background image

19

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Installation and Operation Instructions

900299-00, 08/2015

Innovative Hearth Products
DRT40 Multi View Series Direct Vent Gas Fireplace

First Vent

Component
Align the dimple (four places)

with the opening of the locking

incline channel on appliance

collar.  Twist vent component

clockwise to engage and seal.

Locking

Incline Channel

Dimple

Appliance collar

Vent / Appliance Collar

Connection

Align the dimple (four places) of the

upper vent section with the opening of

the locking incline channel on  the

lower vent section.  Twist vent

component clockwise to engage and

seal until arrow and dimple align.

Locking

Incline Channel

Dimple

Arrow

Connected

Vent Sections

Vent / Vent Section

Connection

Arrow

Arrow

Figure 26 

Figure 27 

Figure 29 

Figure 28 

C. Attach vent components to each other -

 Other 

vent sections may be added to the previously 

installed section in accordance with the require-

ments of the vertical vent figures and tables.  

To add another vent component to a length of 

vent run, align the dimpled end over the inclined 

channel end of the previously installed section, 

adjusting the radial alignment until the four 

locking dimples are aligned with the inlets of 

the four incline channels of the previous section. 

Push the vent component against the previous 

section until it fully engages, then twist the 

component clockwise running the dimples down 

and along the incline channels until they seat at 

the end of the channels.

This seating position 

is indicated by the alignment of the arrow and 

dimple as shown in

 

Figure 28.

D.

 

Install  firestop/spacer  at  ceiling  (

Figure 

29 

) -

 When using Secure Vent, use SV4.5VF 

firestop/spacer at ceiling joists; when using 

Secure Flex, use SF4.5VF firestop/spacer. If 

there is living space above the ceiling level, the 

firestop/spacer must be installed on the bottom 

side of the ceiling. If attic space is above the 

ceiling, the firestop/spacer must be installed on 

the top side of the joist. Route the vent sections 

through the framed opening and secure the 

firestop/spacer with 8d nails or other appropriate 

fasteners at each corner. 

Remember to maintain 

1" (25 mm) clearance to combustibles, fram

-

ing members, and attic or ceiling insulation 

when running vertical chimney sections. Attic 

insulation shield (H3907) must be used and 

may help to obtain the required clearances 

indicated here. See installation accessories 

tables on pages 38 and 39.

Vertical (Offset) Installation

Analyze the vent routing and determine the 

quantities of vent sections and number of 

elbows required. Refer to 

Vertical Vent Figures 

and Tables on page 18

 to select the type of 

vertical installation desired. Vent sections are 

available in net lengths of 4-1/2" (114 mm), 

10-1/2" (267 mm), 22-1/2" (572 mm), 34-1/2" 

(876 mm) and 46-1/2" (1181 mm). Refer to the 

Effective Vent Length Chart Table 7 on page 

18

 for an aid in selecting length combinations. 

Elbows are available in 90° and 45° configura-

tions. Refer to 

Figure 30

 

for the SV4.5E45 and 

SV4.5E90 elbow dimensional specifications.   

Where required, a 

telescopic vent section  

(SV4.5LA)

  may be used to provide the installer 

with an option in installing in tight and  confined 

spaces or where the vent run made up of fixed 

length pieces develops a joint in a undesirable 

location, or will not build up to the required 

length. The SV4.5LA Telescopic Vent Section 

has an effective length of from 1-1/2" (38 mm) 

to 7-1/2" (191 mm). The SV4.5LA  is fitted with 

a locking inclined channel end (identical to a 

normal vent section component) and a plain end 

with 3 pilot holes. Slip the plain end over the 

locking channel end of  a standard  SV4.5 vent 

component the required distance and secure 

with three screws.

Maintain a minimum 1" (25 mm) clearance to 

combustible materials for all vertical elements. 

Clearances for all horizontal elements are 3" 

 

(76 mm) on top, 1" (25 mm) on sides and 1" 

 

(25 mm) on the bottom.

A.

 

Frame ceiling opening -

 Use a plumb line 

from the ceiling above the appliance to locate 

center of the vertical run. Cut and/or frame an 

opening, 10-1/2" x 10-1/2"  (267mm x 267mm) 

inside dimensions, about this center mark 

(

Figure  26

 

).

To attach a vent component to the appliance 

collar, align the dimpled end over the collar, 

adjusting the radial alignment until the four 

locking dimples are aligned with the inlet of 

the four inclined channels on the collar (

refer to 

Figure 27 

).  Push the vent component against 

the collar until it fully engages, then twist the 

component clockwise, running the dimples 

down and along the incline channels until they 

seat at the end of the channels.  The unitized 

design of the 

Secure Vent

 components will 

engage and seal both the inner and outer pipe  

without the need for sealant or screws.  If desired 

a #6 x 1/2" screw may be used at the joint, but 

it is not required as the pipe will securely lock 

when twisted.

Note:

 An elbow may also be attached to the 

appliance collar.  Attach in the same manner 

as you would a vent section. 

B.

 

Attach vent components to appliance -

 

Se-

cure Vent

®

 SV4.5 direct vent system compo-

nents are unitized concentric pipe components 

featuring positive twist lock connections (

see 

Figures 27 and 28

 ).  

All of the appliances covered in this document 

are fitted with collars having locking inclined 

channels. The dimpled end  of the vent com-

ponents fit over the appliance collar to create 

the positive twist lock connection.

1” (25.4 mm) 

Minimum 

Clearance to

Combustibles

8 ft. (2.4 M)

Maximum

v

 SV4.5VF

Firestop / 

spacer

u

SV4.5SP

Support Plate

u

SV4.5SU

Support Strap

Shown With 

Optional 

Radiant 

Panels

u

Secured 

to Vent with 

Appropriate 

Fasteners

Ceiling

Framing

v

When 

using 

secure 

Flex, use 

Firestop/

Spacer 

SF4.5VF

SV4.5FA or

SV4.5FB Flashing

and SV4.5SC 

Storm Collar

SV4.5CGV-1

Termination

10-1/2" Min. 

(267 mm)

10-1/2" Min. 

(267 mm)

Attic Insulation shield

Summary of Contents for DRT40CL40DEN

Page 1: ...urnisseur Si vous ne pouvez rejoindre le fournisseur de gaz appelez le service des incindies L installationetl entretiendoivent treassur spar un installateur ou un service d entretien qualifi ou par l...

Page 2: ...DE TOUCHER LA VITRE EL VIDRIO CALIENTE CAUSAR QUEMADURAS USTED DEBE NUNCA TOCAR EL VIDRIO CALIENTE LOS NI OS DEBEN NUNCA TOCAR EL VIDRIO L cran pare tincelles fourni avec ce foyer r duit le risque de...

Page 3: ...uede causar quemaduras graves si se toca Mantenga a los ni os alejados de la chimenea en funcionamiento Supervise en forma cercana a los ni os en cualquier cuarto donde haya una chimenea funcionando p...

Page 4: ...ic stone and one bag of vermiculate is located in the bottom compartment 5 oneventrestrictortobeappliedasshownon page14 restrictoristapedtotheenvelope 6 barriers 7 front face assemblies NOTE If the ba...

Page 5: ...e absence of local codes with the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition or the Natural Gas and Propane Instal lation Code CSA B149 1 The appliance when installed must be electri ca...

Page 6: ...Vent Requirements IntheCommonwealthofMassachusetts hori zontal terminations installed less than seven 7 feet above the finished grade must comply with the following additional requirements A hard wir...

Page 7: ...ir tightness and caulk firestops MANUFACTURED HOME REQUIREMENTS Thisappliancemaybeinstalledinanaftermarket permanently located manufactured home and must be installed in accordance with the manu factu...

Page 8: ...ada Vertical Vent Termination Clearances Terminatemultipleventterminationsaccordingto the installation codes listed above and Figures 4 and 5 Note See Figure 42 on Page 22 for the exterior wall recess...

Page 9: ...m 5 127 mm minimum G Clearance to inside corner 6 152 mm minimum 6 152 mm minimum H Clearance to each inside of center line extended above meter regulator assembly 36 910 mm within a height of 15 ft a...

Page 10: ...ible materials such as surrounds and other appliance trim may be installed on the appliance face with these exceptions they must not cover any portion of the removable glass panel or control compartme...

Page 11: ...Bottom SERVICE CLEARANCES Feet meters Front Back Sides 3 feet 0 9 meters Table 5 Figure 10 Unit Parts Identification Detailed Installation Steps The appliance is shipped with all gas controls and com...

Page 12: ...s and or rear of the unit using the factory providednailingflanges Installthenailing flanges 8 DRT40ST 4 DRT40PF DRT40CL and DRT40CR as shown in Figure 12 using the existing screws Position the firepl...

Page 13: ...drywall For 1 2 drywall use 23 Provide Additional Space For Side Vent Seal Cap If Installing Against A Solid Wall LibraPF Peninsula Gas Line Center of gas line is 3 in 76 mm up from floor 41 1 2 1054...

Page 14: ...1 4 1200 37 3 4 959 40 3 16 1021 41 1041 37 940 34 1 8 867 23 7 16 595 27 3 4 705 23 7 8 607 41 1041 2 51 FRAMING SPACERS Top and both sides FINISHED WALL BRACKET Front and back edge of unit top Step...

Page 15: ...ner Right 10 5 16 262 12 303 3 76 6 7 8 174 41 1041 34 1 8 867 1 26 25 9 16 649 23 7 8 607 21 3 8 543 37 11 16 957 45 7 16 1154 11 3 8 289 10 254 21 3 8 543 TOP VIEW FRAMING SPACERS Top and both sides...

Page 16: ...hutoff valve See Step 7 on Page 30 Installingagassupplylinefromthefuelsupplyto theapplianceinvolvesnumerousconsiderations of materials protection sizing locations con trols pressure sediment andmore C...

Page 17: ...wall such as a chase There is no requirement for inspection openings in the enclosing wall at any of the joints in the vent pipe Installation of Vent Restrictor A vent restrictor may be needed with th...

Page 18: ...5 2 1 9 1 0 0 1 6 0 7 5 2 3 2 5 7 3 9 1 0 0 0 0 5 5 7 3 2 5 7 9 1 1 0 0 0 5 6 5 1 4 2 5 2 1 0 2 0 0 0 7 0 7 6 4 2 5 0 2 1 0 0 7 0 8 2 5 2 1 2 0 1 0 7 0 8 4 6 2 2 2 0 0 1 7 0 8 6 7 2 3 2 0 0 0 8 0 8 9...

Page 19: ...the Effective Vent Length Chart Table 7 on page 18 for an aid in selecting length combinations Elbows are available in 90 and 45 configura tions Refer to Figure 30 for the SV4 5E45 and SV4 5E90 elbow...

Page 20: ...e vent outlet One method of support is by utiliz ing field provided support straps conventional plumber s tape Secure the plumber s tape to theframingmemberswithnailsorscrews Loop the tape around the...

Page 21: ...Top Vent STRAIGHT Figure 37 Top Vent TWO 90 DEGREE ELBOWS 40 feet 12 2 meters Maximum uCeiling Firestop Spacer SV4 5VF uWhenusingSecureFlex use Firestop Spacer SF4 5VF uCeiling Firestop Spacer SV4 5V...

Page 22: ...using Secure Flex use Firestop Spacer SF4 5VF vWhen using Secure Flex use Firestop Spacer SF4 5HF uCeiling Firestop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF Table...

Page 23: ...a joint does not occurintheceilingorroofjoists Allowforelbows as indicated in Figure 30 on page 18 Maintain a minimum 1 25 mm clearance to combustiblesontheverticalsections Clearances for the horizont...

Page 24: ...adaptor for a particular range of wall thicknesses L Install Firestop Spacer at exterior wall When using the square termination install SV4 5HF Secure Vent SF4 5HF Secure Flex Firestop Spacer over the...

Page 25: ...anytime vent pipe passes through a combustible floor or ceiling SV4 5HF Secure Vent SF4 5HF Secure Flex firestop spacer must be used anytime vent pipe passes through a combustible wall Note Secure Ven...

Page 26: ...ical vent will be required Thistableshowsa1 V to5 H ratio Forevery1 foot of V vertical you are allowed 5 feet of H H1 horizontal run up to a maximum horizontal run of 20 feet Table H H H1 Maximum V Mi...

Page 27: ...ft 12 192 m Max V H H1 V1 v Wall Firestop Spacer SV4 5HF uCeiling Firestop Spacer SV4 5VF uCeiling Firestop Spacer SV4 5VF vWall Firestop Spacer SV4 5HF vWall Firestop Spacer SV4 5HF Figure 47 Side Ve...

Page 28: ...dofMill PacBlack 700 F high temperature sealant Catalog No 10K81 to the inner adaptor collar approximately 1 2 inch from the end 3 Pull and extend the inner flexible vent pipe 4 Slide the inner flex p...

Page 29: ...0VAC power supply 2 Install the junction box and receptacle outlet to the left of the valve in the front for optional blower kit See junction box and receptacle outlet as explained in steps 1 11 for B...

Page 30: ...d in the gas piping within the home to prevent moisture and debris in the line from damaging the valve These appliances are equipped with a gas flex lineforuse wherepermitted inconnectingthe unit to t...

Page 31: ...sly the left and right top corners of the door The door is hinged at the bottom Removethebottomcompartmentdoor by sliding the hinge pin located at the door s left side to the right until it disengages...

Page 32: ...Replace logs if removed for pilot inspection To light the burner turn ON the remote wall switch and rotate the gas valve control knob counterclockwise to the ON position ON will be at the top side of...

Page 33: ...BURNER Note This appliance is provided with enough Glowing Embers for several applications do not use all that is in a new bag at one time For best glowingeffect replacetheembermaterialannually Replac...

Page 34: ...he Grate And Slide It Forward Against The Grate Here Position Log 2 Over The Grate Bar And Slide It Against The Back Of The Grate Here Position Groove At The Bottom Of Log 2 Over The Grate Here And Sl...

Page 35: ...ire log set 55M04 2 6 5 4 1 3 Figure 62 3 Grate Assembly 5 Position Small End Of Log 6 On The Notch Of Log 3 Here 6 4 Position The Round End Of Log 6 Against The Notch Of Log 4 Here Two Charred Spots...

Page 36: ...the top flange of thedoorframeoverthetopofthefireboxframe Let the bottom of the door frame swing gently intowardsthefireplaceensuringthatthegasket seats evenly as the door frame draws shut Fasten the...

Page 37: ...ly to ensure that the proper flame appearance has been achieved If the following conditions are present adjust accordingly If flame appears weak or sooty adjust the air shutter incrementally to a more...

Page 38: ...Figure 65 Air Shutter Adjusting Rod Orifice Increase Shutter Opening In This Direction Decrease Shutter Opening In This Direction Note Burners are omitted in this view for clarity MAIN BURNER FACTORY...

Page 39: ...z que l interrupteur contr le le fonctionnement du foyer en le faisant basculerdeMarche Arr t etvice versa Nettoyez soigneusement la plaque murale de l interrupteur ou le thermostat mural pour liminer...

Page 40: ...lashings come packaged with a storm collar 77L78 SV4 5F Flat Roof Flashing 77L79 SV4 5FA 1 12 to 7 12 Adjustable Flashing 77L80 SV4 5FB 7 12 to 12 12 Adjustable Flashing 77L81 SV4 5SC6 Storm Collar 6...

Page 41: ...Cat Model Description 17M52 SV4 5HGS 1 Termination Guard Square 1 pack Ref instr 750 109M 17M53 SV4 5HGS 12 Termination Guard Hori zontal Square 12 pack Ref instr 750 109M 87L02 SV4 5HGS Termination G...

Page 42: ...nel by the tab on the panel s right end pull the right end of the panel away from the cabinet and then pull the panel diagonally out of the left side cabinet panel slots In the above procedure reverse...

Page 43: ...models Figure 72 illustrates the orifice Always check and verify correct orifice size B Install the burner as shown in Figure 73 When reinstalling the igniter assembly use extreme care to prevent dam...

Page 44: ...il ni proximit WARNING Children and adults should be alerted to the hazards of high surfacetemperatureandshould stay away to avoid burns or clothing ignition CARE AND OPERATIONS WARNINGS Burn in Perio...

Page 45: ...euvent subir des br lures s ils viennent en contact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer...

Page 46: ...burning pilot flame Exercise caution when using products with combustible vapors H I LO W TPTH TP TH P I L O T P I L O T O N i t OFF Variable Flame Height Adjustment Manifold Pressure Port Inlet Press...

Page 47: ...nea verifiquequeelinterruptor opera la chimenea encendi ndola y apag ndola Limpiebienlaplacadelinterruptoroeltermostatode paredparaquitarelpolvoyaceite Peguelaetiqueta enlasuperficiedelaplacadelinterr...

Page 48: ...tion should include ensuring that exhaust or intake passages are unobstructed and vent components are properly assembled and not damaged Homeowner must contact a qualified service technician at once i...

Page 49: ...front glass enclosure panel should not be re moved except to gain access to the components within the firebox Removing Glass Enclosure Panels see Figure 76 To access the glass door securing latches fi...

Page 50: ...is provided with enough Glowing Embers for several applications do not use all that is in a new bag at one time For best glowingeffect replacetheembermaterialannually ReplacementGlowing Embers are ava...

Page 51: ...he Grate And Slide It Forward Against The Grate Here Position Log 2 Over The Grate Bar And Slide It Against The Back Of The Grate Here Position Groove At The Bottom Of Log 2 Over The Grate Here And Sl...

Page 52: ...ire log set 55M04 2 6 5 4 1 3 Figure 80 3 Grate Assembly 5 Position Small End Of Log 6 On The Notch Of Log 3 Here 6 4 Position The Round End Of Log 6 Against The Notch Of Log 4 Here Two Charred Spots...

Page 53: ...ot soot the shutter opening must be adjusted between these two extremes Air Shutter Adjustment Guidelines Amount of Primary Air Flame Color Air Shutter Adjustment If air shutter is closed too far Flam...

Page 54: ...ance is achieved If flame remains blue adjust the air shutter incrementally to a more closed position until the proper flame appearance is achieved 4 Leave the control knob off pilot on in the ON posi...

Page 55: ...he appliance 3 The part number 4 The description of the part 5 The quantity required 6 The installation date of the appliance If you encounter any problems or have any questions concerning the install...

Page 56: ...n Timer Includes batteries Child lock Low battery indicator Receiver may be wall mounted or placed in the valve compartment Cost Effective Solution Simple On Off operation Workswithmillivoltandlowvolt...

Page 57: ...of the fireplace burner Install the OFF ON wallswitchinaconvenientlocationnearthefireplace WhiteWallSwitchKit Cat No ModelNo Description 85L87 FWSK OFF ONWallSwitchKit Accessory Components CONTINUED...

Page 58: ...gs excessive condensation can be caused by long lateral runs too many elbows and or exterior portions of the system being exposed to cold weather Also inspect wall straps or plumbers s tape to ensure...

Page 59: ...released stop and immediately call your service technician or gas supplier LIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCE If the pilot will not stay lit after several tries turn the gas control kn...

Page 60: ...arr ter et appeler imm diatement un technicien qualifi ou le fournisseur de gaz Si la veilleuse ne reste pas allum e apr s plusieurs tentatives r glez la manette d admission du gaz la position OFF et...

Page 61: ...appliance 10 If applicable Set thermostat to desired setting Turn wall on off switch unit mounted on off switch or remote control switch ON 11 Close control compartment OPERATING INSTRUCTIONS 1 If ap...

Page 62: ...applicable R glez le thermostat la temp rature la plus basse Tournez e c n a t s i d e l r t n o c e l u o t i n u l r u s r u e t p u r r e t n i l e l a r u m r u e t p u r r e t n i l OFF 2 Coupez...

Page 63: ...lve system troubleshooting should only be accomplished by a qualified service technician Clean and or adjust pilot flame for maximum flame impinge ment on thermocouple Figure 11 on page 14 Check burne...

Page 64: ...Voltage Transformer Limit Controller Thermostat Wiring 2 CHECK START NO Plug Control Harness Into Valve Wait For Internal Check Delay YES Igniter Warms Up And Glows Red With Pilot Burner Cable Connec...

Page 65: ...Assembly 55M42 1 1 1 1 9 Gasket Venturi Tube Mounting 43K85 1 1 1 1 10 Venturi Tube Arm 42M80 1 1 1 1 11 Switch Rocker 80L41 1 1 1 1 12 Air Shutter Adjustment Rod H3707 1 1 1 1 13 Flexline Gas Conduc...

Page 66: ...LACEMENT PARTS LIST continued GAS CONTROLS HONEYWELL Electronic GAS CONTROLS SIT Millivolt No DESCRIPTION Natural Propane Part No Qty Part No Qty 30 Gas Valve SIT H6209 1 88J53 1 31 Piezo Igniter 10K8...

Page 67: ...ural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c d...

Page 68: ...ial number Date fireplace was Installed Type of gas fireplace uses Dealer name Innovative Hearth Products reserves the right to make changes at any time with out notice in design materials specificati...

Reviews: