Superior GHC-5500 SERIES Installation Instructions Manual Download Page 14

14

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

FINISHING REQUIREMENTS
Wall Details

Note:

 Combustible wall finish materials and/or

surround materials must not be allowed to
encroach the area defined by the appliance
front face (black sheet metal). Never allow
combustible materials to be positioned in front
of or overlapping the appliance front face.

Surround Materials Relative to Appliance
Facing-

Surround materials (noncombustible) can
be placed around the appliance facing to
provide a flush surface between the sur-
round materials and the appliance front fac-
ing. Do not cover the louvers of the GHC or
the bottom control compartment access on
the GRD.

 (Figures 36 and 38 ).

Hearth Extensions

A hearth extension is not required with this
appliance.  Any hearth extension used is for
appearance only and does not have to con-
form to standard hearth extension installa-
tion requirements.

Appliance Facing Flush with Finished Wall -

Complete finished interior wall. To install the
appliance facing flush with the finished wall,
position framework to accommodate the thick-
ness of the finished wall (

Figure 35 and 37 ).

Figure 33

Adjustment

To adjust the flame, position the air shutter to
the nominal setting 

(Figure 33 ).

 Allow the

burner to operate for at least 30 minutes.
Observe the flame continuously. If it appears
weak or sooty as previously described, adjust
the air shutter open or closed until desired
effect is achieved.

WARNING: AIR SHUTTER ADJUSTMENT
SHOULD ONLY BE PERFORMED BY A
QUALIFIED PROFESSIONAL SERVICE
TECHNICIAN.

When satisfied that the appliance operates prop-
erly, proceed to finish the installation. Leave
the control knob/lever in “ON” position and
turn the remote switch “OFF.”  Replace the
refractory access panel.

Orifice

Air Shutter

Burner Tube

Adjusting
Set Screw

Nominal Air Shutter Settings:
Natural Gas - Closed
Propane Gas - 1/6 in. (1.59 mm) Open

Step 12. Adjustments – 

The following para-

graphs address adjustment concerns and pro-
cedures.

Flame Appearance and Sooting

Proper flame appearance is a matter of taste.
Generally most people prefer the warm glow of
a yellow to orange flame. Appliances operated
with air shutter openings that are too large, or
with long vertical vent runs, will exhibit flames
that are blue and transparent. These weak, blue
and transparent flames are termed anemic.

If the air shutter opening is too small sooting
may develop. Sooting is indicated by black
puffs developing at the tips of very long orange
flames. Sooting results in black deposits form-
ing on the logs, appliance inside surfaces and
on exterior surfaces adjacent to the vent termi-
nation. Sooting is caused by incomplete com-
bustion in the flames and a lack of combustion
air entering the air shutter opening.

To achieve a warm yellow to orange flame with
an orange body that does not soot, the shutter
opening must be adjusted between these two
extremes.

No smoke or soot should be present. Reposi-
tion the log set if the flames impinge on any of
them.

If sooting conditions exist, the air shutter open-
ing on the main burner can be adjusted. Nor-
mally, the more offsets in the vent system, the
greater the need for the air shutter to be opened
further.

Summary of Contents for GHC-5500 SERIES

Page 1: ...seur de gaz depuis un voisin Suivez les instructions du fournisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service dos incendies L installationetservicedoit treex cut parunqualif...

Page 2: ...al or propane gas WARNING IMPROPER INSTALLATION ADJUSTMENT ALTERATION SERVICE OR MAINTENANCE CAN CAUSE INJURY ORPROPERTYDAMAGE REFERTOTHIS MANUAL FOR ASSISTANCE OR ADDI TIONAL INFORMATION CONSULT A QU...

Page 3: ...SERI OUS INJURY OR DEATH FORM FIRE BURNS EXPLOSION OR CARBON MON OXIDE POISONING A NPT test gage connection is provided on either gascontrolvalveadjacenttotheoutletto the main burner Minimum inlet gas...

Page 4: ...w 8 216 mm 16 406 mm Left View Gas Inlet Line 10 267 mm Combustion Air Inlet 38 984 mm Right View Left View 15 381 mm 27 705 mm 35 911 mm 6 165 mm Top View 1 25 4 mm Top View 8 216 mm 10 254 mm 16 406...

Page 5: ...t Line 7 191 mm Combustion Air Inlet 40 1029 mm 40 1029 mm 17 454 mm Right View 19 483 mm Left View 17 454 mm 31 787 mm 40 1032 mm 7 197 mm Top View 1 25 4 mm 1 41 mm 13 mm 17 454 mm 31 787 mm 40 1032...

Page 6: ...and the area directly behind the nailing tabs are exempt from the clearances described in the above table See Figure 9 on page 8 o N l e d o M A B C D E 0 0 5 5 D R G C H G n i 3 3 4 1 8 3 4 3 5 1 2...

Page 7: ...ogs and rockwool 9 Install the optional glass doors enclosure panel if required 10 Checkout appliance operation 11 Spillage Test and Safety Limit Switch Operation 12 Adjust burner to ensure proper fla...

Page 8: ...f not install a sediment trap upstreamtopreventmoistureandcontaminants from passing through trap to the appliance con trols and burners Failure to do so could prevent the appliance from operating reli...

Page 9: ...ocation and con nect it to the millivolt circuit using the 18 ft of 2 conductor wire supplied with the unit See Figure 16 Note The supplied 18 feet of 2 conductor wire has one end of each conductor co...

Page 10: ...the screw and washer provided with the plate 4 Refer to Figure 18 and 21 and the instal lationinstructionsprovidedwiththeforced air kit s for blower connections to the appliance receptacle and ground...

Page 11: ...25 Figure 26 Combustion Air Control Lever and Extension on GHC 6500 Series Units Location of Controls GHC GHR 5500 SERIES Step 7 Install Optional Outside Combustion Air Kit When outside combustion ai...

Page 12: ...ors or to lift out panel Figure 28 Figure 29 CAUTION THE APPLIANCE SHOULD ONLY BE OPERATED WITH THE GLASS DOORS FULLY OPEN OR FULLY CLOSED Combustion Air Control Lever and Extension on GRD 6500 Series...

Page 13: ...t the burner push the gas control lever in and toward the left to the ON position Turn ON the remote wall switch Ensure the ignitor lights the pilot The pilot flame should engulf the ignitor Step 11 S...

Page 14: ...PERFORMED BY A QUALIFIED PROFESSIONAL SERVICE TECHNICIAN Whensatisfiedthattheapplianceoperatesprop erly proceed to finish the installation Leave the control knob lever in ON position and turn the rem...

Page 15: ...ering Wall NonCombustible Surround Louvers GHC 5500 Top of Fireplace Opening Top of Fireplace Spacer Framing Combustible Finished Wall Materials Combustible Mantel Noncombustible Covering Wall NonComb...

Page 16: ...elevations greater than that use the correct orifice as shown in table 2 on page 2 Kit part numbers are listed on the next page and the following steps detail the conversion procedure WARNING THIS CO...

Page 17: ...r P o T l a r u t a N n o i t a c i l p p A t i K n o i s r e v n o C s a G t i n U o N s l e d o M l e d o M t i K o N e p y T t i n U o N t r a P D R G C H G 0 0 5 5 0 0 5 5 K C G P N M t l o v i l...

Page 18: ...18 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE...

Page 19: ...19 NOTE DIAGRAMS ILLUSTRATIONS NOT TO SCALE...

Page 20: ...t any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 20...

Reviews: