28
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
Installation and Operation Instructions
900299-00, 05/2016
Innovative Hearth Products
DRT40 Multi-View Series Direct-Vent Gas Fireplace
VERTICAL OR HORIZONTAL VENTING USING
SECURE FLEX
®
KITS AND COMPONENTS
Secure Flex
®
venting kits and components may
be used in any venting application where rigid
Secure Vent
®
(SV4.5) Direct-Vent components
can be used. All restrictions, clearances and
allowances that pertain to the rigid piping apply
to the flexible venting.
Secure Flex
kits may
not be modified; also, under no circumstances
may separate sections of flex pipe be joined
together. Secure Flex kits may be added to
the end of a vent run made up of rigid Secure
Vent (SV4.5) vent sections provided that doing
so does not violate any of the venting length,
height, routing, horizontal to vertical ratio re-
quirements or clearance considerations detailed
in this manual.
Secure Flex kits come with an included adaptor
that can be fitted to the appliance collar or the
inclined channel end of the last Secure Vent
(SV4.5) vent section in a rigid system in the
exact same fashion as any other Secure Vent
section. Align the dimpled end of the adaptor
over the previously installed section or appliance
collar, adjusting the radial alignment until the
four locking dimples of the adaptor are aligned
with the inlets of the four incline channels of
the last vent section or collar. Push on the
adaptor until it fully engages, then twist the
adaptor clockwise running the dimples down
and along the incline channels until they seat
at the end of the channels.
Attach the flexible vent to the adaptor as fol-
lows
(see Figure 49)
:
A. Install the Inner Flex Pipe -
1. Install the small gear clamp loosely around
the inner flexible vent pipe, push it back out
of the way.
2. Apply a bead of Mill-Pac Black (700°F) high
temperature sealant - Catalog No. 10K81)
to the inner adaptor collar, approximately
1/2" from the end.
3. Pull and extend the inner flexible vent pipe.
4. Slide the inner flex pipe over the adaptor col-
lar. Ensure the flexible vent pipe completely
engages the adaptor collar to a distance of
1-3/4" from the end, and that it is free from
damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adaptor
inner collar approximately 3/4" from the end
of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the
adaptor collar just below the gear clamp to
provide additional security to the connection.
B. Install the Outer Flex Pipe -
1. Install the large gear clamp loosely around
the outer flexible vent pipe, push it back out
of the way.
2. Apply a bead of Mill-Pac Black (700°F) high
temperature sealant - Catalog No. 10K81)
to the outer adaptor collar; to the grooves
of the collar which extend approximately 1
inch from the end and to the flat surface,
approximately 1-3/8" from the end.
3. Pull and extend the outer flexible vent pipe.
4. Slide the outer flex pipe over the adaptor col-
lar. Ensure the flexible vent pipe completely
engages the adaptor collar to a distance of
1-3/8" from the end, and that it is free from
damage or tears.
5. Slide the gear clamp down and tighten it
fully to secure the flexible vent to the adaptor
outer collar approximately 3/4" from the end
of the flex.
6. Install three screws 120 degrees apart
through the flexible vent pipe and into the
adaptor collar just below the gear clamp to
provide additional security to the connection.
C. Route Flex Vent -
Ensure that the flex vent is properly routed to
provide the required clearance. Do Not allow
the flexible vent to bend in a radius tighter than
5" (127 mm). Refer to
Figure 50
. Support
horizontal sections of flex with metal straps at
2 foot (0.61 m) intervals.
D. Install Firestop/Spacers at ceilings and walls -
When Secure Flex penetrates a wall or ceiling,
a firestop/spacer is required: use the SF4.5 VF
firestop/spacer for ceilings and the SF4.5 HF
firestop/spacer for walls.
Figure 49
GEAR
CLAMPS
Adaptor
(SV4.5RF)
Apply ONLY MIL-PAC BLACK HIGH
TEMPERATURE SEALANT (Catalog No.
10K81) to the outside surface of both
collars of the adaptor (be especially
careful to fill the grooves of the outer
collar to be covered by the flexible
pipe) and slide flexible pipe over
inner and outer adaptor collars.
NOTE: OUTER PIPE IS PULLED AWAY TO
SHOW THE DETAIL OF THE INNER PIPE
FLEX VENT
1-3/4” (44 mm)
Flexible Pipe and
Adaptor Outer
Collar Overlap
1-3/4” (44 mm)
Flexible Pipe and
Adaptor Inner
Collar Overlap
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
Attach Adaptor to Appliance
Collar, or Secure Vent Sections
SECURING SCREW
(3 PLACES EQUALLY SPACED
JUST BELOW GEAR CLAMP)
5" (127 mm)
Radius Minimum
Flexible Vent Section
E. Attach Flex Vent to Termination -
Secure Flex components can be purchased
separately and attached to bulk lengths of
Secure Flex flexible tubing cut to size at the
job site. Secure the flexible vent to the Secure
Flex terminations in the same manner (see
Figure 49)
as it was attached to the adaptor.
NOTE: Secure Flex vent must be attached
to Secure Flex terminations only. DO NOT
substitute Secure Vent terminations or the
Secure Vent adaptor for Secure Flex compo-
nents. The collars of Secure Flex terminations
and adaptors have a different circumference
than that used with the Secure Vent pipe.
Additionally, Secure Flex components have
an extended length center tube for use in
attaching the flexible vent.
See the appropriate sections and figures shown
throughout the venting section for their instal-
lation requirements.
Figure 50