
2.0 APPLIANCE DATA
3
Destination Country
Cat
Inlet/Operating
Pressure (±2.0 mbar)
Max Energy Input (kW)
Min Energy Input (kW)
G20
G25
G30
G31
Gross
Net
Gross
Net
GB - IE
I2H
20
-
-
-
2.6
2.35
1.5
1.35
Natural Gas
GB IE
©
2011 Focal Point Fires plc.
Flow Restrictor Orifice
1.18mm
Oxypilot (Natural Gas Models)
SIT 9082
Gas Control (All Models)
Copreci 21400 Series
Gas Inlet
8mm
Ignition
Double Piezo Spark
Spark Gap
3.5 - 4.5mm
Please see Data Badge affixed to appliance for current data.
This appliance is for use only with the gas type, and at the pressure stated on the appliance Data Badge.
3.0 INSTALLATION REQUIREMENTS
If the appliance is to be sited near a disused or unserviceable fireplace served by a natural draught flue then the old flue must be
sealed off. It will be necessary to ventilate the old flue to prevent condensation and dampness forming, however any air vent used
to ventilate the old flue must not be sited within 500mm of this appliance. If the flue can be ventilated to the outside of the build-
ing then this is usually the best solution. If in doubt then advice should be sought from a local building control officer.
The appliance is designed to be wall mounted. If the appliance is to be mounted on a newly fabricated area of wall that also serves
the purpose of sealing off the old flue then it is very important that there are no holes, gaps or otherwise in this wall that will
allow draughts from the old flue to enter the room, especially directly behind the appliance. Such draughts could affect the per-
formance of the ODS system and result in nuisance cutting out, for example. If the gas supply pipe is to enter the appliance from
the rear, i.e. emerge from the wall behind the appliance, then any hole in the wall from which the pipe emerges must be tightly
sealed.
The room size
MUST
be a minimum of 30m
3
(e.g. 3.5m x 3.5m x 2.45m or 11'6" x 11'6" x 8').
This is to allow adequate circulation of air and ensure the correct operation of the fire. This volume may include adjacent spaces
but these spaces must not be separated by a door.
Note :
To calculate a room size in cubic metres (m
3
) divide the room volume
in cubic feet (ft
3
) by 35.3.
This appliance may be installed in any room in the home except bathrooms. In accordance with BS5871 part 4, installation in bed-
rooms is permitted. If the appliance is to be installed in a bedroom then an electronic carbon monoxide detector complying with
the current edition of BSEN 50291 must be installed in the same room as the appliance. For maximum safety it is recommended
that such device is continuously (mains) powered and arranged in such a way that the gas supply to the appliance is isolated in
the event of an alarm. The selection and installation of such device shall be in accordance with the current edition of BSEN 50292,
and the user must be briefed regarding the use and maintenance of such a device.
The appliance is designed to be versatile, and as such will operate correctly when exposed to normal gentle draughts experienced
within the home. It is not recommended, however that the appliance be installed in areas where it is likely to be directly exposed
to persistent strong draughts, that may be generated by outside doors, windows, air vents, air conditioning units, extractor fans,
ceiling fans etc. See section 4.1 for more information on ventilation.
Clearances to non-combustible materials
Non combustible surfaces are defined as brick, metal, marble, concrete etc. and also a
number of man-made materials impervious to flame. If in doubt refer to the material
manufacturer for further information before proceeding with installation.
Clearances to the sides of the appliance are 100mm (4”). Clearance to the front of the
appliance is 500mm (20”).
The back of the appliance may be installed directly onto a non-combustible wall, pro-
viding the area behind the appliance is flat and does not interfere with the various vent holes in the back panel of the appliance.
A non combustible shelf of any depth may be positioned above the appliance provided it is no closer than 400mm (16”) from the
top of the appliance glass panel and the wall above the appliance is non combustible. The appliance must not be positioned ver-
tically within 60mm (2.4”) of a solid floor (i.e. wood or stone) or hearth. This dimension is measured vertically to the bottom of
the appliance firebox.
3.1 ROOM SIZING
4.0 SITE REQUIREMENTS
This appliance is designed to be
wall-hung. Do not recess any part
of the appliance into the wall.
WARNING