superior fires CORINTHIA BLACK NG Installation & User'S Instructions Download Page 3

2.0 APPLIANCE  DATA

3

Destination Country

Cat

Inlet/Operating 

Pressure (±2.0 mbar)

Max Energy Input (kW)

Min Energy Input (kW)

G20

G25

G30

G31

Gross

Net

Gross

Net

GB - IE

I2H

20

-

-

-

2.6

2.35

1.5

1.35

Natural Gas

GB IE

©

2011 Focal Point Fires plc.

Flow Restrictor Orifice

1.18mm

Oxypilot (Natural Gas Models)

SIT 9082

Gas Control (All Models)

Copreci 21400 Series

Gas Inlet 

8mm

Ignition

Double Piezo Spark

Spark Gap 

3.5 - 4.5mm 

Please see Data Badge affixed to appliance for current data.
This appliance is for use only with the gas type, and at the pressure stated on the appliance Data Badge.

3.0 INSTALLATION REQUIREMENTS

If the appliance is to be sited near a disused or unserviceable fireplace served by a natural draught flue then the old flue must be
sealed off. It will be necessary to ventilate the old flue to prevent condensation and dampness forming, however any air vent used
to ventilate the old flue must not be sited within 500mm of this appliance. If the flue can be ventilated to the outside of the build-
ing then this is usually the best solution. If in doubt then advice should be sought from a local building control officer.

The appliance is designed to be wall mounted. If the appliance is to be mounted on a newly fabricated area of wall that also serves

the purpose of sealing off the old flue then it is very important that there are no holes, gaps or otherwise in this wall that will
allow draughts from the old flue to enter the room, especially directly behind the appliance. Such draughts could affect the per-
formance of the ODS system and result in nuisance cutting out, for example. If the gas supply pipe is to enter the appliance from
the rear, i.e. emerge from the wall behind the appliance, then any hole in the wall from which the pipe emerges must be tightly
sealed. 

The room size 

MUST

be a minimum of 30m

3

(e.g. 3.5m x 3.5m x 2.45m or 11'6" x 11'6" x 8'). 

This is to allow adequate circulation of air and ensure the correct operation of the fire. This volume may include adjacent spaces
but these spaces must not be separated by a door.  

Note :

To calculate a room size in cubic metres (m

3

) divide the room volume

in cubic feet (ft

3

) by 35.3. 

This appliance may be installed in any room in the home except bathrooms. In accordance with BS5871 part 4, installation in bed-
rooms is permitted. If the appliance is to be installed in a bedroom then an electronic carbon monoxide detector complying with
the current edition of BSEN 50291 must be installed in the same room as the appliance. For maximum safety it is recommended
that such device is continuously (mains) powered and arranged in such a way that the gas supply to the appliance is isolated in
the event of an alarm. The selection and installation of such device shall be in accordance with the current edition of BSEN 50292,
and the user must be briefed regarding the use and maintenance of such a device.  
The appliance is designed to be versatile, and as such will operate correctly when exposed to normal gentle draughts experienced
within the home. It is not recommended, however that the appliance be installed in areas where it is likely to be directly exposed
to persistent strong draughts, that may be generated by outside doors, windows, air vents, air conditioning units, extractor fans,
ceiling fans etc. See section 4.1 for more information on ventilation.

Clearances to non-combustible materials

Non combustible surfaces are defined as brick, metal, marble, concrete etc. and also a
number of man-made materials impervious to flame. If in doubt refer to the material
manufacturer for further information before proceeding with installation.
Clearances to the sides of the appliance are 100mm (4”). Clearance to the front of the
appliance is 500mm (20”). 
The back of the appliance may be installed directly onto a non-combustible wall, pro-

viding the area behind the appliance is flat and does not interfere with the various vent holes in the back panel of the appliance.

A non combustible shelf of any depth may be positioned above the appliance provided it is no closer than 400mm (16”) from the

top of the appliance glass panel and the wall above the appliance is non combustible. The appliance must not be positioned ver-
tically within 60mm (2.4”) of a solid floor (i.e. wood or stone) or hearth.  This dimension is measured vertically to the bottom of
the appliance firebox.

3.1 ROOM SIZING

4.0 SITE REQUIREMENTS

This appliance is designed to be
wall-hung. Do not recess any part
of the appliance into the wall.

WARNING

Summary of Contents for CORINTHIA BLACK NG

Page 1: ...thout the prior written permission of Focal Point Fires plc 1 Revision A 10 11 2011 Focal Point Fires plc The products covered by this booklet are protected under patent GB2275331C GB IE BS EN 14829 2007 KM579167 Superior Fires Christchurch Dorset BH23 2BT Tel 01202 588 632 Fax 01202 499326 www superiorfires co uk e info superiorfires co uk INTHE UK ALWAYS USE A GAS SAFE REGISTERED ENGINEERTO INST...

Page 2: ...sed in a room without some form of background heating present If the appliance is used in a room as the sole source of heat then condensation may occur on colder surfaces within the room On first light up of a new appliance burning off of high temperature paint and lubri cants may occur for the first few hours of operation During this period some smoke may be emitted from the outlet grille this sh...

Page 3: ...t ft3 by 35 3 This appliance may be installed in any room in the home except bathrooms In accordance with BS5871 part 4 installation in bed rooms is permitted If the appliance is to be installed in a bedroom then an electronic carbon monoxide detector complying with the current edition of BSEN 50291 must be installed in the same room as the appliance For maximum safety it is recommended that such ...

Page 4: ...y cause cracking along the joint line If the appliance is to be mounted on a dry lined wall or a timber framed construction wall then the integrity and ability of the wall to carry the weight of the appliance must be confirmed It is important in these circumstances that any vapour control bar rier is not damaged and that any structural members of the house frame are not damaged refer to section 7 ...

Page 5: ...only on a vertical surface Avoid sloped surfaces Installation onto anything other than a vertical wall may result in fire damage or injury If the appliance is to be mounted on the inner leaf of a conventional cavity brick wall or a solid wall then the wall plugs and fixing screws provided may be used Depending on the condition of the wall it may be necessary to use additional fixings In this situa...

Page 6: ... approximately ten seconds Now release the knob and the pilot should stay alight If the pilot is extinguished during use wait three minutes before repeating the ignition procedure To achieve the HIGH setting push the control knob in slightly and continue turning fully anti clockwise to the high position The main burner should light after a few seconds To decrease the setting to low turn the contro...

Page 7: ...is cold using a damp cloth and mild detergent on most surfaces Advise that on first light up of a new appliance initial curing of high temperature paint and burning off of lubricants may occur for the first few hours of operation During this period some smoke may be emitted from the outlet grille this should be no cause for concern Accordingly the room should be well ventilated with all windows an...

Page 8: ...he catalysts are inspected for signs of damage and dirt during routine servicing procedures The expect ed life of the catalysts is in excess of 11 000 hours 10 years of normal use After this time the catalysts should be replaced If there are any deposits of dirt or soot on the catalyst they should be cleaned with a soft brush and a vacuum cleaner If removed for cleaning ensure the seals are in goo...

Page 9: ...ere is a draft Fire is too close the an air vent Fire is sited on disused chimney breast which has not been adequately sealed up Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If the pilot will not stay lit there could be a problem with contamination of the gas supply drafts room size and or ventilation or the thermocouple needs replacement Modifications are dangerous an...

Page 10: ...ucts The expected life of the catalyst is in excess of 11 000 hours 10 years of normal use After this time the catalyst should be replaced Should any home improvements be carried out to the property after the fire is installed such as installation of extractor fans for example the fire should be re checked by a competent person for safe operation U S E R I N S T R U C T I O N S 2 0 CLEARANCES TO C...

Page 11: ...e discoloured This appliance is intended as a secondary source of heat only and should not be used in a room without some form of background heating present If the appliance is used in a room as the sole source of heat then condensation may occur on colder surfaces within the room This appliance must not be used in bathrooms Refer to section 4 0 of the installation manual for guidance on installat...

Page 12: ...ridiana and Merrion models TRAY116 Burner unit Corinthia models TRAY111 Burner unit Meridiana and Merrion models F780079 Catalyst seal kit must also be supplied F940136 Seal kit for Catalyst 7 0 SERVICING 8 0 LIST OF REPLACEMENT PARTS 9 0 INSTALLATION DETAILS Installer GAS SAFE registration No Model Fire serial No Name contact details of installer Supplied by 10 0 SERVICE HISTORY Date of service S...

Reviews: