background image

SuperiorFireplaces.us.com

901009-00_NC

7

AIR FOR COMBUSTION AND VENTILATION

Confined and Unconfined Space

The 

National Fuel Gas Code, ANSI Z223.1/NFPA 54

 allows two meth-

ods for determining whether the space in which the heater is being 

installed is confined or unconfined. The standard method defines a 

confined space as a space whose volume is less than 50 cubic feet 

per 1,000 Btu per hour (4.8 m3 per kw) of the aggregate input rating 

of all appliances installed in that space and an unconfined space as 

a space whose volume is not less than 50 cubic feet per 1,000 Btu 

per hour (4.8 m3 per kw) of the aggregate input rating of all appli-

ances installed in that space. Rooms communicating directly with the 

space in which the appliances are installed*, through openings not 

furnished with doors, are considered a part of the unconfined space.
Where the air infiltration of a structure is known, the Known Air 

Infiltration Rate Method may be used. Follow the 

National Fuel Gas 

Code, ANSI Z223.1/NFPA 54

 to use this method to determine if the 

space is confined or unconfined.
* Adjoining rooms are communicating only if there are doorless 

passageways or ventilation grills between them.

DETERMINING FRESH-AIR FLOW FOR FIREBOX LOCATION
Determining if You Have a Confined or Unconfined Space using 

the standard method

Use this work sheet to determine if you have a confined or uncon-

fined space.

Space:

 Includes the room in which you will install heater plus any 

adjoining rooms with doorless passageways or ventilation grills be-

tween the rooms.
1.  Determine the volume of the space (length x width x height).
  Length x Width x Height =__________cu. ft. (volume of space)
 

Example:

 Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling 

height) = 3,168 cu. ft. (volume of space)

  If additional ventilation to adjoining room is supplied with grills 

or openings, add the volume of these rooms to the total volume 

of the space. 

2.  Multiply the space volume by 20 to determine the maximum Btu/Hr 

the space can support.

   _______ (volume of space) x 20 = (Maximum Btu/Hr the space 

can support)

 

Example:

 3,168 cu. ft. (volume of space) x 20 = 63,360 (maximum 

Btu/Hr space can support)

3.  Add the Btu/Hr of all fuel burning appliances in the space.
 

Vent-free  fireplace   ________Btu/Hr

  Gas water heater*   ________Btu/Hr
  Gas furnace 

  ________Btu/Hr

  Vented gas heater   ________Btu/Hr
  Gas fireplace logs   ________Btu/Hr
  Other gas appliances*  Btu/Hr
 Total 

= _______Btu/Hr

  * Do not include direct-vent gas appliances. Direct-vent draws 

combustion air from the outdoors and vents to the outdoors.

 

Example:

  Gas water heater       40,000 Btu/Hr
  Vent-free fireplace  +  39,000 Btu/Hr
  Total 

=   79,000 Btu/Hr

 WARNING: This heater shall not be installed in a 

room or space unless the required volume of indoor 

combustion air is provided by the method described 

in the 

National Fuel Gas Code, ANSI Z223.1/NFPA 54,

 

the 

International Fuel Gas Code,

 or applicable local 

codes. Read the following instructions to ensure proper 

fresh air for this and other fuel-burning appliances in 

your home.

Today’s homes are built more energy efficient than ever. New materials, 

increased insulation and new construction methods help reduce heat 

loss in homes. Home owners weather strip and caulk around windows 

and doors to keep the cold air out and the warm air in. During heating 

months, home owners want their homes as airtight as possible.
While it is good to make your home energy efficient, your home ne eds 

to breathe. Fresh air must enter your home. All fuel-burning appliances 

need fresh air for proper combustion and ventilation.
Exhaust fans, fireplaces, clothes dryers and fuel burning appliances 

draw air from the house to operate. You must provide adequate fresh 

air for these appliances. This will ensure proper venting of vented 

fuel-burning appliances.

PROVIDING ADEQUATE VENTILATION

The following are excerpts from 

National Fuel Gas Code, ANSI 

Z223.1/NFPA 54, Air for Combustion and Ventilation

.

All spaces in homes fall into one of the three following ventilation 

classifications:
1.  Unusually Tight Construction
2.  Unconfined Space
3.  Confined Space
The information on pages 8 through 10 will help you classify your space 

and provide adequate ventilation.

Unusually Tight Construction

The air that leaks around doors and windows may provide enough 

fresh air for combustion and ventilation. However, in buildings of 

unusually tight construction, you must provide additional fresh air.

Unusually tight construction is defined as construction where:
a.  walls and ceilings exposed to the outside atmosphere have a 

continuous water vapor retarder with a rating of one perm (6 x 

10

-11

 kg per pa-sec-m

2

) or less with openings gasketed or sealed 

and

b.  weather stripping has been added on openable windows and 

doors and

c.  caulking or sealants are applied to areas such as joints around 

window and door frames, between sole plates and floors, be-

tween wall-ceiling joints, between wall panels, at penetrations 

for plumbing, electrical and gas lines and at other openings.

If your home meets all of the three criteria above, you must provide 

additional fresh air. See 

Ventilation Air From Outdoors

, page 10. 

If your home does not meet all of the three criteria above, proceed 

to 

Determining Fresh-Air Flow For Firebox Location

.

Summary of Contents for VRT6036

Page 1: ...ult causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instru...

Page 2: ...material on or near the appliance Never place any objects in the firebox or on logs Firebox front and screen becomes very hot when run ning firebox Keep children and adults away from hot surfaces to avoid burns or clothing ignition Firebox will remain hot for a time after shutdown Allow sur faces to cool before touching Carefully supervise young children when they are in the room with firebox WARN...

Page 3: ... firebox with care Follow all local codes In the absence of local codes use the latest edition of The National Fuel Gas Code ANSI Z223 1 NFPA 54 Firebox must be electrically grounded in accordance with the National Electrical Code ANSI NFPA70 latest edition Available from American National Standards Institute Inc 25 West 43rd Street 4th floor New York NY 10036 National Fire Protection Association ...

Page 4: ...0_NC 4 PRODUCT SPECIFICATIONS 36 MODEL Figure 1 36 Model VRT6036 Picture may vary from actual firebox 30 1 2 29 30 11 1 8 54 1 2 7 7 8 7 36 45 1 8 35 16 97 16 50 365 16 7 3 8 111 8 3 3 4 4 7 8 36 HEARTH 1 1 4 20 1 4 Ref 35 1 4 19 22 1 2 ...

Page 5: ...RODUCT SPECIFICATIONS Continued 42 MODEL Figure 2 42 Model VRT6042 Picture may vary from actual firebox 4 7 8 54 1 2 7 7 8 7 36 5 16 50 42 51 1 8 32 3 8 3 3 4 30 5 16 8 3 4 13 3 5 16 9 7 16 30 11 1 8 42 HEARTH 1 1 4 23 Ref 41 3 8 26 3 8 21 3 4 ...

Page 6: ... PRODUCT SPECIFICATIONS Continued 50 MODEL Figure 3 50 Model VRT6050 Picture may vary from actual firebox 365 16 50 8 3 4 13 35 16 97 16 59 1 8 50 7 7 8 7 30 54 1 2 11 1 8 32 3 8 3 3 4 38 5 16 4 7 8 50 HEARTH 1 1 4 23 Ref 49 3 8 34 3 8 21 3 4 ...

Page 7: ...utdoors and vents to the outdoors Example Gas water heater 40 000 Btu Hr Vent free fireplace 39 000 Btu Hr Total 79 000 Btu Hr WARNING This heater shall not be installed in a room or space unless the required volume of indoor combustion air is provided by the method described in the National Fuel Gas Code ANSI Z223 1 NFPA 54 the International Fuel Gas Code or applicable local codes Readthefollowin...

Page 8: ...FuelGasCode orapplicablelocalcodes Figure 4 Ventilation Air from Inside Building Or Remove Door into Adjoining Room Option 3 Ventilation Grills Into Adjoining Room Option 2 Ventilation Grills Into Adjoining Room Option 1 12 12 VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to an adjoining unconfined space you must ...

Page 9: ...ES WARNING Maintain the minimum clearances If you can provide greater clearances from floor ceil ing and adjoining wall INSTALLATION Carefully follow the instructions below This will ensure safe instal lation Minimum Wall and Ceiling Clearances see Figure 6 A Clearances from the side of the fireplace cabinet to any combus tible material and wall should follow diagram in Figure 6 Example The face o...

Page 10: ...ust follow the clearances shown in Figure 7 Follow these instructions to install the firebox in this manner 1 Frame in rough opening The firebox framing should be constructed of 2 x 4 lumber or heavier Use dimensions and rough opening lay out in Figure 8 Adjust framing so that firebox flushes with finished wall surface If installing in a corner use dimensions in Figure 9 for rough opening 2 Instal...

Page 11: ...binet mantel against a wall in your home The firebox and cabinet mantel can be installed directly on the floor Mantels may be available from your retailer or custom built for your home 1 Assemble cabinet mantel as instructed 2 Install gas piping to firebox location See Gas Line Installation on page 14 You may have to cut an access hole in the floor or wall to run gas line to firebox Make sure to l...

Page 12: ...th and Leading Brick panels Hearth Panel Side leading brick Panel 3 Install the left and right firebrick walls There is a bracket with 2 tabs on the bottom of each firebrick wall Angle the wall into the fireplace opening and into the slots on the side of the hearth Fig ure 14 then tilt the top of the panel toward the firebox surround Figure 14 Slots for Firebrick Walls Figure 15 Installing Side an...

Page 13: ...e smaller opening is downward and over a moist towel to avoid spilling Place a wet towel over the bucket making sure it is directly on the surface of grout mixture This will keep the mixture moist and it will not dry out before use 5 Grout all joints where two firebrick walls come together 6 Using a trowel remove excess grout mixture by moving trowel in the direction of the joint Grout mixture in ...

Page 14: ... Fitting Connection Figure 19 Gas Line Installation Side Firebrick Finished Side Brick with Access Hole Outside of Fireplace Gas Line Conduit Insulation Gas Conduit Cover 1 2 Dowel Remove Knockout GAS LINE INSTALLATION CAUTION All gas piping and connections must be tested for leaks after the installation is completed After ensuring that the gas valve is on apply soap and water solution to all conn...

Page 15: ...6 to 18 for a complete replacement parts list Use only parts supplied from the manufacturer Normally all parts should be ordered through your IHP distributor or dealer Parts will be shipped at prevailing prices at time of order When ordering repair parts always give the following information 1 The model number of the fireplace 2 The serial number of the fireplace 3 The part number 4 The descriptio...

Page 16: ...SuperiorFireplaces us com 901009 00_NC 16 PARTS VRT6036 VRT6042 AND VRT6050 MODELS 11 10 11 13 14 15 16 14 3 20 20 21 1 19 5 14 15 16 13 12 11 9 7 6 8 17 2 12 18 4 ...

Page 17: ...replace Top 42 1 Fireplace Top 50 1 9 J6997 Standoff 4 10 Fireplace Surround Assembly 1 11 J4362 Clearance Spacer 6 12 J5329 Fireplace Handle Bracket 4 13 J6900 Outside Air Cover Plate 2 14 J6934 Gas Conduit Cover 4 15 J4368 Conduit One 2 16 J4369 Conduit Two 2 17 Heat Shield Support 1 18 Firebox Top 1 19 J4342 Screen 36 2 J4341 Screen 42 2 J4340 Screen 50 2 20 J6928 Screen Rod 36 2 J4391 Screen R...

Page 18: ...it F0350 Mosaic50M2 Red Full Stacked F0351 Mosaic50M4 Red Split Stacked F0352 Mosaic50M2 Ivory Full Stacked F0353 Mosaic50M4 Ivory Split Stacked F0354 Mosaic50M3 Red Herr Full F0355 Mosaic50M5 Red Herr Split F0356 Mosaic50M3 Ivory Herr Full F0357 Mosaic50M5 Ivory Herr Split PARTS MOSAIC MASONRY BRICK KITS A Mosaic Masonry brick panel kit is required for use with your VRT6036 VRT6042 or VRT6050 Fir...

Page 19: ...atural or propane gas only Burning conventional fuels such as wood coal or any other solid fuel will cause damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions provided with the Product d damages repairs or inefficiency resulting from faulty installation ...

Page 20: ...01009 00 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications prices and also to discontinue colors styles and products Consult your local distributor for fireplace code information Printed in U S A 2019 Innovative Hearth Products LLC P N 901009 00 Rev NC 07 2019 1769 East Lawrence Street Russellville AL 35654 ...

Reviews: