background image

Superiorfireplaces.US.com

127055-01C

6

FIREPLACE INSTALLATION 

Continued

Figure 3 - Hearth Extension

Fireplace Front

Fireplace Front 

Raised Hearth

Fireplace Front 

Elevated

Seal Gap

Seal Gap

Ember Protector

Ember Protector

Ember Protector

Hearth 

Extension

Hearth Extension, Noncirculating Models

 WARNING: Hearth extension is to be installed 

only as shown in Figure 3.

FIREBOX

SAFE ZONE

Top View of Fireplace

Min. 12" from 

Perpendicular Side Wall

3"

2" Max.

33°

8"

MANTELS

A mantel may be installed if desired (see Figures 4 and 5). Woodwork 

such as wood trims, mantels or any other combustible material 

projecting from front face, must not be placed within 12" of fireplace 

opening and within 9" of top louver opening. Combustible materials 

above 12" and projecting more than 1 1/2" from fireplace must not 

be placed less than 12" from top opening of fireplace (NFPA 211, 

Section - Clearance from Combustible Material).

Mantels or any other combustible material may come up to side edge 

of black metal face of fireplace if projection from front face falls within 

limits shown in Figure 4.

Figure 4 - Mantel Clearances to Combustible Material 

12 

1

/

4

" Ref.

6"

Ref.

15" Min.

12" Min.

1

1

/

2

" Max.

3" Nom.

33°

Combustible 

Material

Safe 

Zone for 

Projection of 

Combustible 

Materials

Fireplace Opening

Non-Combustible 

Materials Below 

Top Spacer

Upper 

Section of 

Fireplace

DRAIN PAN (DP42)

For outdoor installations, the fireplace enclosure must allow for 

adequate drainage and fresh air ventilation. It is recommended that 

a sealed, corrosion resistant catch pan with provision for drainage 

be installed under the fireplace within the fireplace enclosure (see 

Accessories, page 18).

HEARTH EXTENSION

A hearth extension projecting a minimum of 20" in front of and a 

minimum of 12" beyond each side of fireplace opening is required 

to protect combustible floor construction in front of fireplace. Fab-

ricate a hearth extension using a material which meets the following 

specifications: a layer of noncombustible, inorganic material having 

a thermal conductivity of k = .84 BTU IN/FT

2

 HR °F (or less) at 1" 

thick. For example, if material selected has a k factor of 0.25, such 

as glass fiber, the following formula would apply:
  0.25 x 1.0" = 0.30" thickness required

 0.84
Thermal conductivity "k" of materials can be obtained from manu-

facturer or supplier of noncombustible material. If hearth extension 

is to be covered, use noncombustible material such as tile, slate, 

brick, concrete, metal, glass, marble, stone, etc. Provide a means to 

prevent hearth extension from shifting and seal gap between fireplace 

frame and hearth extension with a non-combustible material such 

as sand-cement grout (see Figure 3).

Summary of Contents for WRE3036RH

Page 1: ...explosion may result causing property damage personal injury or death AVERTISSEMENT Assurez vous de bien suivre les instructions donn es dans cette notice pour r duire au minimum le risque d incindie...

Page 2: ...er control b Use of any component part not manufactured or approved by IHP in combination with an IHP fireplace system Proper installation is the most important step in ensuring safe and continuous op...

Page 3: ...treat insects and fungus When burned thesechemicalscanposeasignificanthazard WARNING BURNING IMPROPER FUEL I E CHARCOAL CAN RESULT IN CARBON MONOXIDE POISONING WHICH MAY LEAD TO DEATH Carbon Monoxide...

Page 4: ...COMBUSTIBLE WALL BOARD TOP SPACERS 0 TO 1 AIRSPACE TO COMBUSTIBLE MATERIAL NO COMBUSTIBLE MATERIAL ON FACE NO COMBUSTIBLE MATERIAL BELOW TOP SPACERS GAS LINE KNOCK OUT AIR KIT KNOCK OUTS GAS LINE STA...

Page 5: ...Height for Outdoor Installation The minimum height of the chimney measured from the base of the fireplace to the flue gas outlet of the termination is 8 feet minimum of 4 feet of chimney pipe sections...

Page 6: ...f Combustible Materials Fireplace Opening Non Combustible Materials Below Top Spacer Upper Section of Fireplace DRAIN PAN DP42 For outdoor installations the fireplace enclosure must allow for adequate...

Page 7: ...gained after fitting overlaps must be taken into consideration lineal gain and are given in lineal gain chart see Figure 6 Lineal gain is actual measurable length of a part after two or more parts are...

Page 8: ...R 30 Offset return elbow A section or sections of chimney may be used between offsets and return elbow Transition pipe must be used after elbow offset is attached 1 To achieve desired offset you may i...

Page 9: ...ntinued Figure 8 Typical Offset Installation 30E 8DM Return Elbow 30E 8DM Return Elbow 30E 8DM Offset Elbow 30E 8DM Offset Elbow 30E 12DMO 8DMR Offset Elbow 30E 12DMO 8DMR Offset Elbow 30E 12DMO 8DMR...

Page 10: ...ening into a living space above firestop must be placed onto ceiling from below as shown in Figure 10 They also provide complete separation from one floor space to an other or attic space as required...

Page 11: ...aterial use only noncombustible mortar or adhesive Storm Collar Installation SC1 Place storm collar over pipe and slide down until it is snug against open edge of flashing see Figure 14 Use SC1 for al...

Page 12: ...ne conduit sleeve if using a raised platform add height Provide sufficient gas line into fireplace chamber for fitting OPTIONAL GAS LINE INSTALLATION VENTING INSTALLATION Continued connection see Figu...

Page 13: ...lass WARNING FIREPLACESEQUIPPEDWITHDOORS SHOULD BE OPERATED ONLY WITH DOORS FULLY OPENORDOORSFULLYCLOSED IFDOORSARELEFT PARTLYOPEN GASANDFLAMEMAYBEDRAWNOUT OF THE FIREPLACE OPENING CREATING RISKS OF B...

Page 14: ...t These coverplatesmustbekeptintheproperlocationpriortousingthefireplace See Figure 23 For further operating guidelines instructions and warranty informa tion please refer to your homeowner s guide or...

Page 15: ...Refractory Textured Red Herringbone 1 11 107816 03 Rear Refractory Textured White Brick 1 108171 03 Rear Refractory Textured White Herringbone 1 107816 02 Rear Refractory Textured Red Brick 1 108171...

Page 16: ...27 4 32 34 19 12 25 20 30 17 8 1 5 21 2 35 18 11 14 3 13 22 10 6 39 31 7 37 38 36 28 29 24 23 15 PARTS WOOD BURNING FIREPLACE MODELS WRE3042WS WRE3042WH WRE3042RS WRE3042RH MODEL NO CATALOG NO WRE3042...

Page 17: ...ge 15 Bottom Rear Refractory 1 13 See Page 15 Bottom Front Refractory 1 14 106683 01 Firebox Support Leg 4 15 Damper Can Collar 1 16 107839 01 Screen Rod 2 17 Firebox Top Assembly 1 18 106703 01 Air K...

Page 18: ...WITH SLIP SECTION RTT 8DM MESH ROUND TOP TERMINATIONS WITH SLIP SECTION RTTL 8DM ACCESSORIES DOUBLE WALL PIPE 12 8DM 12 8HT 18 8DM 18 8 HT 24 8DM 24 8HT 36 8DM 36 8HT 48 8DM 48 8HT ROOF FLASHING 0 TO...

Page 19: ...delivery services IMPORTANT NOTICE A manufactured shroud which has been approved by a national testing agency for use with this fireplace may be used if installed in accordance with the instruc tions...

Page 20: ...n design materials specifications pricesandalsotodiscontinuecolors stylesandproducts Consult your local distributor for fireplace code information Printed in U S A 2013 IHP LLC P N 127055 01 Rev C 06...

Reviews: