9.2. GENERAL SPECIFICATIONS
Electrical:
Output Accuracy
Adjustable from ±1% to 3%
Load Capacity
100% rated continuous
200% rated 60 seconds
400% rated 3 seconds
600% rated 1 second
800% rated 0.5 second
1000% to 2500% 1/2 cycle inrush
Load Power Factor
0 lagging to 0 leading
Load Crest Factor
6 Max (I peak / I RMS)
Efficiency
97% typical, at full load
Heat Generated
BTU (typical) = 106 x rated kVA
Harmonic Distortion
Less than 1% added
Surge Withstand Capability
6000 volts per IEEE C62.41, location category B
Impedance
4% (typical)
Common-mode Attenuation
120 dB
Transverse-Mode Noise Attenuation
60 dB
Environmental:
Service Conditions
Units are housed in NEMA 1 ventilated enclosures, intended for indoor use under usual
service conditions.
Temperature
Operating
Average ambient temperature for any 24 hour period not to exceed 30°C (86°F), and
maximum temperature not to exceed 40°C (104°F). Average ambient temperature for any
24 hour period may be increased to 40°C (104°F),and the maximum temperature may be
increased to 50°C (122°F),if the load is decreased to 90%of standard rating. Minimum
temperature is 0°C (32°F).
Storage
-40°C to +70°C (-40°F to +158°F)
Humidity (Operating and Storage)
Units without tropicalization
10 to 75% average relative humidity for any 7 day period, and maximum relative humidity
not to exceed 95% non-condensing.
Units with tropicalization
10 to 95% average relative humidity and maximum relative humidity not to exceed 95%
non-condensing.
Altitude
Operating
Maximum Altitude
Derating
6,600 Ft.(2,000 meters)
No de-rating
10,000 Ft.(3,000 meters)
load to 95%,ambient 30°C (86°F)
15,000 Ft.(4,500 meters)
load to 90%,ambient 20°C (68°F)
Storage
50,000 Ft.(15,000 meters)max