background image

 

10

 
7.0. 

MAINTENANCE 

To  ensure  maximum  life  of  the  equipment,  the 
following  should  be  part  of  an 

annual 

maintenance 

program. 
 

Warning 
De-energize  unit  before  performing  maintenance. 
Voltages  are  present  inside  this  unit  which  can 
cause injury. Therefore, only personnel qualified to 
service  electrical  equipment  should  perform 
maintenance on this unit. 

 

7.1. 

Vacuum  the  voltage  regulator  inside  and  out  to 

remove  accumulated  dirt,  which  could  lead  to 
overheating or insulation failure. 
 

7.2. 

Tighten  all  electrical  connections,  particularly  all 

power wiring to, and in, the unit. 
 

7.3. 

Inspect  all  variable  transformer  brushes  and 

commutators  for  signs  of  wear  or  pitting.  Replace  as 
required. See diagram below. 
 

 

 

Do  not  attempt  to  clean  a  commutator  with  an 
abrasive  such  as  sandpaper  or  a  file. 

This  will  ruin 

the  soft  precious  metal  plating  on  the  commutator  and 
will  shorten  the  life  of  the  unit.  It  is  normal  for 
commutators  to  become  black  due  to  carbon  brush 
tracking.  If  a  commutator  is  to  be  cleaned,  use 
denatured alcohol and a soft cloth. 
 

7.4. 

Inspect  the  variable  transformer  drive  belts, 

sprockets,  gears,  cams,  etc.  for  signs  of  slippage  or 
wear and adjust as required. 
 

7.5. 

Check  the  variable  transformer  radiator(s)  (the 

die cast part that holds the brush assembly) for signs of 
slippage,  and  see  if  all  brushes  driven  by  the  same 
motor are aligned with each other. The alignment of the 
radiator  and  brushes  depends  on  the  setscrews  that 
hold the variable transformer center tube(s) to the shaft 
and  the  setscrews  that  hold  the  radiator  to  the  center 
tube. Adjust and tighten as needed. 
 

7.6. 

Lubrication  of  the  WHR  Series voltage regulator 

is  not  required  since  it  has  been  lubricated  at  the 
factory for its lifetime. 
 

8.0. 

TROUBLESHOOTING 

WHR  Series  voltage  regulators  will  provide  long, 
reliable  service  with  little  attention.  Unless  the  unit  is 
overloaded,  there  is  little  likelihood  of  component 
failure. 
 

Warning 
Voltages  are  present  inside  this  unit  which  can 
cause injury. Therefore, only personnel qualified to 
service  electrical  equipment  should  perform 
trouble-shooting procedures on this unit. 

 
If  the  regulator  fails  to  operate  correctly,  the  following 
checks  will  help  locate  and  correct  the  problem.  Refer 
to the schematic, rating chart and replacement parts list 
for further information. 
 

8.1. 

Check  the  load  connected  to  the  voltage 

regulator  to  be  sure  the  unit's  output  current  rating  is 
not being exceeded. 
 

8.2. 

See  if the POWER pilot lamps are on. If a lamp 

is not on, there is no power to the voltage regulator, or 
control  module  fuses  F1  and  F2  (POWER  fuses)  are 
blown, or the lamp has burned out. Check the POWER 
fuses (F1 and F2). Check the power input to the unit to 
be sure the voltage is within the range specified for the 
selected output voltage. 
 

8.3. 

Check  the  output  voltmeters.  If  a  meter  shows 

zero  output  voltage,  check  the  input  line,  control 
module  fuses  F3  and  F4  (CONTROL  fuses),  remote 
sense  wiring  if  applicable,  and  input  connections.  If  so 
equipped,  check  position  of  input  circuit  breaker  and 
manual bypass switch. 
 

8.4. 

Check  the  CONTROL  pilot  lamps.  If  one  is  not 

lit,  check  it's  VOLTAGE  RANGE  switch  to be sure it is 
on  and  check  for  blown  CONTROL  fuses  (F3 and F4). 
If applicable, check the remote sense wiring. 
 

8.5. 

If the motor hunts (cycles continuously), readjust 

the SENSITIVITY control. 
 

8.6. 

If  a  motor  drives  a  POWERSTAT  variable 

transformer  to  one  end  of  its  travel,  and  the  voltage 
decreases when it should increase or increases when it 
should  decrease,  check  to  see  if  the  input  and  output 
power  connections  to  the  voltage  regulator  are 
reversed. If applicable, check the remote sense wiring. 
 

8.7. 

If  the  unit  has  been  reworked or repaired, check 

to  see  if  the  leads  driving  the  motor  have  been 
reversed.  A1-TB1-2  and  A1-TB1-3  provide  the  motor 
power to lower and raise the motor with A1-TB1-1 being 
the common for both AC voltages.  
 

Summary of Contents for STABILINE WHR34 S Series

Page 1: ...R64 S WHR94 S WHRS34 S WHRS64 S or WHRS94 S Superior Electric reserves the right to make engineering changes on all its products Such refinements may affect information given in the instructions Therefore USE ONLY THE INSTRUCTIONS THAT ARE PACKED WITH THE PRODUCT WARNING High voltages are present inside this unit during operation Do not operate this unit unless all covers are in place Installation...

Page 2: ...2 ...

Page 3: ... The Damage and Shortage instructions packed with the unit outlines the procedure to follow if any parts are missing or damaged 2 0 DESCRIPTION 2 1 GENERAL WHR34 S Series STABILINE Automatic Voltage Regulators are three phase 380Y 220 X 480Y 277 volt fast acting electromechanical regulators These WHR Series voltage regulators regulate one line to line voltage and correct all phases by the same amo...

Page 4: ... S Single Control D Double Control T Triple Control LNN Size Code 3 or 4 digits R Rack Cabinet T Tall Cabinet CB Input Circuit Breaker CS Input Circuit Breaker w 120vac Shunt Trip CR Input Circuit Breaker w 120vac Under voltage Trip Release D Delayed Output M Manual Bypass Switch T Tropicalization Treatment 0 No Meter Options 1 Ammeter s 2 Frequency Meter w Alarm Contacts 3 Both 1 2 above 0 No Ala...

Page 5: ...vided in the base and the rear panel of the unit for wire entry and exit The location of the power connections varies depending on the options provided On units with an input circuit breaker input connections are made directly to the circuit breaker On units without any options the input connections are located on the POWERSTAT variable transformer The input power connections are labeled L1 L2 and...

Page 6: ...lator should not be operated without the front panel s of the cabinet in place However during the initial operation of the regulator the front panels can be removed to allow setting the OUTPUT VOLTAGE and SENSITIVITY potentiometers 5 2 1 Energize Regulator On units equipped with a manual bypass switch ensure it is in the REGULATOR position Energize the regulator power source and place the input ci...

Page 7: ...ge release coil This coil allows the circuit breaker to close when voltage is applied and opens the breaker if the coil voltage is lost The trip coil is rated 120 volt AC The coil voltage must be present in order to close the circuit breaker 6 2 1 3 Circuit Breaker Trip Coil Alarm Contacts When alarm contact options and a circuit breaker trip option are ordered together the unit is furnished with ...

Page 8: ...n the factory setting can be reinstated by pressing both RECALL buttons at the same time The stored factory settings are shown in the table below To return the stored settings to the factory defaut tap the ENTER key to go to the next feature then use SET and ADVANCE keys to change the setting to those shown below When the display shows Store tap the Enter key to lock the setting into memory If no ...

Page 9: ...but will not correct high input voltages Since operation in the all boost mode will increase the voltage and heating in the WHR regulator the rated load current and in some cases the maximum rated nominal input voltage must be reduced Refer to the All Buck and All Boost Rating Chart for the all boost ratings For all boost operation the input line to each POWERSTAT variable transformer must be move...

Page 10: ...less the unit is overloaded there is little likelihood of component failure Warning Voltages are present inside this unit which can cause injury Therefore only personnel qualified to service electrical equipment should perform trouble shooting procedures on this unit If the regulator fails to operate correctly the following checks will help locate and correct the problem Refer to the schematic rat...

Page 11: ...e motor at the end of travel If the motor operates successfully in this test the problem may be with the control board 8 10 Inspect the POWERSTAT Variable Transformer brush es and commutator s for signs of wear or damage The brush assemblies on the variable transformer section will not need replacement under normal conditions When excessive brush wear or commutator damage occurs it is usually the ...

Page 12: ...UT VOLTAGE 380Y 220 X 480Y 277 FREQUENCY 50 60 Hz X 60 Hz CONNECTION 3 Phase 4 Wire Wye RANGE 20 to 10 of Selected Output OUTPUT VOLTAGE 380Y 220 X 480Y 277 CONNECTION 3 Phase 3 or 4 Wire Model Number base unit Rated Load Max Input Amps Amps kVA at 380 V 480 V WHR34NSR31 15 10 13 20 WHR34NSS31 28 18 23 35 WHR34NST31 65 43 54 80 WHR34NST32 130 85 105 160 WHR34NST33 195 125 160 240 WHR34NST34 260 17...

Page 13: ...tilated enclosures intended for indoor use under usual service conditions Temperature Operating Average ambient temperature for any 24 hour period not to exceed 30 C 86 F and maximum temperature not to exceed 40 C 104 F Average ambient temperature for any 24 hour period may be increased to 40 C 104 F and the maximum temperature may be increased to 50 C 122 F if the load is decreased to 90 of stand...

Page 14: ...ve a similar control module but some of the parts are specially treated and therefore have a different part number FLOOR MOUNT CONTROL MODULE ASSEMBLY A1 Standard Tropicalized Reference Symbol Part Description Part Number Part Number A1 CONTROL MODULE 213244 006 213244 010 A1 A1 CONTROL BOARD 227412 001 227412 001 SM A1 F1 F2 F3 F4 FUSE 600V 213274 001 A1 LP1 LP2 LIGHT INDICATOR GREEN 227571 001 A...

Page 15: ...REPLACEMENT BRUSH ASSEMBLY Each POWERSTAT Variable Transformer contains a durable brush assembly These assemblies are designed to reduce the need for attention or replacement however because these are moving parts that rely on contact friction to operate properly an annual inspection is suggested Refer to the maintenance section of this manual for details The replacement brush assembly is listed a...

Page 16: ...16 11 0 SCHEMATIC For reference only use full size supplied with unit ...

Page 17: ...17 12 0 FLOOR MOUNT DIMENSIONS Enclosures A through G Note All dimensions are inches millimeters ...

Page 18: ...18 Enclosures A through G continues Note All dimensions are inches millimeters ...

Page 19: ...19 Enclosures A through G continues Note All dimensions are inches millimeters ...

Page 20: ...20 Enclosures DPLUS through GPLUS Note All dimensions are inches millimeters ...

Page 21: ...21 Enclosures DPLUS through GPLUS continues Note All dimensions are inches millimeters ...

Page 22: ...22 Enclosures DD through GG Note All dimensions are inches millimeters ...

Page 23: ...23 Enclosures DD through GG continues Note All dimensions are inches millimeters ...

Page 24: ...24 Enclosures EEE through GGG Note All dimensions are inches millimeters ...

Page 25: ...25 Enclosures EEE through GGG continues Note All dimensions are inches millimeters ...

Page 26: ...seller network which offer literature technical assistance and a select range of models off the shelf for fastest possible delivery and service In addition Superior Electric Manufacturer s Representatives are available to provide prompt attention to customer needs Call or fax for ordering and application information or for the address of the closest Manufacturer s Representative Authorized Distrib...

Reviews: