved for
all combustible materials extending for any
continuous length surrounding the chimney.

Reference 

Figures 16 and 17 and charts Fram-

ing Dimensions for Ceiling and Roof, which
specify minimum ceiling and roof dimensions.

In new construction, to determine chimney cen-
ter line, use plumb line from roof or ceiling above
fireplace to center of flue collar on fireplace.

For remodeling, plumb to center of flue collar
from ceiling above, drive nail through ceiling
from below to mark position, then mark and
cut to passage from above ceiling (around
nail) (

Figure 20 ). Then plumb from ceiling or

roof level directly above hole which has just
been completed.

Optional

Connection

Chimney

Air Kit

Figure 19

Step 7. Connect the 4" (102 mm) Class 0 air
duct to the collar with two (2) No. 8 x 

¹⁄₂

" screws

provided in the hardware kit.

Step 8. Route the Class 0 air duct out the back
wall or side wall, up through the ceiling or floor
joists to an outside wall. The air duct should be
located above snow level.

Plumb Line

Figure 21

Summary of Contents for TM-4500 Series

Page 1: ...tions before beginning your installation Do not alter or modify the fireplace or its components under any circumstances Any modification or alteration of the fireplace system including but not limited...

Page 2: ...our distributor or qualified factory representative to ensure safe condition When in doubt con sult your distributor 16 For additional safety considerations and complete operating instructions refer t...

Page 3: ...ationinresidentialhomesandbuildingsof conventionalconstruction notinmobilehomes These fireplace systems are designed for in stallation in accordance with the National Fire Protection Standard for chim...

Page 4: ...ust be Used to Cover Chase Opening Optional Insulation in Outside Walls of Chase Solid Continuous Surface Outside Base Insulation Thermal Barrier 8 2 4m Level Hearth Hearth Optional Outside Chase Figu...

Page 5: ...ng Usually no special floor support is needed for the fireplace however to be certain 1 Estimate the total weight of the fireplace system including chimney and surround ma terials such as brick stone...

Page 6: ...TED BY THEM Step 4 Fireplace may be anchored to floor Bend down four 4 anchor tabs located at the base of the fireplace and secure to the floor by nailing with 8d nails Figure 10 Note The Z type safet...

Page 7: ...7 445 mm K 67 1702 mm Framing Dimensions Figure 16 Flue Type A B FTF10 19 19 Vertical 483 mm 483 mm FTF10 30 19 29 Offset 483 mm 737 mm Framing Dimensions for Ceiling Figure 14 Figure 15 Pitch C D 0 1...

Page 8: ...ward Ensure nothing blocks the hood opening This air duct must never terminate higher than the chimney Step 9 Cut or frame hole through the outside wall for the installation of the duct inlet hood A 4...

Page 9: ...the roof flashing openings Figure 26 Always maintain 2 minimum air space to com bustiblematerialsandalwayscheckeachchim ney joint inner and outer to ensure proper engagement Checkverticalalignmentofch...

Page 10: ...ntative paint designed for metal This is especially important when installationsaremadeinabnormallyadverseor corrosive environments such as near lakes oceans or in areas with consistently high hu midi...

Page 11: ...sfromtotaldesiredheight Reference Vertical Elevation Chart and deter minethenumberofchimneysections quantity and length required SPECIAL OFFSET INSTRUCTIONS To clear any overhead obstructions you may...

Page 12: ...3 Use Elevation Chart as job estimator only Add necessary firestop spacers and sta bilizers as required Firestop spacers must be used as shown in Figures 21 and 22 and stabilizers as shown in Figure...

Page 13: ...171 14 3 0 0 5 182 15 2 1 0 5 188 15 8 0 1 5 192 16 0 2 0 5 198 16 6 1 1 5 206 17 2 0 0 6 215 17 11 1 0 6 222 18 6 0 1 6 226 18 10 2 0 6 232 19 4 1 1 6 240 20 0 0 0 7 250 20 10 1 0 7 256 21 4 0 1 7 FT...

Page 14: ...s install the same way as round terminations and stabilizers Step 1 Hold return elbow over top of last chimney section Step 2 Center inner slip section into inner flue pipe slip down Step3 Centerouter...

Page 15: ...cts to a gas shut off valve recessed flush into the wall or floor The valve should be controlled by a removable valve key for safety Always plumb gas line installation per local codes Check all connec...

Page 16: ...corner no wall shields are required Fireplace Opening Typical Installation 6 167mm 12 305mm Min Combustible Mantel and Trim Spacer Noncombustible Wall Covering Finished Wall 12 305mm Max 1 38mm Figure...

Page 17: ...4 2 3 4 Cultered Stone Hearth stone 2 82 355 3 36 3 3 8 Wonderboard 3 23 31 3 85 3 7 8 Super Firetemp M Johns Manville 61 1 64 73 3 4 Super Firetemp L Johns Manville 54 1 85 64 5 8 Face brick 9 00 111...

Page 18: ...inations If you encounter any problems or have ques tions concerning the installation or application of this system please contact your distributor For the name of your nearest distributor call LENNOX...

Page 19: ...2 Firestop Spacer Flat 63L36 F10FS 2 Chase Termination Square 63L52 FTF10 CT2RS INSTALLATION COMPONENTS Firestop Spacer 30 63L37 F10FS30 2 Round Termination 63L55 FTF10 CTDTM Termination Shroud 63L56...

Page 20: ...at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A...

Reviews: